Electrical
Requirements
Power Supply
Cord
Wiring Requirements
NEMA 5-15P
115-Volt (103.5 min to
126.5 max.)
0 to 13amps
15-amp time-delay fuse or
circuit breaker
Use on single outlet circuit
only.
NEMA 6-15P
230-Volt (198 min to 253
max.)
0 to 12 amps
15-amp time-delay fuse or
circuit breaker
Use on single outlet circuit
only.
NEMA 6-20P
208/230-Volt (198 min to
253 max.)
0 to 16 amps
20-amp time-delay fuse or
circuit breaker
Use on single outlet circuit
only.
NEMA 6-30P
230-Volt (198 min to 253
max.)
0 to 24 amps
25-amp time-delay fuse or
circuit breaker
Use on single outlet circuit
only.
TABLE - 2
Recommended Grounding Method
This air conditioner must be grounded. This air
conditioner is equipped with a power supply cord
having a grounded 3 prong plug. To minimize
possible shock hazard, the cord must be
plugged into a mating, grounded 3 prong outlet,
grounded in accordance with all local and
national codes. If a mating outlet is not available,
it is the customer’s responsibility to have a
properly grounded 3 prong outlet installed by a
qualified electrical installer.
It is the customer’s responsibility:
To contact a qualified electrical installer.
To assure that the electrical installation
is adequate and in conformance with
National Electrical Code, ANSI/NFPA
70- latest edition, and all local codes
and ordinances.
Power Supply Cord
NOTE:
Your unit’s device may differ from the
ones shown.
This room air conditioner is equipped with a
power supply cord required by UL. This power
supply cord contains state-of-the-art electronics
that sense leakage current. If he cord is crushed,
the electronics detect leakage current and power
will be disconnected in a fraction of a second.
To Test your power supply cord:
1.
Plug power supply cord into a grounded 3
prong outlet.
2.
Press RESET
3.
Press TEST (listen for click, Reset button
will trip and pop out).
4.
Press and release RESET (listen for click;
Reset button will latch and remain in). The
power supply cord is ready for operation.
NOTES:
The reset button must be pushed in for
proper operation.
The power supply cord must be replaced if it
fails to trip when the test button is pressed
or fails to reset.
Do not use the power supply cord as an
off/on switch. The power supply cord is
designed as a protective device.
A damaged power supply cord must be
replaced with a new power supply cord
obtained from the product manufacturer and
must not be repaired.
The power supply cord contains no user
serviceable parts. Opening the tamper-
resistant case voids all warranty and
performance claims.