DGC6 – UserManual
4.6.5 Error Status
Symbol
Description
Setting
Status
Function
OFF
System Errors OFF
OFF = Faults are not stored.
ON = Faults are stored.
Release of the fault recording for all active measuring points on the USB device in the common CSV file for alarms
and faults.
Internal structure of the file
(The headlines are not written in the file!)
Current Time
Source
Error Code
+ Error present
- Error absent
Error date (month day)
Time(hours minutes)
Error text
10_22_28
DP 79
0x8100
+
03_30 10_20
Underrange
13_48_28
DP 79
0x8100
-
03_30 13_46
Underrange
The first column gives the current time, the second one the error source. The third column indicates the error code.
In the fourth column there is the action:
+ = Error occurred.
- = Error acknowledged.
The fifth column gives the time and date when the error has occurred
From the sixth column on, there is the plain text of the error code. If several errors are coded so you can read multiple
entries here.
Every internal restart of the system (system reset) is also documented in the current day file.
Frequent reboots (several times per day) may point to a technical problem. Please consult the installer as soon as
possible.
Info
Date
Time
DGC06 Reset
30_03_12
13_38_19