Goodrive10 Series Mini VFD
Function parameters
-26-
P00 group Basic functions
Function
code
Name
Description
Default Modify
P00.00
Speed
control
mode
2:SVPWM control (suitable for asynchronous
motor)
2 is suitable in cases where it does not need
high control accuracy.
Note:
AM: asynchronous motor. Carry out motor
parameter autotuning before adopting vector
mode.
2
◎
P00.01
Channel of
running
commands
Select the channel of VFD running commands.
The control command of the VFD includes:
start-up, stop, forward, reverse, jogging and fault
reset.
0:Keypad (“LOCAL/REMOT” light off)
Carry out the command control by RUN,
STOP/RST on the keypad.
Set the multi-function key QUICK/JOG to
FWD/REV shifting function (P07.02=3) to
change the running direction; press
RUN and
STOP/RST
simultaneously in running state to
make the VFD coast to stop.
1:Terminal (“LOCAL/REMOT” flickering)
Carry out the running command control by the
forward rotation, reverse rotation and forward
jogging and reverse jogging of the multi-function
terminals
2:Communication (“LOCAL/REMOT” on)
The running command is controlled by the upper
monitor via communication
0
○
P00.03
Max.
output
frequency
The parameter is used to set the max. output
frequency of the VFD. It is the basis of
frequency setup and the
acceleration/deceleration.
Setting range: P00.04
–400.00Hz
50.00Hz
◎