ALARMS 

8.1.1

 

GENERALITY 

In case of problems or breakdowns, take note of any error code appearing on the display of the electronic control unit or of the 

remote control, take note of the model and serial number of the unit you own (present on the identification plate attached to the 

side of the unit) and contact the installer. 

8.1.2

 

PROBLEMS WITHOUT ERROR INDICATION ON THE DISPLAY 

 

PROBLEM 

CAUSE 

REMEDIES

 

The fans are not active 

-The power supply is not switched on 
- The fan speed regulation device does not 

work 
- Wrong electrical connections 
- Fans in thermal protection 

-Check the power supply on the fan 
- Check the fan speed adjustment device 
-Check that the fan is not overheated and in thermal 

protection 

Insufficient air flow or 

useful pressure 

-Clogged filters 
- Insufficient rotation speed 
- Clogged pipes or exchanger 

-Clean the filters 
-Increase the rotation speed 
-Clean pipes or exchanger   

Insufficient efficiency of 

the exchanger 

- Exchanger fins clogged 

-Clean the surfaces of the exchanger 

Excessive vibration and 

noise 

-Incorrect installation of the drive 
- Incorrect installation of the pipes 
- Imbalance of the impeller of the fans 

-Check the unit's brackets and fixings 
-Check brackets and pipe fastenings 
- Check the fan impellers status 

Water leaks from the 

unit 

- Condensate drain blocked 
-Siphon not installed correctly 

-Clean the condensate drain 
-Check the correct installation of the siphon 

Difficult starting 

- Supply voltage too low 
Insufficient engine torque 

-Check that the power supply voltage is not below 10% of the 

rated voltage on the plate 
-Power the unit with partially closed dampers in order to 

reduce the motor starting torque. If starting correctly, replace 

the motor with a larger one. 

 

8.1.3

 

ALARM SIGNAL 

Below is a list of all the alarms managed by the application. 

The presence of an alarm has two display modes: 

 

an error code present on the EQA649 / EQB649 or ERA649 / ERB649 command; 

 

a led on the electronic board that shows a flashing sequence with the type of alarm present. 

 

 

Содержание HRC +

Страница 1: ...re capital int vers 150 000 Tax code VAT number 01827470228 REA registration nr 180610 Reg Companies TN 10656 Mechanographic number TN025148 www innovaenergie com INSTALLATION USE AND MAINTENANCE MANU...

Страница 2: ...LIVERY STATE 8 1 1 11 START UP REQUIREMENTS 8 1 1 12 DISASSEMBLY AND DISPOSAL 8 2 INSTALLATION 9 2 1 1 INSTALLATION CONDITIONS 9 2 1 2 UNIT POSITIONING 10 2 1 3 CONDENSATE DRAIN CONNECTION 17 3 AREAUL...

Страница 3: ...ING OR REPLACING FILTERS 33 7 1 2 CLEANING THE HEAT EXCHANGER 34 7 1 3 GENERAL CLEANING OF THE UNIT 34 8 ALARMS 36 8 1 1 GENERALITY 36 8 1 2 PROBLEMS WITHOUT ERROR INDICATION ON THE DISPLAY 37 8 1 3 A...

Страница 4: ...les Department to receive further information or updates to the technical documentation and for any improvement proposals to this manual All reports received will be rigorously examined 1 1 2 BASIC SA...

Страница 5: ...the presence of moving parts and involves a risk of damage to exposed people 1 1 4 WARNINGS The unit must be installed by qualified and authorized personnel according to the regulations in force in th...

Страница 6: ...liance on distribution pipes Momentary surges of high intensity could damage the unit Installations performed outside the warnings in this manual or use outside the operating limits will instantly voi...

Страница 7: ...h polyethylene insulated interiors HEAT EXCHANGER High efficiency countercurrent cross flow polypropylene exchanger Low freezing temperatures and operation down to 25 C Very high exchange efficiency F...

Страница 8: ...rotection control unit with display predisposition for easy connection to the network and remote control 1 1 10 DELIVERY STATE The supply includes recovery unit complete with fans installed inside the...

Страница 9: ...he condensate water must be drained not frozen at a certain inclination using a siphon do not install the unit in areas with a high relative humidity rate such as a bathroom or toilet to avoid condens...

Страница 10: ...ale fittings on the unit which will be used to connect the pipes to the outside The ducted installation provides for the possibility of creating a maximum of 8 meters of ducting For non ducted install...

Страница 11: ...of the unit Place the installation template on the ceiling Mark or drill directly according to the dowel threaded bar used Ensure sufficient space for carrying out maintenance activities the opening o...

Страница 12: ...drill the wall making the two holes for external air and internal air expulsion Prepare the condensate drain if it is conveyed directly outside with the air passage holes Ensure sufficient space for c...

Страница 13: ...of the unit Place the installation template on the ceiling Mark or drill directly according to the dowel threaded bar used Ensure sufficient space for carrying out maintenance activities the opening...

Страница 14: ...nd drill the wall making the two holes for external air and internal air expulsion Prepare the condensate drain if it is conveyed directly outside with the air passage holes Ensure sufficient space fo...

