GENERAL INFORMATION

IPAQ R202 is a low cost, non-isolated, easy-to-use 2-wire temperature 

transmitter for Pt100 input intended to be used in industrial environment.

IPAQ R202 is designed to be mounted on a 35 mm DIN Rail. 

The transmitter is configured from a PC via a USB port, connected via the 

INOR USB Interface, by using the ConSoft program. 

All necessary hardware and software for configuration are included in the 

ICON Configuration Kit, 70CFGUS001.

 

R202

DATA  (short form)

Input Pt100 

3-wire connection

Pt100 (IEC 60751, 

α

=0.00385) 

-200 to +850 °C / -328 to +1562 °F

Adjustments - Zero                     Any value within range limits
Adjustments - Minimum span  20 °C / 36 °F
Output 

4-20 mA, temperature linear

Sensor failure indication 

Upscale (≥21.0 mA) or downscale (≤3.6 mA)

NAMUR Compliance 

Current limitations and failure currents acc.  

 

to NAMUR NE 43

Response time 

0.13 to 54 s, adjustable filtering level

Ambient temperature  
Storage and operation 

-40 to +85 °C / -40 to +185 °F

Galvanic isolation No
Power supply 

6 to 35 VDC

Accuracy  

Max. of ±0.1 °C / ±0.2 °F or ±0.1 % of span

Sensor error correction 

Via two-point correction

Runtime counter 

Hour counter for elapsed operational time

Mounting 

DIN rail acc. to EN 60715 / EN 50022, 35 mm

Factory settings
Input 

Pt100 3W, 0 to 100 °C

Output 

4 to 20 mA

Filtering level 

Response time 0.9 s

Sensor failure indication 

Upscale (≥21.0 mA)

CONFIGURATION

Before making a configuration of IPAQ R202 you need to do 

following:

1.  Install the configuration software ConSoft and drivers for the  

 

INOR USB communication interface on a PC.

2.  Connect the USB Interface to a free USB port of your PC and  

 

wait for automatic installation of the USB Interface.

Please refer to the installation guide for ConSoft for detailed

installation instructions.

 

Required versions of configuration software: 

ConSoft, 3.1.0 or higher

USB Interface, firmware 1.2.06 or higher

Connections: 

     

PC to Interface: through USB type A to USB type B connection cable

Interface to transmitter: Mini USB type B to Mini USB type B cable

 

   

 

 

Configuration procedure:

1.  Connect the transmitter to the PC via the USB Interface, LED indicator   

 

“DEV” on the USB Interface becomes green. 

 

Configuration can be performed with or without connected power  

 

supply to the transmitter.

2.  In ConSoft, click on the “Read” button. The software will recognize     

 

the connected transmitter and open the configuration window.

3.  In the “C202/R202” configuration window you can edit:

 

a. Measuring range in three different engineering units

 

b. Upscale or downscale action at sensor errors

 

c.  Compensation for known sensor errors

 

d. TAG-number

4.  The selected configuration is downloaded to the transmitter by  

 

clicking the button “Write”, when the data transfer is complete,  

 

the transmitter begins using the new parameters directly.

MEASURE OF SUCCESS

This product should not be mixed with other kind of scrap, after usage.

It should be handled as an electronic/electric device.

www.