12
Innovative Circuit Technology Ltd.
Alarm Status
This page displays the status of currently active alarms as well as the alarm
history.
Device Setup
Use this page to configure the panel settings. Click on the
Save Settings
button
when finished to save and implement all new changes.
Device Info
Site Name
: Enter a custom descriptive name for the panel
Model:
Displays the ICT model number for the panel
Hardware
: Displays the hardware version of the panel
Date and Time Settings
Current System Time
: Displays the date and time used in the panel’s internal
clock for time stamping data entries in the data logs. This clock may be set
manually, or synchronized with a remote NTP Time Server over the Internet
(recommended).
Synchronize with NTP Server
: Check this box to select automatic
synchronization with the external server. (recommended)
NTP Server
: Enter the name or IP address of the NTP Server used for date
and time synchronization, such as “
pool.ntp.org”
.
Time Zone
: Select the appropriate time zone relative to GMT for your unit so
that the NTP server time can be converted to your local time zone.
Set Time Manually
: Checking this box will allow the unit’s clock and calendar
to be set manually by entering date and time in MM/DD/YY and HH:MM:SS
format.
Power-On Sequencing/Cycling
Sequence/Cycle Delay
: Entering a time delay in this field (0-60s) will cause
all outputs to be enabled in sequence when the
Enable All Outputs
button is
pressed on the
Status & Control
page, rather than enabling all outputs
simultaneously. This delay helps prevent power surges that can occur when
too many devices are turned on at the same time. Setting this time to 0 or
leaving the box blank will cause all outputs to always be enabled
simultaneously. (Factory default).
Note the
Sequence Delay
time will also be used as the
Power Cycling
time
delay for each output that has the
Power Cycling
feature enabled on the
Output Setup
page.