ICT200-LVD LOW VOLTAGE DISCONNECT SWITCH 

This  automatic  LVD  switch  is  designed  to  protect  your  battery 
from  excessive  discharge  that  may  cause  permanent 
degradation of the cells. The ICT200-LVD disconnect switch may 
be wired in series with the battery positive or negative lead for 
use with any dc grounding configuration. 

 

The  intelligent  back-lit  LCD  display  makes  set  up  simple. 
Selecting  your  nominal  battery  voltage  at  first  power  up  will 
automatically  set  the  disconnect  and  reconnect  voltages  to 
standard levels for the battery voltage chosen. Custom voltage 
thresholds  may  be  set  for  specialized  applications,  and  the 
internal  contactor  may  be  manually  set  to  an  open  or  closed 
state if required. The display also shows the battery voltage and 
the current drawn by the load, along with the operating state of 
the LVD and any alarm conditions. 

 

CONNECTION DIAGRAM 

 

WARNINGS 

Risk of personal injury or damage to equipment and property! 
Always observe the following: 

 

Use an appropriate over-current protection device in line 
with the battery sense connection, and in line with the 
main load battery connection 

 

Use a disconnect switch or circuit breaker in series with the 
main load battery connection, for installation and service 

 

Use wire and connectors rated for the maximum load 
current, and size of fuse or circuit breaker. Tighten all 
connections 

 

Ensure load current does not exceed max rating of unit 

 

INSTALLATION 

Mount  the  unit  in  a  standard  19”  equipment  rack  using  the 
front panel mounting ears (included). 

 

With the main battery service disconnect switch open; connect 
the LVD LOAD and BATTERY terminals using appropriately sized 
wire,  disconnect,  and  an  over-current  protection  device  rated 
for the application. Bond the chassis to ground using the ground 
stud located on the back panel.

  

Installation

 (continued)

 

Connect  the  alarm  output  contacts  (if  desired)  to  an  external 
monitoring  system,  using  the  REMOTE  connector  (P10) 
terminals 1, 2, and 3 as shown in the REMOTE table, below. Use 
the mating 7 pin REMOTE connector plug (included). 

 

Connect  the  battery  sense  lines  using  22  AWG  or  larger  wire 
and  an  over  current  protection  device  (5A  fuse  or  circuit 
breaker) to the battery terminals. These lines provide power to 
the  unit,  and  allow  the  control  circuitry  to  sense  the  battery 
voltage. The internal display should then power up, allowing the 
nominal battery voltage to be set (see Initial Set Up section). 

 

REMOTE Connector P10: (pins 4, 5 not used) 

 

CONTROL PANEL MENUS

 

FRONT PANEL CONTROL 

Use  the  front  panel  scroll  knob,  ENTER,  and  BACK  buttons  to 
navigate  the  interface  menus  and  set  up  the  following 
parameters: 

 

Nominal battery SYSTEM VOLTAGE (set to 12/24/48V 
to correctly scale factory default LVD points)

 

 

Restore to FACTORY SETTINGS (default values, 12V 
system, AUTO mode, contactor open) 

 

LVD SETTINGS (set custom disconnect and reconnect 
voltage levels, set mode for AUTO disconnect or 
MANUAL-OPEN/MANUAL-CLOSED configuration)

 

 

SECURITY SETTINGS (set a four digit password and 
lock-out timer to prevent unauthorized adjustment of 
LVD settings, if desired) (default is no password)

 

 

Use the scroll knob to cycle between the top-level menus, press 
ENTER to select a menu for adjustment, and then use the scroll 
knob  to  select  the  parameter  for  adjustment,  press  ENTER  to 
select. 

 

Adjust the selected parameter with the scroll knob; press ENTER 
to  activate  the  setting.  Use  the  BACK  button  to  return  to  a 
higher level menu 

 

 

Pin Number 

Name 

Note 

Common 

Alarm out common 

NC 

Alarm NC (alarm state) 

NO 

Alarm NO (alarm state) 

BATT POS 

Battery sense Positive 

BATT NEG 

Battery sense Negative 

SET SYSTEM VOLTAGE 

NOMINAL BATT V: 

12V 

FACTORY SETTINGS 

BATTERY:              13.6V 

83A 

LVD MODE: 

AUTO 

DISCONN VOLTAGE: 

10.5V 

RECONN VOLTAGE: 

12.5V

 

LVD SETTINGS 

DISCONN VOLTAGE: 

10.5V 

RECONN VOLTAGE: 

12.5V 

LVD MODE: 

AUTO 

SET SECURITY SETTINGS 

PASSWORD 
CLEAR PASSWORD 
SET LOCKOUT TIMER 

SET SYSTEM VOLTAGE 

NOMINAL BATT V: 

24V 

<SCROLL> TO CHANGE 
PUSH <ENTER> TO SET 

LVD SETTINGS 

DISCONN VOLTAGE: 

11.2V 

<SCROLL> TO CHANGE 
PUSH <ENTER> TO SET 

ENTER PASSWORD 

0*** 

<SCROLL> TO CHANGE 
PUSH <ENTER> TO SET 

Press ENTER to 
activate setting 
after

 

adjustment

 

Press ENTER to 
activate setting 
after adjustment 

Press ENTER to 
activate setting 
after adjustment 

Scroll 

Scroll 

Scroll 

Press ENTER to 
select desired 
parameter to 
adjust 

Press ENTER to 
select desired 
parameter

 

to 

adjust

 

Press ENTER to 
select desired 
parameter to 
adjust 

Home Screen 

System Voltage Setting 
(Nominal) 

LVD (min)  

LVD (default) 

LVD (max)* 

Reconnect 
(min)* 

Reconnect 
(default) 

Reconnect 
(max) 

12V (default) 

10.5 

11.5 

12.5 

12.0 

12.5 

13.8 

24V 

21.0 

23.0 

25.0 

24.0 

25.0 

27.6 

48V 

42.0 

46.0 

50.0 

48.0 

50.0 

55.2 

 

ADJUSTABLE LVD SETTINGS: 

*Note: The disconnect voltage setting cannot be set higher than the 
reconnect  voltage  setting,  less  a  1.0V  guard  band.  Likewise  the 
reconnect voltage cannot be set lower than the LVD point plus 1.0V. 

e.g.  for  a  12V  system  with  the  reconnect  V  set  to  12.6V  the  LVD  set 
point cannot exceed 11.6V 