5.1 Optimum Environment
When installing the server in a rack, select a location that meets the environmental
standards described in this section.
5.1.1 Space and Airflow Requirements
To allow for servicing and adequate airflow, observe the following space and airflow
requirements when deciding where to install a rack:
•
Leave a minimum clearance of 63.5 cm (25 in) in front of the rack.
• Leave a minimum clearance of 76.2 cm (30 in) behind the rack.
•
Leave a minimum clearance of 121.9 cm (48 in) from the back of the rack to the back of
another rack or row of racks.
Inspur Servers draw in cool air through the front door and expel warm air through the
rear door. Therefore, the front and rear rack doors must be adequately ventilated to allow
ambient room air to enter the cabinet, and the rear door must be adequately ventilated to
allow the warm air to escape from the cabinet.
CAUTION:
To prevent improper cooling and damage to the equipment, do not block the
ventilation openings.
When vertical space in the rack is not filled by a server or rack component, the gaps
between the components cause changes in airflow through the rack and across the servers.
Cover all gaps with blanking panels to maintain proper airflow.
CAUTION:
Always use blanking panels to fill empty vertical spaces in the rack. This
arrangement ensures proper airflow. Using a rack without blanking panels results in
improper cooling that can lead to thermal damage.
CAUTION:
If a third-party rack is used, observe the following additional requirements to
ensure adequate airflow and to prevent damage to the equipment:
• Front and rear doors—If the 42U rack includes closing front and rear doors, you must
Содержание NF8480M5
Страница 1: ...Inspur Server User Manual NF8480M5 ...
Страница 51: ...45 BIOS Setup b It will display the memory RAS configuration by entering the Memory RAS Configuration submenu ...
Страница 66: ...60 information 3 2 Create RAID Volume Enter this menu interface as shown below ...
Страница 92: ...86 sensor Figure 6 Sensor fru Figure 7 Fru chassis Figure 8 Chassis user Figure 9 User ...
Страница 93: ...BMC Settings 87 mc Figure 10 MC fan Figure 11 Fan psu Figure 12 Psu id Figure 13 Id diagnose ...
Страница 143: ...BMC Settings 137 Figure 56 SOL Setting in BIOS Figure 57 Default Serial Setting ...