Intermatic IG250LA Скачать руководство пользователя страница 1

120/240 VAC Three wire 

F ound at S ervice entrances and 
Meter C ans.

Line

Line

G rounded/
Neutral

120 v

120 v

240 v

WHIT E

B LAC K

B LAC K

120/240 VAC Three wire plus Ground 

F ound in Main Disconnect S witches, 
Main Distribution panels, Load C enters 
S ub panels and equipment locations.

Line

Line

Neutral

G round

120 v

120 v

240 v

120 v

120 v

B LAC K

B LAC K

240 VAC Two wire plus Ground 

from a single phase panel 

F ound at connections for individual 
pieces of equipment such as motors, 
water heaters and parking lot lights. 

Line

Line

G round

240 v

B LAC K

B LAC K

120 v

WHIT E

WHIT E

WARNING:

 

Intermatic Incorporated recommends that the UG and IG series Secondary Surge Arresters be 

installed by a licensed electrician.  Hazardous voltages may be present.  These units are not 

intended to protect against direct lightning strikes.

MAINTENANCE:

Inspect periodically to be sure that the Red indicator LED is on.  If it not, unit is no longer providing 

surge protection and should be replaced.

APPLICATION

This model is designed specifically for 120 / 240 VAC single phase or split phase applications.  If 

your application does not match one of the diagrams shown below, call your supplier or Intermatic. 

INTERMATIC INCORPORATED 

 

 PLAZA, SPRING GROVE, ILLINOIS  60081-9698 

© Copyright

 2007 Intermatic Inc.

Model UG240R and IG250LA 

Secondary Surge Arresters

INSTALLATION 

INSTRUCTIONS

Отзывы: