International comfort products PH4E Series Скачать руководство пользователя страница 1

516 01 2502 02

 09

14

10

PACKAGED HEAT PUMP UNITS

Installation Instructions

PH4E Series

400V

3Ph

50Hz

International Comfort Products, LLC
Lewisburg, TN. 37091

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

RECEIVING AND INSTALLATION

2

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Check Equipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Identify Unit

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspect Shipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Unit Support

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Roof Curb

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Slab Mount

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide Clearances

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rig and Place Unit

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspection

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Rigging/Lifting of Unit

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Select and Install Ductwork

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Converting Horizontal Discharge Units to Downflow

(Vertical) Discharge Units

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Provide for Condensate Disposal

8

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Install Electrical Connections

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

High

Voltage Connections

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Control Voltage Connections

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Standard Connections

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Transformer Protection

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Special Procedures for 420

v Operations

10

. . . . . . . . . . . . . . . . .

Accessory Electric heaters Installation

10

. . . . . . . . . . . . . . . . . . . .

Sequence of Operation

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PRE

START

UP

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START

UP

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Checking Cooling & Heating Control Operation

13

. . . . . . . . . . . .

  Check for Refrigerant Leaks

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .

PAGE

Start

Up  Adjustments

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Checking & Adjusting Refrigerant Charge

14

. . . . . . . . . . .

Indoor Airflow & Airflow Adjustments

15

. . . . . . . . . . . . . . .

Defrost Control

16

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Quiet Shift

16

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Defrost

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

MAINTENANCE

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Air Filter

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Blower and Motor

17

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Outdoor Coil, Indoor Coil, & Condensate Drain Pan

18

. . . . .

Outdoor Fan

18

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Electrical Controls and Wiring

18

. . . . . . . . . . . . . . . . . . . . . . . .

Refrigerant Circuit

19

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Indoor Airflow

19

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Metering Devices

  Piston

19

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Pressure Switches

20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Loss of Charge Switch

20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

High Pressure Switch

20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Copeland Scroll compressor (R

410A Refrigerant)

20

. . . . . .

Refrigerant System

20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Refrigerant

20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Compressor Oil

20

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Servicing Systems on Roofs with Synthetic Materials

20

.

Liquid Line Filter Drier

20

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

R

410A Refrigerant Charging

20

. . . . . . . . . . . . . . . . . . . . .

System Information

21

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Loss of Charge Switch

21

. . . . . . . . . . . . . . . . . . . . . . . . . . .

Check Defrost Thermostat

21

. . . . . . . . . . . . . . . . . . . . . . . .

TROUBLESHOOTING

23

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

START

UP CHECKLIST

24

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Содержание PH4E Series

Страница 1: ...Accessory Electric heaters Installation 10 Sequence of Operation 10 PRE START UP 13 START UP 13 Checking Cooling Heating Control Operation 13 Check for Refrigerant Leaks 13 PAGE Start Up Adjustments...

Страница 2: ...and screws Although special care is taken to reduce sharp edges to a minimum be extremely careful when handling parts or reaching into the unit CAUTION INTRODUCTION The PH4E heat pump is fully self co...

Страница 3: ...le materials Slab mounted units should be at least 4 in 102 mm above the highest expected water and runoff levels Do not use unit if it has been under water Step 4 Rig and Place Unit Rigging and handl...

Страница 4: ...4 513 01 3402 02 FIGURE 3 MODEL SIZE 24 36 DIMENSIONS...

Страница 5: ...5 513 01 3402 02 FIGURE 4 MODEL SIZE 48 DIMENSIONS...

Страница 6: ...NUMBER A IN mm B small base IN mm B large base IN mm C IN mm D IN mm E IN mm F IN mm G IN mm H IN mm Small or Large CPRFCURB010A00 11 279 10 254 14 356 16 406 47 8 1214 32 4 822 2 7 69 30 6 778 46 1 1...

Страница 7: ...standards of the NFPA for installation of non residence type air conditioning and ventilating systems NFPA 90A or residence type NFPA 90B and or local codes and ordinances Select and size ductwork sup...

Страница 8: ...ight seal 4 All units must have field supplied filters or accessory filter rack installed in the return air side of the unit Recommended sizes for filters are shown in Table 1 5 Size all ductwork for...

Страница 9: ...to the unit ground screw in the control compartment or conduit approved for electrical ground when installed in accordance with NEC NFPA 70 National Fire Protection Association latest edition in Canad...

Страница 10: ...rom transformer splice connection and connect black wire from transformer to splice connection Insulate unused blue transformer tap See transformer label During unit start up check secondary voltage t...

Страница 11: ...4 15 4 5 9 3 7 34 4 15 4 5 9 4 7 44 INDOOR BLOWER Nominal Cooling Airflow CFM Nominal Cooling Airflow L s Size in Size cm Motor HP Motor W 800 378 10x10 25 4x25 4 1 4 187 1000 472 10x10 25 4x25 4 1 2...

Страница 12: ...12 513 01 3402 02 FIGURE 12 Wiring Diagram 400 3 50...

Страница 13: ...cellaneous loose parts have been removed 5 Each unit system has 2 Schrader type ports one low side Schrader fitting located on the suction line and one high side Schrader fitting located on the compre...

Страница 14: ...a substantial adjustment is indicated an abnormal condition exists somewhere in the cooling system such as insufficient airflow across either coil or both coils Proceed as follows 1 Remove cap from lo...

Страница 15: ...ow Watts 303 305 306 300 Cfm 969 879 785 687 High Watts 435 428 428 422 Cfm 963 833 758 676 PH4E30 Low Watts 1002 954 921 889 853 814 Cfm 1189 1115 1041 971 903 833 High Watts 700 683 688 755 Cfm 1223...

Страница 16: ...55 850 944 1038 7 5 8 2 9 2 10 4 11 7 12 9 14 9 16 7 18 7 Step 3 Defrost Control Quiet Shift Quiet Shift is a field selectable defrost mode which will eliminate occasional noise that could be heard at...

Страница 17: ...esult in personal injury or death 1 Turn off electrical power to the unit and install a lockout tag before performing any maintenance or service on this unit 2 Use extreme caution when removing panels...

Страница 18: ...l be sure to clean between the coils Be sure to flush all dirt and debris from the unit base Inspect the drain pan and condensate drain line when inspecting the coils Clean the drain pan and condensat...

Страница 19: ...lly indicates a refrigerant leak If oil is detected or if low performance is suspected leak test all refrigerant tubing using an electronic leak detector or liquid soap solution If a refrigerant leak...

Страница 20: ...4E including the compressor oil needed servicing systems on roofs containing synthetic materials the filter drier and refrigerant charging Refrigerant PROPERTY HAZARD PERSONAL INJURY OR ENVIRONMENTAL...

Страница 21: ...system charge so that pressure gauges read zero gauge Never open system without breaking vacuum with dry nitrogen Check Defrost Thermostat The defrost thermostat is usually located on the lowest liqu...

Страница 22: ...ned to detect HFC refrigerant R 410A as with other HFCs is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated working pressure...

Страница 23: ...nd correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refr...

Страница 24: ...IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMP...