Chapter 4 Functional Parameters
-
31
-
Chapter 4 Functional Parameters
4.1 Parameter Description
The content in each column of the parameter table is described as follows:
Parameter
Name
Setting Range Factory Setting
Unit
Operation
Number
of the
functional
parameter
Full name
of the
functional
parameter
Valid range of
the functional
parameter
value
Factory setting
of the functional
parameter
Unit of the
functional
parameter
Operation attribute
of the functional
parameter (operation
allowed or not, and
condition)
★
:The parameter can be viewed but cannot be modified when the system is in the
running state. It can be modified when the system is in the stop state.
●
:The parameter is the actually measured value and cannot be modified.
In commissioning, you only need to adjust the parameters in group F0. Group F1 contains
state parameters, group F2 contains fault parameters, FF contains factory parameters and
group FP contains the specialized application parameters.
Group F0: Basic Parameters
Parameter
Name
Setting Range
Factory Setting Unit Operation
F0-00
System type
0: Escalator
1: Moving walkway
0
-
★
It is used to set the system type and defines the upper limit of nominal speed (F0-01).
Parameter
Name
Setting Range
Factory Setting Unit Operation
F0-01
Nominal speed
0.30–0.90
0.50
m/s
★
It indicates the nominal speed when the escalator/moving walkway is in the no-load state.
Parameter
Name
Setting Range
Factory Setting Unit Operation
F0-02
Radius of driving
chain sprocket
0.30–0.90
0.33
m
★
It indicates the radius of the driving chain sprocket. The linear speed of the driving chain
sprocket calculated based on the radius is the step running speed.
Parameter
Name
Setting Range
Factory Setting Unit Operation
F0-03
PPR of driving chain
sprocket
1–200
65
-
★
It is used to set the pulses per revolution (PPR) of the driving chain sprocket, namely, the
number of teeth of the driving chain sprocket.