8

 

ALARMS 

8.1.1

 

GENERALITY' 

In case of problems or failures, take note of any error code appeared on the display of the electronic control unit or the remote 
control, make a note of the model and the serial number of unit you have (present on the nameplate attached on the side of the 
unit) and contact your installer. 

 

8.1.2

 

PROBLEMS WITHOUT ERR OR INDICATION ON DISPLAY

 

Problem 

Causes 

Remedies 

Display off 

No power 

(Off light switch) 

Check the connection to the electricity grid 

Check and if necessary replace the fuse on the power 
supply connector (black) on the side of the unit. 

Air flow Little or no 

The premises remain 
wet 

clogged filters 

 

Replace the filters 

exchanger plugged 

Clean the heat exchanger 

ice cream exchanger 

Bring the heat exchanger in a warm place and wait for it 
to thaw, do not heat with direct heat. 

dirty Fan 

Clean the fan 

Ducts fan clogged 

Clean the ventilation ducts 

Outside temperature below 0 ° C 

The unit could be in antifreeze mode, wait until the 
outside temperature rises or provide for the installation 
of an electric heater for pre-heating. 

Noise level high 

Noise coming from the 

Verify the presence of cracks and / or air leaks from the 
unit panels 

Check the siphon connection 

Verify if the engines are running properly (bearings) 

Noise coming from the pipes 

Verify the presence of cracks on the suction ducts / entry 
/ expulsion 

Vibrations 

Elevate 

Panels that vibrate 

Verify the integrity of the panels and the unit in 
aluminum profiles 

Check the correct closure of the lid unit and the panel 
that covers the electronic card 

Check that there are no walls that can transmit vibrations 
to the wall / floor / ceiling 

Pale of unbalanced fans 

Check the integrity of the blades 

Clean fans 

Check that the fans are still present small metal clip for 
balancing the blades 

Loss of condensate 

Condensate drain clogged 

Clean the condensate drain 

The condensate does not flow from the 
exhaust pipe into the collection tray 

Verify that the unit is perfectly flat 

Check that the condensate drain connections are clogged 

 

Содержание HRW DOMO

Страница 1: ...50 000 CF P IVA 01827470228 Iscrizione REA nr 180610 Num reg Imprese TN 10656 Numero Meccanografico TN025148 www innovaenergie com Pag 1 N420229A_ManualHRW_rev2 en docx INSTALLATION USE AND MAINTENANC...

Страница 2: ...N COMPONENTS OF THE UNITY 9 1 1 10 PACKING AND TRANSPORT 9 1 1 11 RECEPTION CONTROL AND HANDLING 10 1 1 12 REMOVAL AND DISPOSAL 10 2 INSTALLATION 11 2 1 1 INSTALLATION CONDITIONS 11 2 1 2 POSITIONING...

Страница 3: ...NING AND METHOD FOR USE 26 6 1 1 WORKING VERSION I 26 7 MAINTENANCE 29 7 1 1 CLEANING OR REPLACING FILTERS 29 7 1 2 CLEANING THE COOLER 29 7 1 3 GENERAL CLEANING UNIT 30 8 ALARMS 31 8 1 1 GENERALITY 3...

Страница 4: ...ves the right to update products and manuals without any obligation to the previous update except in exceptional cases Contact the Sales Department of the manufacturer for further information or techn...

Страница 5: ...k It warns that failure to observe the precaution may cause electric shock DANGER It warns that failure to observe the precaution may cause risk of injury to exposed persons WARNING It warns that fail...

Страница 6: ...or on electrical panels any incomplete connection of the covers may cause overheating of the terminals Make sure that it meets the ground connection not to ground the appliance on the distribution pi...

Страница 7: ...The unit is identifiable through the label on the front panel of the same lower On the package will be an additional nameplate with dell drive model and shipping references The plaque on the packaging...

Страница 8: ...h painted externally is galvanized all indoor ofthe unit Structure perimetric self supporting in sheet metal galvanized There insulation of panels is realized with insulating to high performance of th...

Страница 9: ...1 1 10 PACKING AND TRANSPORT The units are supplied to the transport fixed on a wooden pallet and inserted into cardboard boxes To facilitate travel units are equipped with a wooden pallet and the ho...

Страница 10: ...ssors heat exchangers etc Keep anyway the unit horizontally without tilting All indications about the necessary precautions in order not occur made damage to the unit and the indication of the weight...

Страница 11: ...the condensation water must be discharged not frozen at a certain inclination using a siphon not install the unit in areas with a high relative humidity such as the bathroom or toilet to avoid condens...

Страница 12: ...direct contact with the walls to avoid possible noises from contact insert strips of rubber or neoprene in this case Ceiling mount Floor mounting For mounting unit on the ground is needed Position 4...

Страница 13: ...exhaust condensation adhere to the following standards give a slope of at least 2 to the exhaust pipe provide for the possibility to disconnect the drain pipe for maintenance in particular in the cas...

Страница 14: ...fferent applications and versions are always common to all units Make to respect the flows indicated on the plates input incoming water towards the unit output outgoing water from the unit Make so tha...

Страница 15: ...haracteristics could affect the integrity of the hydraulic part of the the unit Check water quality DESCRIPTION Limit value Hardness 10 F PH value 7 5 9 Oxygen 2 mg l Conductivity 500 uS cm Iron 2 mg...

Страница 16: ...tions are male threaded Observe the IN and OUT as the unit water inlet as a water outlet from the unit Connect the pipes with threaded female fitting and tighten with dedicated tools Be careful not to...

Страница 17: ...r l Pag 17 N420229A_ManualHRW_rev2 en docx 4 1 3 2 3 WAY VALVE CONNECTION The connections of the valves to 2 3 Optional are to be made as indicated Attention to comply with the instructions placed on...

Страница 18: ...ch take account of the compressor inrush currents as well as the maximum attainable load THE related data are indicated on the wiring diagram and on the unit nameplate E forbidden to enter the electri...

Страница 19: ...Innova S r l Pag 19 N420229A_ManualHRW_rev2 en docx...

Страница 20: ...ir quality regulator Contact closed active function CHILLER Chiller generators Activation Clean Contact Hot cold activation required N CL CP Water valve battery post Contact voltage 220v REMOTE DISPLA...

Страница 21: ...t Closed alarm units ON OFF REMOTE for On Off control input units Closed unit ON SUMMER WINTER Input for change of digital input seasonal Closed units in summer FAN ONLY Input unit for forcing in vent...

Страница 22: ...SION Link remote panel CNV The I Version tab provides a capacitive touch type remote control for the management of all functions of the unit and arranged for installation on wall or outer box 502 For...

Страница 23: ...ORE the unit The CNV panel provides for the control of multiple units E can connect up to 30 units to be managed by the one remote control panel They will have to be connected in series connection wit...

Страница 24: ...it OFF Contact open Unit ON CONNECTION TO ELECTRONIC CONTROL QUALITY AIR SQA E provided the connection of a regulator for the air quality of the digital type On the controller there are three levels o...

Страница 25: ...umidity NB E can connect both the air quality regulator is the humidity regulator in parallel on the same terminals CONNECTION VALVE AFTER BATTERY The unit provides for the control of a valve battery...

Страница 26: ...ity switch 3V Below are given the keys present on the main form Meaning of the main display keys Allows the ignition keyboard unit is turned off Button for changing the set temperature Keys for select...

Страница 27: ...the speed the speed sensors The input is a digital input to connect a clean contact AUTO Function 6 1 1 4 CHANGING SEASON The change of season on the version I must be made from the keyboard Hold for...

Страница 28: ...nualHRW_rev2 en docx 6 1 1 6 ADJUSTING BRIGHTNESS PANEL With Ignition is off hold down the button for 5 seconds until the written 01 With the button set the value to 00 and wait 20 seconds to verify t...

Страница 29: ...he state of the heat exchanger at each cleaning exchange filters and proceed to its cleaning if deemed appropriate This operation must be performed only by qualified personnel installer To clean the h...

Страница 30: ...n the case of ceiling installation disconnect the drain pipe open the cover by unlocking the fastening hooks on it proceed to the verification and eventual cleaning of the fans the condensate drain an...

Страница 31: ...Outside temperature below 0 C The unit could be in antifreeze mode wait until the outside temperature rises or provide for the installation of an electric heater for pre heating Noise level high Noise...

Страница 32: ...e and failure of the probe reading Check the connection of the probe or replace it NO LINK communication alarm Check the green LED on the board The LED indicates the presence of power on the card Chec...

Страница 33: ...Innova S r l Pag 33 N420229A_ManualHRW_rev2 en docx 9 NOTES AND INFORMATION SERVICE NOTE...

Страница 34: ...Innova S r l Pag 34 N420229A_ManualHRW_rev2 en docx 09 2017 rev 3 Technical Assistance Center The data contained herein may be modified by the manufacturer without notice...

Отзывы: