MODEL: T185

24 HOUR DIAL TIME SWITCH
WITH ADJUSTABLE TRIPPERS

ONE NORMALLY OPEN -ONE NORMALLY CLOSED CONTACTS
MAY BE WIRED AS SINGLE POLE DOUBLE THROW.

40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN
OR 1000 VA, PILOT DUTY - 120-277 VOLT AC;
2 HP (24 FLA) - 120V. AC; 5 HP (28 FLA) - 240V AC.

CLOCK MOTOR: 110-125V. 60 HZ.

PRESSURE PLATE

TERMINAL SCREW

MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE

MINIMUM

COPPER

WIRE SIZE

(AWG)

MAX.

LOAD

(AMP)

MIN.

INSUL-

ATION

TEMP(°C)

75°C INSULATION MAX. MOTOR

LOAD (HP)

SINGLE PHASE

3 PHASE

120 V.

240 V.

208 V.

240 V.

14
12
10

8

15
20
30
40

60
60
60
75

1/2

1
2

-

2

2 1/2

3
5

N/A

N/A

CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO 

ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.

WIRING
DIAGRAM

FIGURE 1

WIRING INSTRUCTIONS:

To wire switch follow diagram above.

To wire as 

SINGLE POLE NORMALLY OPEN, move motor lead from

terminal 3 to 1, and connect LINE to 1, LOAD to 2. To wire as 

SINGLE

POLE DOUBLE THROW, install jumper (the same gauge as LINE wire)
between terminals 

and and connect LINE to 2, LOADS to and 4.

NOTE: Line 2 if present is uninterrupted. Use COPPER wire only. For
gauge selection and wire connection, see details below. Use 3//16 or larg-
er screwdriver, tighten terminal screws firmly (25lb-in minimum).
REPLACE FRONT INSULATOR BEFORE TURNING ON ELECTRICITY.

PROGRAMMING INSTRUCTIONS
• TO SET TRIPPER(S): A. 
Loosen screw A. (Fig. 1 inset); move time 

selector pointer to desired timing (scale is in minutes); tighten screw A.
Place 

TRIPPER(S) on CLOCK-DIAL at time(s) daily operation(s) is/are 

to take place. Tighten screw B. firmly.

• TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either

direction and align the exact time-of-day on the 

CLOCK-DIAL (the time

now, when switch is being put into operation) to the pointer. 

DO NOT 

MOVE POINTER.

OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: 
Move MANUAL LEVER  below

CLOCK-DIAL left or right as indicated by arrows. This will not effect
next operation.

NOTE: The MANUAL LEVER is inoperative for 15 

minutes immediately after an automatic operation.

• IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-

of-day. See programming instructions.

INTERMATIC INCORPORATED

SPRING GROVE, ILLINOIS 60081-9698

158T10710                                                  

CLOCK
DIAL

TIME
POINTER

TRIPPER

LEVER

TYPICAL WIRING: SINGLE POLE NORMALLY CLOSED
SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES

GROUND

120V

SUPPLY

CLOCK

MOTOR

GRD.

N

LINE

TO
LOAD

A

1

2

3

4

LISTED

885L

LR3730

Project4  7/27/04  3:45 PM  Page 1