Страница 15: ...oints to remove it Remove the 4 screws of the two aesthetic sides under the grille Extract the side towards the front of the unit in order to release the rear fixings Ensure sufficient space for carry...

Страница 16: ...f a nut and washer on the 4 brackets on the sides Level the unit by tilting it 1 2 towards the left side condensate drain by adjusting the height of the fixing on the brackets Ensure sufficient space...

Страница 17: ...of disconnecting the drain hose for any maintenance in particular in the case of ceiling installation make sure that the discharge end of the pipe is at least below the water level of the siphon make...

Страница 18: ...e expulsion towards the outside For the correct connection of the air ducts refer to the following diagram and the stickers placed on the unit As seen in the unit positioning part there are two instal...

Страница 19: ...Use cables and electrical conductors with adequate sections and in compliance with the regulations in force in the various countries Absolutely avoid running electrical cables in direct contact with...

Страница 20: ...the lower central panel itself after removing the two lower external panels Use the two cable glands on the left side of the unit to enter the electrical cables inside the unit Use electric cables wi...

Страница 21: ...CUSTOMER GRID Speed Booster Contact closed function active CHILLER Post battery generator control or pre heating battery Clean Contact N CL CP Water valve rear coil Live contact 220v REMOTE DISPLAY Re...

Страница 22: ...nection ERA ERB649 Serial control with the possibility of connection to a WIFI network and management of the unit through a dedicated APP The controls can be supplied in both White and Black colors Th...

Страница 23: ...network is an RS485 network Use a 2 wire shielded cable with a maximum length of 150 m Carry out a layout in order to minimize the length of the leads terminate the line with the supplied 120 resisto...

Страница 24: ...Innova Srl Page 24 N420741A_manuale HRC 2022 rev 01 _EN docx...

Страница 25: ...30 v control provided on the board N COMMON CL FIXED VOLTAGE FOR 3 POINT VALVE CONTROL CP ON OFF CONTROL VALVE 2 3 POINTS Water valve rear coil connection POST PRE HEATING GENERATOR BATTERY CONNECTION...

Страница 26: ...m intervening in summer mode Coil with pre heating function The coil has the function of defrosting and anti freeze protection of the unit Installation mount the heater on the fresh air duct connect t...

Страница 27: ...RA649 ERB649 wall mounted touch control The remote control has an internal air quality and humidity sensor for automatic control of the air flow The sensors interact to regulate the air flow and ensur...

Страница 28: ...eating coil Deactivation of the CHILLER contact preheating battery DIP SWITCH B ON OFF Enable unit with modulating battery control Disabling of units with modulating battery control NB The unit model...

Страница 29: ...EQA649 EQB649 or ERA649 ERB649 The keys present in the main screen are shown below Meaning of the keys in the main display Allows the unit to be turned on off from the keyboard Button for changing th...

Страница 30: ...NOMINAL SPEED FUNCTION By pressing the auto key the unit will operate according to the humidity and air quality sensor request setting according to the dipswitch settings made when starting the unit...

Страница 31: ...is given by the display of the message bL All adjustments are disabled for the user and bL appears when any key is pressed By repeating the sequence the keys are unlocked bL Key lock 6 1 4 6 PANEL BR...

Страница 32: ...g and holding the central fan key 3sec The panel immediately shows the humidity detected by pressing one of the two keys and the set humidity set point is shown immediately and it will be possible to...

Страница 33: ...to clean them proceed as follows disconnect the unit from the power supply open the lower external aesthetic covers by removing the fixing screws then open the filter holder caps by removing the addi...

Страница 34: ...sconnect the unit from the power supply open the lower aesthetic covers i by removing the fixing screws remove the lower panel by removing the additional fixing screws remove the filters to access the...

Страница 35: ...sate drain and the internal walls of the unit These operations must only be carried out by qualified personnel installer For cleaning you can use a vacuum cleaner a rag dampened slightly with water a...

Страница 36: ...ed Clean pipes or exchanger Insufficient efficiency of the exchanger Exchanger fins clogged Clean the surfaces of the exchanger Excessive vibration and noise Incorrect installation of the drive Incorr...

Страница 37: ...Innova Srl Page 37 N420741A_manuale HRC 2022 rev 01 _EN docx 1 LED FOR SIGNALING THE UNIT CARD ALARMS 2 PANEL ALARM SIGNALEQA649 EQB649 or ERA649 ERB649...

Страница 38: ...pulsion probe Broken or missing reading of the probe Check the connection of the probe or replace it 3 flashes off 3 seconds Alarm External air probe H4 Broken or missing reading of the probe Check th...

Страница 39: ...______________________________________________________________________________________________________________________________________________________ _________________________________________________...

Страница 40: ...__________________________________________________________________________________________________________________________________ _____________________________________________________________________...

Страница 41: ...Innova Srl Page 41 N420741A_manuale HRC 2022 rev 01 _EN docx N420741A _01 2022 rev 01 The data contained in this manual can be changed by the manufacturer without prior notice...

Отзывы: