Optidrive P2 Elevator User Guide V2.30
67
Technical Data
www.InvertekDrives.com
Output Power and Current ratings
200 – 240 Volt, 1 Phase Input
Frame
Size
Power Rating
Input
Current
A
Fuse or MCB (Type B)
Maximum Cable Size
Rated
Output
Current
A
Maximum Motor
Cable Length
Recommended
Brake
Resistance
(Minimum)
kW
HP
Non UL
UL
mm
AWG/
kcmil
m
ft
Ω
2
0.75
1
8.5
10
15
8
8
4.3
100
330
100 (50)
2
1.5
1.5
15.2
25
20
8
8
7
100
330
50 (32)
2
2.2
1.5
19.5
25
25
8
8
10.5
100
330
35 (25)
200 – 240 Volt, 3 Phase Input
Frame
Size
Power Rating
Input
Current
A
Fuse or MCB (Type B)
Maximum Cable Size
Rated
Output
Current
A
Maximum Motor
Cable Length
Recommended
Brake
Resistance
(Minimum)
kW
HP
Non UL
UL
mm
AWG/kcmil
m
ft
Ω
3
4
5
21.6
25
30
8
8
18
100
330
20 (20)
3
5.5
7.5
29.1
40
40
8
8
24
100
330
20 (20)
4
7.5
10
36.4
50
50
16
5
30
100
330
22 (22)
4
11
15
55.8
63
70
16
5
46
100
330
22 (22)
5
15
20
70.2
80
90
35
2
61
100
330
12 (12)
5
18.5
25
82.9
100
110
35
2
72
100
330
12 (12)
6
22
30
103.6
125
150
150
300MCM
90
100
330
6 (6)
6
30
40
126.7
160
175
150
300MCM
110
100
330
6 (6)
6
37
50
172.7
200
225
150
300MCM
150
100
330
6 (6)
380 – 480 Volt 3 Phase Input
Frame
Size
Power Rating
Input
Current
A
Fuse or MCB (Type B)
Maximum Cable Size
Rated
Output
Current
A
Maximum Motor
Cable Length
Recommended
Brake
Resistance
(Minimum)
kW
HP
Non UL
UL
mm
AWG/kcmil
m
ft
Ω
2
4
5
11.2
16
15
8
8
9.5
100
330
100 (50)
3
5.5
7.5
19
25
25
8
8
14
100
330
75 (40)
3
7.5
10
21
25
30
8
8
18
100
330
50 (40)
3
11
15
28.9
40
40
8
8
24
100
330
40 (40)
4
15
20
37.2
50
50
16
5
30
100
330
22 (22)
4
18.5
25
47
63
60
16
5
39
100
330
22 (22)
4
22
30
52.4
63
70
16
5
46
100
330
22 (22)
5
30
40
63.8
80
80
35
2
61
100
330
12 (12)
5
37
50
76.4
100
100
35
2
72
100
330
12 (12)
Note
Ratings shown above apply to 40°C ambient temperature. For derating information, refer to section 18.5
The maximum motor cable length stated applies to using a shielded motor cable. When using an unshielded cable, the maximum cable length
limit may be increased by 50%. When using the Invertek Drives recommended output choke, the maximum cable length may be increased by
100%
The PWM output switching from any inverter when used with a long motor cable length can cause an increase in the voltage at the motor
terminals, depending on the motor cable length and inductance. The rise time and peak voltage can affect the service life of the motor.
Invertek Drives recommend using an output choke for motor cable lengths of 50m or more to ensure good motor service life
For UL compliant installation, use Copper wire with a minimum insulation temperature rating of 70°C, UL Class CC or Class J Fuses