background image

© 2004 Inovonics Wireless - www.inovonicswireless.com

EN4201/R EchoStream™ Receiver

Installation and Operation Manual - 04056B

1 Overview

The EN4201/R receiver allows you to add one transmitter to any application. With diversity reception and 
advanced signal processing, Inovonics Wireless EchoStream technology is designed to minimize dead spots in 
transmission areas.

1.1 Inovonics Wireless Contact Information

If you have any problems with this procedure, contact Inovonics Wireless technical services:

•  E-mail: [email protected]
•  Phone: (800) 782-2709; (303) 939-9336

1.2 EN4201/R LEDs

Alarm LED: 

Lights when the selected transmitter is sending an alarm transmission (Fig. 1A).

Tamper Fault LED: 

Lights when the transmitter is sending a tamper transmission (Fig. 1B).

Low Battery Fault LED: 

Lit when the selected tramsitter has a low battery (Fig. 1C).

Inactive Fault LED: 

Lit when the selected transmitter is inactive (Fig. 1D).

Power LED: 

Lit when receiving power (Fig. 1E).

Decode LED: 

Flashes when any recognizable transmission is received. This button is only accessible when 

the pry-out door on the front panel is removed (Fig. 1G).

Reset Button: 

Clears the current point status and resets outputs and LEDs. Resets the supervision window 

timer. This button is only accessible when the pry-out door on the front panel is removed (Fig. 1H).

 Figure 1  

Receiver LEDs

2 Installation and Startup

2.1 Select the Frequency Band

EchoStream products are able to use a range of radio frequencies, and must be configured for your geographic 
area. To configure the receiver:

1. 

Use a small screwdriver to press the housing release tab on the top or bottom of the receiver (Fig. 2A, Fig. 

3A); separate the housing.

2. 

Place a selection jumper on the appropriate frequency band selection pins (Fig. 2F, Fig. 3F).

•  Place the jumper on the top two pins, marked AUS, to set the frequency range to 915-928 MHz for 
Australia.
•  Place the jumper on the bottom two pins, marked NZ, to set the frequency range to 921-928 MHz for 
New Zealand.
•  Leave the jumper off the pins to set the frequency range to 902-928 MHz for North America.

Note: 

North American is also selected when the jumper is only attached to one pin. This can prevent the 

jumper from being lost when selecting North America.

3. 

Cycle power source to reset.

2.2 Program the Receiver

The receiver can be set in program mode to change point settings. The default settings are:

2.3 Program Output

To program the transmitter output or the fault output:

1. 

Use a small screwdriver to press the housing release tab on either side of the receiver (Fig. 6A, Fig. 7A); 

separate the housing.

2. 

Use the Advance button to select either the transmitter output or the fault output (Fig. 2).:

 Figure 2  

Select the Transmitter Output or the Fault Ouput

Note: 

When programming the EN4201, the only programmable parameter for the fault output is whether the 

switch is normally opened or normally closed. If F is selected, the EN4201 automatically advances to the 
switch option.

3. 

Press the Program button (Fig. 2K, Fig. 3K) to begin programming the point. If no transmitter has been 

registered to the point, the receiver advances to the supervision window option.

Note: 

If a transmitter has already been registered to the chosen point, the Delete LED lights. Press Advance 

to delete the point and return to normal operation; press Program to advance to the supervision window 
option.

4. 

Use the Advance button to choose a supervision window of None, 2h, 4h and 96h. Press Program to 

complete and advance to the output type option (Fig. 3).

 Figure 3  

Select the Supervision Window

5. 

Use the Advance button to select the output type (Fig. 4). There are four output types:

Follower: 

The output reflects the transmitter’s alarm status.

Momentary: 

The output turns on for seven seconds, then turns off, regardless of the device status.

Toggle: 

The output changes state each time the device sends a new activation. A minimum of five seconds 

must elapse before the output can send a new activation.

Latching: 

The output turns on when activated and remains on until the receiver is reset.

