10.7.2. Profibus Master Configuration
The latest applicable GSD file may be downloaded from the HMS website, www.anybus.com.
The actual configuration process will differ for different Profibus Master Systems and is not possible to explain in this document.
Example configurations for Siemens PLC are provided on the HMS website.
When configuring the communication between the Master System and the gateway, 4 words of Input Process Data and 4 words
of Output Process Data should be allocated per drive connected the gateway, up to a maximum of 32 Input and Output words. If
necessary, a configuration may be chosen in the Profibus Master which supports more than the connected number of drives, e.g. if 3
drives are connected to the gateway, the Master System can be configured for 12, 16 or even 32 words of Input and Output process
data. The additional words will simply not contain any data.
10.8. DeviceNet Gateway Features – OD-DEVNT-IN
Communications Adapter, profile no. 12
Group two server
Mac ID and baud rate configuration via on-board switches
Polled, Change-of-state and Bit strobed I/O
10.8.1. Installation
10.8.1.1. Overview - Module Front
Configuration Switches
Mac ID
Baud rate
LED Indicators
1
2
3
4
5
6
1
2
3
4
5
6
7
8
1
Network
Status
Off
Not online
Green
Link ok, online, connected
Flashing Green
Online, not connected
Red
Critical link failure
Flashing Red
Connection timeout
2
Module
Status
Off
No power
Green
Device operational
Flashing Green
Data size bigger than configured
Red
Unrecoverable fault
Flashing Red
Minor fault
3
Not Used
-
-
4
Not Used
-
-
5
Fieldbus
Diagnostics
Flashing Green
Running, but one or more transaction errors
Green
Running
Red
Transaction error / subnet stopped
6
Device Status Off
Power Off
Alternating Red / Green
Invalid / missing configuration
Green
Initialising
Flashing Green
Running
Red
Bootloader Mode
Flashing Red
Diagnostic Code
10.8.1.2. Configuration Switches – Baud Rate
Switch 1
Switch 2
Baud Rate
OFF
OFF
125k
OFF
ON
250k
ON
OFF
500k
ON
ON
N/A