Intermatic Grasslin GM40AV Series Скачать руководство пользователя страница 1

MANUAL OVERRIDE OPERATION

With the manual switch in the middle position, the GM40AV is in 

automatic mode and will switch at the programmed times. 

In the upper position “I”, the load is continuously ON. 

In the lower position, “O”, the load is continuously OFF.

TRIPPERS IN

Green Status LED: OFF 

(Normally-open contacts open)

TRIPPERS OUT

Green Status LED: ON 

(Normally-open contacts closed)

Figure 3 

•  Rotate timer dial clockwise only.
•  Jumper wires are not included.
•  Alterations or modifications to the device will void warranty

GM40AV Series General Purpose Electromechanical Commercial Time Switches 
Installation & Operating Instructions

•  Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
•  More than one circuit breaker or disconnect switch may be required to de-energize the equipment before 

servicing.

•  Do not use the manual shut-off position of the timer for equipment servicing. Always disconnect the power 

at the circuit breaker(s) or disconnect switch(es).

•  Installation and/or wiring must be in accordance with national and local electrical code requirements.
•  This Time Switch is designed to control one or two single phase loads. Do not use to directly control three 

phase loads. Consult a qualified electrician if you are required to control three phase equipment.

•  Some terminals in the Time Switch may be energized even if the yellow and green LED indicators are OFF.
•  The circuit conductors shall have an ampacity not less than the maximum total load to be controlled.
•  For all connections, use COPPER conductors ONLY – min. #8 AWG wires for 40 A loads, or #10 AWG wires 

for 30 A loads, min. 90°C (194°F) 

•  Over current protection shall have an interrupting rating sufficient for the application control circuit voltage 

and the total load current of the equipment being controlled.

•  A fuse or circuit breaker shall be connected in series with each ungrounded conductor (and shall be able to 

simultaneously open each conductor.

•  Check all terminals and wires with an appropriate voltage meter before touching.
•  This enclosure does not provide grounding between conduit connections. When metallic conduit is used, 

you must also install grounding type bushings and jumper wire, in accordance with the (NEC) National 
Electrical Code requirements.

•  For outdoor locations or wet locations (rain-tight), conduit hubs that comply with requirements of the 

UL514B (standard for fitting conduit and outlet boxes) are to be used.

•  Replace plastic insulator covering terminals before powering ON.

WARNING

Read Instructions completely before installation and retain this booklet for future reference.

INSTALLATION INSTRUCTIONS 

1.  Open door and remove the interior protective cover by releasing the spring latch. (See Figure 1)
2.  Remove the printed circuit board by releasing the spring latch holding the bottom of the board. 

(see Figure 1)

3.  Select knockouts to be used. Remove the inner 1/2" knockout by inserting a flathead screwdriver 

in the slot and carefully punch the knockout loose. Remove slug. If 3/4" knockout is required, 
remove the outer ring with pliers after removing the 1/2" knockout. Smooth edge with knife, if 
necessary.

4.  Place the enclosure in the desired mounting location, and mark the three mounting holes (refer to 

Figure 2 for dimensions). Install the top screw first with one of the supplied spacers, and then hang 
the enclosure by the keyhole. Drive the remaining two screws at the bottom of the enclosure 
through the mounting holes while passing each screw through one of the supplied spacers and in 
to the wall.

5.  Connect conduit hubs to conduit before connecting the hubs to the enclosure. After inserting hubs 

into enclosure, carefully tighten hub lock nut. Do not over-torque. 

6.  Replace printed circuit board making sure to engage spring latch at the bottom of PCB.
7.  Wire in accordance with national and local electrical and safety codes (see wiring diagrams).
8.  Grounding: Terminate all ground wires to the ground lug inside the case at the bottom of the 

enclosure.

9.  Replace interior protective cover. 
10.  Close the enclosure door.

PROGRAMMING INSTRUCTIONS

SETTING THE CLOCK TIME 

Rotate the program dial gradually clockwise until the time of day on the outer dial is nearly aligned with 
the triangle marker at the 2 o’clock position. Then set time to the minute by rotating minute hand 
clockwise until the time of day (and AM or PM) on the outer dial is aligned with the triangle marker on 
the inner dial. 

SETTING ON/OFF TIMES 

Move the white tab (tripper) on the outer dial outward at the start of the desired ON period. Move each 
adjacent tab outward until the desired OFF time is reached. (See Fig. 3) 

Figure 2 - Rear View of Enclosure 

with mounting hole dimensions

6-1/8”

2-1/2”

Figure 1 - PCB Latch

Interior 

Protective 

Cover

Timer Mechanism

Spring Latch

GM40AV SERIES TERMINAL DESIGNATIONS 

NO 2

NC 2

NO

NC

L 2/N

L 1

T

TIMER

L

N

COM

LOAD 

#1  

LOAD 

#2 

COM2

120/277 VAC Application Two Loads

COM2

NO 2

NC 2

NO

NC

L 2/N

L 1

T

TIMER

L1

L2

COM

LOAD 

#1  

208/240 VAC Application One Load

NO Contacts:

40 A Resistive, 120-277 VAC
30 A Ballast, 120 VAC
20 A Ballast, 277 VAC
15 A Tungsten, 120 VAC
300 VA Pilot Duty, 120-240 VAC
1 HP, 16 FLA, 90 LRA @ 120 VAC
2 HP, 12 FLA, 52 LRA @ 208-277 VAC

NC Contacts:

30 A Resistive, 120-277 VAC
10 A Ballast, 277 VAC
2 A Tungsten, 120 VAC
1 HP, 12 FLA, 30 LRA @ 120 VAC
2 HP, 10 FLA, 30 LRA @ 240 VAC

WIRING CONNECTIONS:

Screw box lug terminals

ENVIRONMENTAL RATINGS:

Operating Temperature Range:  
-40° F to 131° F (-40° C to 55° C) Non “Q” Models
-4° F to 131° F (-20° C to 55° C) “Q” Models
Operating Humidity: 
10-95% RH, non-condensing

ENCLOSURE DIMENSIONS:

8.795" H x 6.631" W x 2.935" D

SHIPPING WEIGHT: 

2 lbs.

ELECTRICAL RATINGS

Risk of Fire or Electric Shock

NOTICE

Содержание Grasslin GM40AV Series

Страница 1: ...emove the printed circuit board by releasing the spring latch holding the bottom of the board see Figure 1 3 Select knockouts to be used Remove the inner 1 2 knockout by inserting a flathead screwdriver in the slot and carefully punch the knockout loose Remove slug If 3 4 knockout is required remove the outer ring with pliers after removing the 1 2 knockout Smooth edge with knife if necessary 4 Pl...

Страница 2: ...uvrant les bornes avant la MISE SOUS TENSION Risque d incendie ou de choc électrique Tourner le cadran de la minuterie dans le sens horaire seulement Les cavaliers ne sont pas inclus Des altérations ou des modifications de l appareil annuleront la garantie AVIS Lire les instructions complètement avant l installation et conserver ce livret pour référence future DIRECTIVES D INSTALLATION 1 Ouvrez la...

Страница 3: ...guro de resorte Vea la Figura 1 2 Retire el tablero de circuito impreso al aflojar el seguro de resorte y sostenga la parte inferior del tablero Vea la Figura 1 3 Seleccione los troqueles a utilizar Retire el troquel de 1 2 interior al insertar un destornillador de cabeza plana en la ranura y aflojar el troquel con cuidado Retire el vástago Si se requiere un troquel de 3 4 retire el anillo exterio...

Страница 4: ...amation de garantie sur www intermatic com Cette garantie est faite par Intermatic Incorporated Customer Service 1950 Innovation Way Suite 300 Libertyville IL 60048 Pour les services de garantie accédez à la page suivante http www Intermatic com ou appelez au 815 675 7000 INTERMATIC INCORPORATED LIBERTYVILLE ILLINOIS 60048 www Intermatic com GARANTÍA LIMITADA Este servicio de garantía está disponi...

Отзывы: