Optidrive HVAC User Guide V2.00
24
www.invertekdrives.com
4
El
e
ct
ri
cal
In
st
al
la
tion
4.7.
Control Terminal Wiring
All analog signal cables should be suitably shielded. Twisted pair cables are recommended.
Power and Control Signal cables should be routed separately where possible, and must not be routed parallel to each other
Signal levels of different voltages e.g. 24 Volt DC and 110 Volt AC, should not be routed in the same cable.
Maximum control terminal tightening torque is 0.5Nm
Control Cable entry conductor size: 0.05 – 2.5mm
2
/ 30 – 12 AWG.
4.8.
Connection Diagram
4.8.1.
Power Terminal Designations
Incoming Mains Power
Supply
For 1 Phase Supply, connect
to L1/L and L2/N terminals.
For 3 Phase Supply, connect
to L1, L2 & L3 terminals.
Phase sequence is not
important.
Motor Connections
Connect the motor to the U, V & W
terminals.
The motor earth must be connected
to the drive
Protective Earth / Ground
connection.
The drive must be Earthed /
Grounded
4.8.2.
Control Terminal Connections & Factory Settings
Open
Closed
+24V Supply (100mA) / External Input
+24V
1
Digital Input 1
Stop
Run (Enable)
DIN1
2
Digital Input 2
Analog Input Ref
Preset Speed 1
DIN2
3
Digital Input 3
Analog Input 1
Ref
Analog Input 2
Ref
DIN3
4
Digital Inputs : 8 – 30 Volt DC
+ 10 Volt, 10mA Output
+10V
5
Analog Input 1
AIN1
6
0V
7
0V
Output Speed
Analog Output : 0 – 10 Volt / 4-20mA, 20mA Max
8
AOUT1
0 Volt Supply / External Input
0V
9
0V
Output Current
Analog Input 2
AIN2
10
Analog Output : 0 – 10 Volt / 4-20mA, 20mA Max
11
AOUT2
External Hardware Enable Circuit
EN+
12
EN-
13
Relay Contacts
250VAC / 30VDC
5A Maximum
14
RL1-C
Healthy
/ Fault
15
RL1-NO
16
RL1-NC
17
RL2-A
Running
18
RL2-B