Device
ITR412
-
001
Power Supply
21
-
30 V DC
Current Consumption
10 mA (dynamic)
5 mA (static)
Output
2 x Lighting
2 x HVAC
1 x Alarm
Detection Range
360°,
ф16
m (install height 10m)
Sensitivity
4 steps via ETS
Type of Protection
IP 20
Temperature Range
Operation (
-
20°C...45°C)
Maximum Air Humidity
< 90 RH
Flammability
Non
-
flammable Product
Color
White
Dimensions
102×54 (
Φ
xH)
Certification
KNX Certified
Configuration
Configuration with ETS
ITR412
-
001
-
HIGH BAY KNX PRESENCE
SENSOR
DESCRIPTION
ITR412
-
001
-
High Bay KNX Presence Sensor is a multi
-
functional
presence light level and PIR sensor. ITR412
-
001
’
s alarm, 2
-
level
standby, ambient light appraisal and constant light control functions
can be used to ensure comfortable life and energy saving. According
to different application requirements, the sensor can be configured as
the master
-
slave mode. Also, the sensor can be programmed using
the most current ETS software. ITR412
-
001 is for highbay mounted
between 2.5m to 10m height at proper locations.
IMPORTANT NOTES
•
ITR412
-
001 supports movement and LUX detection.
•
Adjustable from approximately 10 Lux to
∞
and Lux learning range: 10
Lux
-
2000 Lux for both Lux1 & Lux2.
•
Load On Time in Standby Mode: 3 precise adjustments: 5min, 10min,
15min and
∞.
•
Load on Illumination in Standby Mode: 3 precise adjustments: 10%,
20%, 30% and OFF.
•
Auto Off Time Adjustment: Adjustable from approximately 5 sec to 30
min.
•
The sensor can be fitted into the European standard boxes such as
surface mount and flush mount boxes.
•
A red LED is equipped as an indicator for test triggering and a green
LED is for indicating ETS installation. Moreover, the LED function can
be disabled by ETS.
•
2 channels can be used for controlling more KNX devices
simultaneously.
FUNCTIONS
•
Special Programming: ITR412
-
001 is designed for professional
KNX installation. It only can be programmed by ETS software.
•
Cable Connections: Ensure making correct connections for Black
and Red wires.
•
Voltage: The input voltage shall be 21
-
30VDC.
•
Mounting Location: Installation at indoors, to avoid installation near
the air
-
conditioner vent, and be away from the heat source.
•
The tightening torque shall not exceed 0.2Nm.
•
Avoid contact with liquids and corrosive gases.
DIMENSIONS
DETECTION