40
| Optidrive Eco User Guide |
Version 3.07
www.invertekdrives.com
9. Extended Parameters
9.1. Parameter Group 2 – Extended parameters
Par.
Parameter Name
Minimum
Maximum
Default
Units
P2-01
Preset Frequency / Speed 1
-P1-01
P1-01
50.0 (60.0)
Hz / Rpm
P2-02
Preset Frequency / Speed 2
-P1-01
P1-01
40.0
Hz / Rpm
P2-03
Preset Frequency / Speed 3
-P1-01
P1-01
25.0
Hz / Rpm
P2-04
Preset Frequency / Speed 4
-P1-01
P1-01
P1-01
Hz / Rpm
Preset speeds can be selected by:
Configuring P1-13 to an option that permits logic selection via the digital inputs (see section
8.1. Digital Input Configuration
Using the user defined logic configuration parameters in Parameter Group 9.
Configured through the drive PLC function using the OptiTools Studio Suite PC software.
P2-05
Preset Speed 5 / Clean 1
-P1-01
P1-01
0.0
Hz /Rpm
Preset speed 5 is automatically reference by the Pump Clean function when this is enabled. When the Pump Clean function is disabled,
Preset speed 5 can be selected as per preset speeds 1 – 4.
P2-06
Preset Speed 6 / Clean 2
-P1-01
P1-01
0.0
Hz / Rpm
Preset speed 6 is automatically reference by the Pump Clean function when this is enabled. When the Pump Clean function is disabled
Preset speed 6 can be selected as per as per preset speeds 1 – 4.
P2-07
Preset Speed 7 / Boost 1 / Pump Stir Speed
-P1-01
P1-01
0.0
Hz / Rpm
Preset speed 7 is automatically referenced by the Start / Stop Boost function, or the Pump Stir Function, when these functions are
enabled. When they are disabled, Preset speed 7 can be selected as per preset speeds 1 – 4.
P2-08
Preset Speed 8 / Boost 2
-P1-01
P1-01
0.0
Hz / Rpm
Preset speed 8 is automatically reference by the Start / Stop Boost function when this function is enabled. When disabled, Preset
speed 8 can be selected as per preset speeds 1 – 4.
P2-09
Skip Frequency Centre Point
P1-02
P1-01
0.0
Hz / Rpm
Defines the centre point of the skip frequency band. The width of the skip frequency band is defined by:
Lower limit = P2-09 - P2-10/2
Upper limit = P2-09 + P2-10/2
All skip frequency bands defined for forward speeds are mirrored for negative speeds.
P2-10
Skip Frequency Band Width
0.0
P1-01
0.0
Hz / Rpm
Defines the width of the skip frequency band. The width of the skip frequency band is defined by:
Lower limit = P2-09 - P2-10/2
Upper limit = P2-09 + P2-10/2
All skip frequency bands defined for forward speeds are mirrored for negative speeds.
P2-11
Analog Output 1 Function
0
12
8
-
Digital Output Mode. Logic 1 = +24V DC
0
Drive running
Logic 1 when the Optidrive is enabled (Running).
1
Drive healthy
Logic 1 When no Fault condition exists on the drive.
2
At speed
Logic 1 when the output frequency matches the setpoint frequency.
3
Motor speed > 0
Logic 1 when the motor runs above zero speed.
4
Motor speed >= limit
Logic 1 when the motor speed exceeds the adjustable limit.
5
Motor current >=limit
Logic 1 when the motor current exceeds the adjustable limit.
6
Motor torque >= Limit
Logic when the motor torque exceeds the adjustable limit.
7
Analog input 2 >=limit
Logic when the signal applied to the Analog Input 2 exceeds the adjustable limit.
NOTE
When using settings 4 – 7, parameters P2-16 and P2-17 must be used together to control the behaviour. The output will switch
to Logic 1 when the selected signal exceeds the value programmed in P2-16, and return to Logic 0 when the signal falls below the
value programmed in P2-17.
Analog Output Mode
8
Motor speed
0 to P1-01.
9
Motor current
0 to 200% of P1-08.
10
Motor torque
0 to 200% of motor rated torque.
11
Motor power
0 to 150% of drive rated power.
12
PID Output
Output from the internal PID Controller, 0 – 100%.
9
Extended P
arameters