| Fieldbus Guide |
Version 1.00
www.invertekdrives.com
6
Eth
ernet Connec
tion
6.2.4 Electrical Installation
WARNING!
Do not connect Ethernet devices to ports D1 or D2. They may be damaged!
Power supply to the module is provided from the connected drive via the RJ45 connection.
WARNING!
Do not use cross over cables! Cables must be pin to pin connected!
COMM
ERROR
P1 Ethernet P2
D1
MS
NS
D2
GND
Optional Drive Keypad
OPT-2-OPORT-IN
OPT-2-OPPAD-IN
RJ45 Cable
Maximum Length: 20 metres
OPT-ETHEG-IN
Ethernet IP Network
Ethernet IP Network
RJ45 Cable
Maximum Length:
3 metres
Optidrive
Ground tab – Observe the recommended grounding procedure for the fieldbus network and if necessary, connect this tab to ground
where required.
6.3. Internal Interface for IP66 Drives
6.3.1 Layout – Internal Interface
L1
L3
EMC
L2/N
U
V
W
1 2 3 4 5 6 7 8 9 10 11
I0I0I
I0I0I
IOIOI: Dual serial ports.
Warning! Do not connect Ethernet devices here!
These ports are for external serial connection of
remote keypad and PC connection only!
Port P1: Primary Ethernet port
Port P2: Secondary Ethernet Port
6.3.2 Labelling – Internal Interface
The MAC address of the device is shown below the ports.
o Additionally, this current level is used by the autotune to determine the correct inductance values.