Intelligent Building Solutions CHB 23 B Скачать руководство пользователя страница 1

Installation Manual

CHB 23 B

NETWORK HUB

up to 8 BUS lines

Desktop

CIB-tech

Содержание CHB 23 B

Страница 1: ...Installation Manual CHB 23 B NETWORK HUB up to 8 BUS lines Desktop CIB tech...

Страница 2: ...network segments connected Power supply via IBB bus connector Standby current IHS1 40mA Maximum current IHM1 65mA Power supply via dedicated power jack Standby current IHS2 50mA Maximum current IHM2...

Страница 3: ...ne switches for CIB tech bus lines every BUS EOL switch corresponds to the bus connector above it IBB bus connector Input backbone bus connector 8P8C RJ45 modular jack connector for connecting the CHB...

Страница 4: ...ew BUS EOL switch BB EOL switch CHB 23 B rear view CHB 23 B 2009 Intelligent Building Solutions 3 I O Bus connectors B8 B7 B6 B5 B4 B3 B2 B1 IBB Bus connector OBB Bus connector LED BB EOL switch BB EO...

Страница 5: ...CHB 23 B top view CHB 23 B 2009 Intelligent Building Solutions 4 LED Power switch Power connector...

Страница 6: ...should only be connected to another hub s OBB bus connector and so on Connecting an IBB bus connector to another IBB bus connector is allowed if none of the two hubs are to be remotely powered but yo...

Страница 7: ...their switches in the OFF position All the other switches corresponding to unused bus connectors should be in the ON position Please check the power consumption of the individual bus lines the maximu...

Страница 8: ...owered via its local power connector NOTE Power supply with 5 5x 2 1mm DC plug is required1 1 See Recommended equipment to be used with CIB tech for details CHB 23 B 2009 Intelligent Building Solution...

Страница 9: ...es in use are 3 to 7 with the default value of 4 Values outside of this range should only be used in extreme cases 0 is factory reserved and should never be used NOTE Before changing the default setti...