background image

WP1000MX SERIES 

WEATHERPROOF RECEPTACLE COVERS

FOR EXTRA-DUTY APPLICATIONS

Single-gang horizontal 

Model WP1010HMXD

Single-gang vertical 

Model 

WP1010MXD, WP1250MVXD and 
WP3110MXD

A grounding wire is provided for all models. The mounting screw that holds the receptacle or light switch should pass through the ring terminal on the end of the wire.

Double-gang 

Model WP1030MXD and 

WP1250MXD

This double-gang cover is designed for installation on double-gang junction 
boxes. If installing on a non-metallic junction box, you will need to use the 
grounding wire (as shown on the Optional Grounding illustration). If the junction 
box is non-metallic, a separate ground will need to be run and connected to 
the grounding wire by cutting and removing the spade terminal, stripping 
the ground wire and making a pigtail connection. Also note for single-gang 
installation you will need to purchase an Intermatic insert model #WP101 for 
duplex receptacle or WP102 for GFCI application.

The insert for model WP1030MXD and WP1250MXD may be oriented for 
horizontally or vertically mounted receptacles and is designed for double duplex 
or double GFCI applications.

This die cast cover can be used outdoors or in other wet locations when cover 

is closed (protects receptacles while in-use for unattended applications). 

The cover is UL Listed, CSA certified, rated Type 3R and meets 2014 National 

Electrical Code requirements covered by Article 406.9 (B)(1). 

 

Contents

The following items are included:
• Weatherproof cover/base - pre-assembled.
•  Universal insert for duplex receptacles (model WP1030 includes a double 

duplex insert)

•  Universal insert for GFCI receptacles (model WP1030 includes a double GFCI 

insert)

•  Gasket with slits for mounting screws
•  Baggie assembly with mounting hardware

Models

The instructions cover these models:

WP1010MXD, WP1250MVXD, WP3110MXD

 

Single-gang vertical mounting only

WP1010HMXD

  

Single-gang horizontal mounting only

WP1030MXD, WP1250MXD

  

double-gang, 2 device installation

Installation

Follow the steps listed below, while referring to the illustrations for your 

particular model. 

1.   If installation is being done on an existing receptacle(s), remove the 

existing cover and discard.

2.   The mounting screws that hold the receptacle or GFCI to the junction box 

can be removed. Do not remove the receptacle wiring connections. 

3.   Select the correct insert for your application and press into base.

4.   Locate the gasket as required for the installation. The gasket can be 

temporarily held to the back of the base/insert assembly using the 

mounting hardware provided. The receptacle cover should be installed on a 

smooth, flat, non-porous surface. 

   To ensure a weatherproof seal on irregular surfaces such as brick or cedar 

siding, a 1/4

"

 bead of non-hardening silicon caulk compound (neoprene, 

urethane or polyurethane type) should be placed between the weather-

proof receptacle gasket and the mounting surface.

5.

   Mount the base/insert assembly and the receptacle(s) to the junction box 

using two of the long screws provided (do not over-tighten). 

   To ensure weatherproof protection, the cover must be installed so that the 

hinge points are located at the top.

6.

   If mounting to an outdoor junction box or FS box, use the remaining long 

screws, 2 or 4 screws as required, to further secure the cover and insert 

assembly to the junction box. Note that holes are located in the insert for 

mounting to an FS box or any standard single-gang box. For specially 

designed junction boxes, holes should be carefully drilled to line up with 

the holes in the box to accommodate mounting.

7.

   Be sure all screws are secure but not over-tightened. Install the remaining 

1 or 2 short screws into the receptacle(s) as required.

8. 

A hasp is provided to allow for padlocking the cover if desired.

FOR BEST PROTECTION FROM RAIN OR HUMIDITY, BE SURE TO ROUTE THE 

CORDS THROUGH THE CORD OUTLETS IN THE COVER AND PRESS THE COVER 

FIRMLY UNTIL IT SNAPS CLOSED OVER THE HASP.

Cover may be removed for ease of mounting and then reattached. 

Optional Grounding

(Single gang 

installation)

Optional 
Grounding

WARNING

•  Disconnect power at the circuit breaker(s) or disconnect switch(es) before 

installing or servicing.

•  KEEP COVER CLOSED when used in wet locations. 

Risk of Fire or Electric Shock

NOTICE

•  If using a power screwdriver, be careful not to over-tighten the screws 

in the junction box and/or the electrical device to prevent stripping the 
threads.

Содержание WP1000MX Series

Страница 1: ...ion is being done on an existing receptacle s remove the existing cover and discard 2 The mounting screws that hold the receptacle or GFCI to the junction box can be removed Do not remove the receptacle wiring connections 3 Select the correct insert for your application and press into base 4 Locate the gasket as required for the installation The gasket can be temporarily held to the back of the ba...

Страница 2: ...ez le de côté 2 Les vis de montage qui maintiennent la prise ou le disjoncteur GFCI au boîtier de raccordement peuvent être retirées Ne retirez pas les raccordements de câblage sur la prise 3 Sélectionnez l insert approprié à votre application et insérez le dans la base 4 Localisez le joint requis pour l installation Le joint peut être temporairement maintenu à l arrière de l ensemble base insert ...

Страница 3: ...instalación en receptáculos existentes extraiga la cubierta actual y deséchela 2 Se pueden extraer los tornillos de montaje que sostienen el receptáculo o el ICFT en la caja de conexiones No extraiga las conexiones del cableado del receptáculo 3 Selecciones el inserto correcto para su aplicación y presiónelo en la base 4 Coloque la empaquetadura según se requiere para la instalación La empaquetadu...

Страница 4: ...ÉTATS N AUTORISENT PAS L EXCLUSION OU LA LIMITATION DES DOMMAGES DIRECTS ET INDIRECTS IL EST AINSI POSSIBLE QUE LA LIMITATION OU EXCLUSION CI DESSUS NE VOUS CONCERNE PAS CETTE GARANTIE REMPLACE TOUTES LES AUTRES GARANTIES EXPLICITES OU IMPLICITES TOUTES LES GARANTIES IMPLICITES Y COMPRIS LA GARANTIE SUR LA QUALITÉ MARCHANDE ET LA GARANTIE DE COMPATIBILITÉ AVEC UNE UTILISATION PARTICULIÈRE SONT PAR...

Отзывы: