Deleting (Clearing) an Event

Astro events and fixed events can be deleted from the time switch. If you need to delete an event, follow this procedure.
1.  If necessary, press MODE to scroll through the different mode selections until SET ASTRO or SET FIXED ON/OFF EVENTS 

appear on the display.

2.  Press ENTER/NEXT as necessary to scroll through the scheduled events until you see the event you want to delete.
3.  Press + and – 

at the same time

 until the display shows --:-- --. This indicates the event is erased.

4.  If necessary, press ENTER/NEXT to advance through the other configured events.
5.  Press MODE to save the changes and exit.

Clearing Time Switch Memory

During a “Clear Time Switch Memory” operation, the time switch resets all programmed setting to their factory default value. The 
following occurs:
• 

After a brief period of time the time switch model number appears, followed by the USB Boot Loader version, EE Boot Loader 
version, the firmware revision and finally the Reset Reason Code.

• 

MEMCLR is displayed followed by DONE when the operation is completed.

To perform a “Clear Time Switch Memory” operation do the following:
1.  Press and hold ENTER/NEXT.
2.  While pressing and holding ENTER/NEXT, press and release the RESET (round) button. Do not release ENTER/NEXT.
3.  Continue to press and hold ENTER/NEXT until 

MEM CLEAR

 then 

DONE

 briefly appears.

4.  IND will now show on the display. Refer to the “Setting Output Configuration” section in these instructions.

Writing Time Switch Program Data to a USB Memory Stick

The time switch has the capability to copy its programmed data (event schedules, holidays, output configuration, DST on/off setting, 
DST rule setting and geographical location) to a USB memory stick. Follow these steps to transfer all programming from the time 
switch to a USB memory stick:
1.  Press MODE to advance until 

wr USb

 is displayed.

2.  Press ENTER and 

insUSb

 is displayed.

3.  Insert a USB memory stick into the USB port on the front face of the time switch.
4. 

SCHEdL 01

 is displayed. Press + or - to increment/decrement the schedule number on the display (01-99).

5.  When the desired number is displayed, press ENTER and this will write the data file to the USB memory stick. The file name will 

be 

SCHEDLxx.TXT

 where xx is the schedule number selected in the previous step.

6.  After the file is written 

REMOVE

 is shown on the display.

7.  Remove the USB memory stick and the time switch will advance to the next mode selection. If all procedures are completed, 

press MODE repeatedly until back to the operating mode selection (AUTO, ENERGY SAVER, MANUAL).

Reading Time Switch Program Data from a USB Memory Stick

The time switch has the capability to read program data (event schedules, holidays, output configuration, DST on/off setting, DST 
rule setting and geographical location) from a USB memory stick. Follow these steps to transfer all programming from a USB 
memory stick to the time switch:
1.  Press MODE to advance until 

rd USb

 is displayed.

2.  Insert a USB memory stick containing the desired data file into the USB port on the front face of the time switch.
3.  Press ENTER and 

insUSb

 is briefly displayed.

4. 

SCHEdL.xx

 is displayed where xx is the first data file number found on the USB memory stick.

5.  Press + or - to scroll through the data files on the USB memory stick (if more than one file is stored on this stick).
6.  When the desired number is displayed, press ENTER and the time switch will read the data file from the USB memory stick.
7.  After the file is read into the time switch, DONE is briefly shown on the display followed by 

REMOVE

.

8.  Remove the USB memory stick and the time switch will advance to the next mode selection. If all procedures are completed, 

press MODE repeatedly until back to the operating mode selection (AUTO, ENERGY SAVER, MANUAL).

USB error codes

If a problem occurs when attempting to perform a USB read or write operation the time switch will show an error code on the 
display. Following is a description of the different error codes:

OPFILE Er

File could not be created on the USB memory stick (stick may be write protected or corrupted)

wrFILE Er

Program data could not be written to the USB memory stick (stick may be full)

oPFILE ER File could not be opened for reading from the USB memory stick
rdFILE Er

File could not be read from the USB memory stick

MSDH Er

USB device is not a memory type device

FATFS Er

Fat file system error indicating the memory stick contains a data format that is incompatible with the time 
switch

DEVICE Er USB memory stick is defective
shCrct Er

The power supply for USB port on the time switch is not functioning

Specifications

Input Voltage:

 120-277 VAC, 60 Hz

Power Consumption:

 7 W MAX

Contact Configuration:

 SPST x 4. See wiring diagrams in this manual. 

Contact Ratings:

 

Rating

Load Type

Voltage

Frequency

30 A

Resistive

120-240 VAC

60 Hz

20 A

Resistive

28 VDC

30 A

Inductive

120-240 VAC

60 Hz

20 A

Magnetic Ballast

120-277 VAC

60 Hz

5 A

Tungsten

120-277 VAC

60 Hz

1 HP

Motor

120 VAC

60 Hz

2 HP

Motor

240 VAC

60 Hz

10 A

Electronic Ballast

120/277 VAC

60 Hz

Events:

 Time switch can support up to 48 fixed ON and 48 fixed OFF events along with 1 astro on and 1 astro off event per circuit.

Clock Backup:

 100-hour Supercapacitor

Wire Size:

 AWG #14-#8

Minimum ON or OFF time:

 1 minute

Maximum ON or OFF time: 

Indefinite

Shipping Weight:

 2.5 lb. (1.1 kg)

Enclosures:

 Rainproof Type 3R indoor/outdoor lockable metal enclosure (ET2845CR), Type 1 indoor lockable metal enclosure 

(ET2845C), Rainproof Type 3R indoor/outdoor lockable plastic enclosure (ET2845CP)

Knockouts:

 Combination 1/2-3/4 in. size, 1 on rear and each side, 2 on bottom

Содержание ET2845C

Страница 1: ...ed in a commercial environment This equipment generates uses and radiates radio frequency energy and if not installed and used in ac cordance with instructions may cause harmful interference to radio...

Страница 2: ...4 COM3 NO 3 COM2 NO 2 COM1 NO 1 AC IN OUTPUT CONFIGURATION SIM CIRCUIT 1 AND 2 OUTPUT CONFIGURATION SIM CIRCUIT 3 AND 4 L1 L2 CIRCUIT 1 CIRCUIT 2 CIRCUIT 3 CIRCUIT 4 TIMER POWER AC IN NO 1 COM1 NO 2 C...

Страница 3: ...ry stick refer to the Read Time Switch Program Data section in these instructions Enable Disable Daylight Saving Time and Setting Daylight Saving Time Rule Configure the time switch to automatically a...

Страница 4: ...yed as indicated by the LOAD icon above the circuit 1 button 8 Repeat steps 2 through 5 as necessary to adjust sunset times 9 When all the sunset times are configured press MODE to save Programming Ev...

Страница 5: ...1 Press MODE to advance until the SET DATE and ON icons appear on the display if this selection is not already active A Holiday Number is also displayed on the right side of the display 2 The time dis...

Страница 6: ...configuration DST on off setting DST rule setting and geographical location from a USB memory stick Follow these steps to transfer all programming from a USB memory stick to the time switch 1 Press M...

Страница 7: ...ge initial installation costs removal costs or reinstallation costs INTERMATIC INCORPORATED WILL NOT BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITAT...

Отзывы: