15.
Pipe the provided 10' of 3/8” drain tubing on the nitrogen cabinet to the floor drain in the sprinkler room. Do not pipe the
drain tubing upward. See Fig 15.
Drain Tube
CAUTION
Restrain all drain tubing.
16. Each riser requires a minimum of ONE Nitrogen Purge Valve to be installed prior to implementing the Nitrogen Purging
Procedure. For installation instructions, refer to Model NGP-SPV Bulletin (#5401520) or Model INS-PV Manual
(#5401532) supplied with each purge valve. See Fig. 7 for NGP-SPV installation diagram. See Fig. 8 for INS-PV installation
diagram.
Installing the purge valve upside down will not allow the system to purge. Also, ensure that there is NO water in
the pipe to the purge valve.