This section describes how to install and configure for first-time use:
•
The Intel
®
Omni-Path Fabric Series switches in a network environment.
Planning the Installation
The Intel
®
Omni-Path switches are designed for installation in standard 19-inch
equipment racks.
Racks should conform to conventional standards. Use the American National
Standards Institute (ANSI)/Electronic Industries Association (EIA) standard ANSI/
EIA-310-D-92 and International Electrotechnical Commission (IEC) 297
Racks should meet the following mechanical recommendations:
•
Four-post, 19" rack to facilitate easy maintenance
•
Universal mounting rail hole pattern identified in IEC Standard 297
•
Mounting holes flush with the rails to accommodate the chassis
NOTE
Operation is subject to the following conditions:
NOTE
Use a rack grounding kit and a ground conductor that is carried back to earth or to
another suitable building ground. Ground the equipment rack to earth ground.
NOTE
Provide enough room to work on the equipment. Clear the work site of any
unnecessary materials. Make sure the equipment will have enough clearance for front
and rear access.
Cable Requirements
Cable Distances
When planning the location of the switches, consider the distance limitations for
signaling, EMI, and connector compatibility. It is recommended that the user does not
exceed specified transmission rate and distance limits.
NOTE
When connecting the outer ports of two (2) 48-port Edge switches (highlighted green
in Figure 1 below), make certain to use active optical cables (AOC) for distances
greater than 2 meters.
2.1
2.1.1
2.1.1.1
Intel
®
Omni-Path Fabric—Installation
Intel
®
Omni-Path Fabric Switches Hardware
Installation Guide
June 2019
28
Doc. No.: H76456, Rev.: 10.0