Invertek Drives OPC-1-12075-1K012 Скачать руководство пользователя страница 1

 
 

User Guide 

 
 

Optidrive Plus 3

GV

 Compact

 

 

OEM AC Variable Speed Drive 
0.75 – 1.5kW (1 – 2HP) 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Installation and Operating Instructions

Для

 

заказов

 : +7(499)707-11-20 Email: [email protected]

8-800-511-65-88 (

Бесплатно

 

по

 

РФ

)

Содержание OPC-1-12075-1K012

Страница 1: ...User Guide Optidrive Plus 3GV Compact OEM AC Variable Speed Drive 0 75 1 5kW 1 2HP Installation and Operating Instructions 7 499 707 11 20 Email i sp t ru 8 800 511 65 88...

Страница 2: ...nts lectriques de puissance vitesse variable Exigences de CEM et m thodes d essais sp cifiques EN 55011 2007 Appareils industriels scientifiques et m dicaux ISM fr quence radio lectrique Caract ristiq...

Страница 3: ...ypad 9 5 2 Changing Parameters 10 5 3 Advanced Keypad Operation Short Cuts 10 5 4 Reset All Parameters to Factory Default Settings 10 5 5 Terminal Control 11 5 6 Keypad Control 11 5 1 Motor Autotuning...

Страница 4: ...equipment should comply with EN60204 Optidrives should be installed only by qualified electrical persons and in accordance with local and national regulations and practice The Optidrive has an Ingress...

Страница 5: ...put Current Fuse or MCB type B Supply Cable Size Nominal Output Current 150 Output Current 60 secs Motor Cable Size Max Motor Cable Length Amps Amps mm2 Amps Amps mm2 m OPC 1 12075 1KB12 0 75 1 12 5 1...

Страница 6: ...ounting The Optidrive Plus 3GV Compact is supplied in an IP20 enclosure designed to be mounted by the user on a thermally conductive material to dissipate the heat generated by the drive Typically thi...

Страница 7: ...his manual and other applicable manuals in their entirety before proceeding Failure to observe this precaution could result in severe bodily injury or loss of life Optidrive should be individually con...

Страница 8: ...ected to L1 L2 and L3 Phase sequence is not important For drives that have a dynamic brake transistor an optional external braking resistor can be connected to DC and BR when re resistor circuit shoul...

Страница 9: ...log Input 1 or Digital Input 3 Digital 8 to 30V Analog 0 to 24V 0 5 Analog Input 2 or Digital Input 4 Analog 0 to 10V 0 to 20mA or 4 to 20mA Digital 8 to 30V DC 6 0V User ground connected terminal 7 7...

Страница 10: ...lly stored Press the key for 2 seconds to return to operating mode Advanced Keypad Operation Short Cuts Display shows Press Result The next highest Parameter group is selected The next lowest Paramete...

Страница 11: ...entiometer set to zero switch on the supply to the drive The display will show StoP StoP StoP StoP 2 The drive is now enabled and the output frequency speed are controlled by the potentiometer On firs...

Страница 12: ...otor Once the autotune is completed the drive will operate further autotuning will be required unless the motor or drive control mode is changed P4 01 The user can program the drive to carry out an au...

Страница 13: ...e will ramp to stop using the P2 25 decel ramp time P1 06 Energy Optimiser 0 Disabled 1 Enabled 0 When enabled automatically reduces applied motor voltage on light load Minimum value is 50 of nominal...

Страница 14: ...is enabled Running 1 Logic 1 When no Fault condition exists on the drive 2 Logic 1 when the motor speed matches the setpoint speed 3 Logic 1 when the motor runs above zero speed Options 4 to 6 the Dig...

Страница 15: ...y as possible whilst preventing an overvoltage trip P2 26 Communication Baud Rate 0 Automatic 0 Factory set serial data link communication Baud Rate P2 27 Drive Communication Address 0 Disabled 1 to 6...

Страница 16: ...Integral time constant 0 0 to 30 0 seconds 1 0 PID Controller Integral Time Larger values provide a more damped response for systems where the overall process responds slowly P3 03 Differential time...

Страница 17: ...rol Drive dependent Version number checksum P0 30 Drive serial number Drive dependent Unique drive serial number Par Description Range Units Default Explanation P4 01 Control Mode 0 Vector Speed Contr...

Страница 18: ...Speed 2 Closed Open Preset Speed 3 Closed Closed Preset Speed 4 10 Open Stop disable Closed Forward Run enable Open Stop disable Closed Reverse Run enable Bipolar Analog Input External trip input Ope...

Страница 19: ...gital speed ref Closed Preset speed 1 Open Forward Closed Reverse Open Preset speed 1 Closed Digital speed ref Open Forward Closed Reverse Open Digital speed ref Closed Preset speed 1 Open Forward Clo...

Страница 20: ...ambient temp additional space or cooling needed Check drive is not forced into overload O O O O Uo Uo Uo Uo1 1 1 1t t t t Over voltage on DC bus Supply problem or increase decel ramp time P 04 U U U U...