 Figure 4  

Select the Output Type

Press Program to complete and advance to the switch type option.

6. 

Use the Advance button to choose between N/O and N/C (Fig 5). Press Program to complete..

 Figure 5  

Select the Switch Type

7. 

All the option LEDs will light and the point you’ve just programmed will flash. If you wish to register the 

transmitter, push the Reset button on the transmitter to be registered; otherwise, press Program to return to 
normal operation mode.

Note: 

All LEDs will turn off when the receiver has received the transmitter’s registration message. If the 

LEDs do not turn off, press Reset on the transmitter again. The registration is not complete until all LEDs turn 
off, indicating the receiver has received the transmitter’s registration message.

2.4 Connect Cabling

Note: 

Always test point programming before connecting cabling.

1. 

Connect power cabling to the Vs (Fig. 6B, Fig. 7B) and GND (Fig. 6C, Fig. 7C) connections.

•  Power source should be 11-14 VDC. Power supply must be unswitched, uninterrupted, and regulated.

2. 

Connect cabling to the tamper output (Fig. 6J, Fig. 7J).

•  The optional tamper output is a normally open (N/O) output that reports receiver case tamper to an 
external device.

3. 

Connect cabling to the jam output (Fig. 6I, Fig. 7I).

•  The optional jam output is a normally closed (N/C) output that opens when noise thresholds on all 
transmission channels remain above a predetermined value for more than 20 seconds.

4. 

Connect cabling to the reset input (Fig. 6H, Fig. 7H).

•  The optional reset input circuit permits installation of a remote momentary normally open (N/O) switch 
to clear faults, unlatch outputs and reset the receiver to a normal state.

5. 

Connect cabling to the output terminal (Fig. 8-11).

•  The EN4201 provides one open collector circuit (Fig. 6D) and an open collector fault output (Fig. 6E); 
the EN4201R provides one Form C relay alarm output (Fig. 7D) and a relay fault output (Fig. 7E).

6. 

Close the receiver housing.

 Figure 6  

EN4201 Components

A. 

Alarm LED

B. 

Tamper Fault LED

C. 

Low Battery Fault LED

D. 

Inactive Fault LED

E. 

Power LED

F. 

Transmitter Number LEDs

G. 

Decode LED

H. 

Reset Button

Point

Supervision Window Ouput

Type

Switch (EN4201 
Only)

1

4 hours

Transmitter 1

Follow

N/O

F

N/A

Fault

Inactive is set to 
follow; low battery 
and tamper are set 
to latching.

N/O

 

A

B

D

E

C

H

I

Delete

Out Type

Output

Sup Wind

Switch

F

Toggle

4h

Latch

96h

Follow

None

N/O

Moment

2h

N/C

1

2

3

4

A. 

Housing release tabs

B. 

Power (11-14 VDC)

C. 

GND connection

D. 

Output terminals

E. 

Fault output

F. 

Frequency selection pins

G. 

Reset button

H. 

Reset input

I. 

Jam output

J. 

Tamper output

K. 

Program button

L. 

Advance button

Delete

Out Type

Output

Sup Wind

Switch

F

Toggle

4h

Latch

96h

Follow

None

N/O

Moment

2h

N/C

1

2

3

4

Delete

Out Type

Output

Sup Wind

Switch

F

Toggle

4h

Latch

96h

Follow

None

N/O

Moment

2h

N/C

1

2

3

4

Delete

Out Type

Output

Sup Wind

Switch

F

Toggle

4h

Latch

96h

Follow

None

N/O

Moment

2h

N/C

1

2

3

4

NZ

AUS

ADVANCE

PROGRAM

TAMP

RESET

Delete

Out Type

Output

Sup Wind

Switch

F

Toggle

4h

Latch

96h

Follow

None

N/O

Moment

2h

N/C

1

2

3

4

A

B
C

D

I

J

G

H

F

E

K

A

A

L

Отзывы: