INSTALLING THE EM14PS

The EM14PS photosensor is designed to be wired directly 
to the EM1400 for single-zone outdoor lighting control 
applications.

Connect the EM14PS to the EM1400MC input using two 
#18 wires. Note that the wires are polarized. If they are 
reversed no damage will be done but the reading on the 
display will show as 1024 and will not change. 

Note that it must be wired to the Master Panel with the 
clock display. The slave panels do not have photocell 
inputs.

Program per instructions in the EM1400 O&M Manual.

1.

2.

3.

INSTALLING THE EMOPS1

The EMOPS1 photosensor is used with the EMPS3IN 
card. This card sits on the data bus and allows for more 
sophisticated control of light level triggers than that avail-
able with the on board photocell input of the EM 1408MC 
or EM 1416MC.

Mount the photosensors in an appropriate location. For 
general controls they should be mounted on the roof 
facing north. For areas that are shaded the photocell 
should be mounted to collect the light level that needs to 
be measured. 

Connect the EMOPS1 to the EMPS3IN inputs using two 
#18 wires. Note that the wires are polarized and must 
be connected correctly. One may run two #18 wires for 
a distance of up to 1000ft. The wires must never be run 
in the same conduit as high voltage wires. They must 
also be kept at least 12” away from any parallel run-
ning conduit except when crossing the conduit at right 
angles. 

See EMPS3IN (Control Card) installation instructions on 
connection to EM1400 system.

Program per instructions in the EM1400 O&M Manual.

1.

2.

3.

4.

EM14PS ANd EMOPS1

PHOTOSENSORS

INSTALLATION

GuIdE

LIGHTING CONTROL EQuIPMENT

INTERMATIC INCORPORATEd • http://www.intermatic.com

EM14PS and EMOPS1 
Photosensors look the same