Innova HRA-I PLUS Скачать руководство пользователя страница 1

 

 

INSTALLATION, USER AND MAINTENANCE MANUAL

 

 

 

 

 

 

 

                                                            

                                 

 

                                         

 

 

 

 

 

HRA-I PLUS 

 

The compact aggregate for heating, cooling and air renewal in 

nZEB homes 

 

Содержание HRA-I PLUS

Страница 1: ...INSTALLATION USER AND MAINTENANCE MANUAL HRA I PLUS The compact aggregate for heating cooling and air renewal in nZEB homes...

Страница 2: ...NENTS OF THE UNIT 7 1 9 PACKAGING AND TRANSPORT 9 1 10 RECEPTION INSPECTION AND HANDLING 9 1 11 DISMANTLING AND DISPOSAL 9 2 INSTALLATION 10 2 1 INSTALLATION CONDITIONS 10 2 2 POSITIONING OF THE UNIT...

Страница 3: ...EED 19 5 5 NOMINAL SPEED FUNCTION 19 5 6 SEASON CHANGE 19 5 7 DESCRIPTION OF THE AIR QUALITY SENSOR S OPERATION 20 6 MAINTENANCE 20 6 1 1 FILTER CLEANING AND REPLACEMENT 20 6 1 2 CLEANING THE HEAT EXC...

Страница 4: ...r any improvement proposal of this manual All notifications received will be rigorously assessed 1 1 1 ESSENTIAL SAFETY RULES We remind the user that the use of products relying on electricity and wat...

Страница 5: ...us situation may occur Avoid installing the unit in rooms that are very damp or have large sources of heat On the electrical side to prevent any possible risk of electrocution the main switch must be...

Страница 6: ...C Electromagnetic Compatibility Directive 2014 30 EC 1 5 RANGE 1 HRA i PLUS 50 08 1 Defines the total flow rate and the flow rate of the renewal air Model 50 08 500 m3 h total flow rate of which 80 m3...

Страница 7: ...m compared to that subtracted through ventilation FILTRATION Upstream of the recovery unit there is a ePM1 filter on the incoming air and an ePM1 filter on the expulsion air with low head loss STRUCTU...

Страница 8: ...or 2 Room inlet fans 3 General expulsion fan 4 MVHR expulsion fan 5 MVHR outdoor air fan 6 MVHR heat exchanger 7 Outer side battery 8 Inner side battery 9 Electrical panel 10 MVHR extraction filter 11...

Страница 9: ...ote producing photographic evidence of the apparent damage and notifying the apparent damage to the forwarder via registered letter with return receipt requested The manufacturer shall not be held lia...

Страница 10: ...e air pipes and for performing maintenance interventions the consistency of the ceiling wall floor where the unit will be installed must be adequate to the weight of the unit and not cause vibrations...

Страница 11: ...Innova S r l Page 11 HRA I SLIM MANUAL...

Страница 12: ...heat exchanger and the dehumidification batteries the humidity in the internal air condenses within the unit To ensure the correct operation of the heat recovery unit therefore it is necessary to conn...

Страница 13: ...r pipes refer to the following diagram and to the stickers on the unit Table of diameters for the unit s aeraulic connections Unit Diameter Outdoor air mm 200 Expulsion mm 200 Inlet mm 700 x 140 Stale...

Страница 14: ...ed load The relative data appears in the enclosed wiring diagram and on the unit s identification plate It is forbidden to enter the unit with the electrical cables except for the areas specified in t...

Страница 15: ...l differs for the ModBUS communication port or Wi Fi black or white version ECA031II SMART TOUCH wall mounted control panel with thermostat and room probe with integrated Wi Fi module BLACK finish ECB...

Страница 16: ...Innova S r l Page 16 HRA I PLUS Manual 4 4 WIRING DIAGRAM...

Страница 17: ...ply needs to be inserted in the panel for connecting the devices The panel houses a communication board for interacting with the unit through the Modbus RTU protocol To connect the modbus board it is...

Страница 18: ...probe with ModBUS serial port BLACK finish ECB032II SMART TOUCH wall mounted control panel with thermostat and room probe with ModBUS serial port WHITE finish Indicated below are the buttons present o...

Страница 19: ...evices therefore they adapt their number of revolutions in relation to the ducting configuration installation and cleanliness of the filter to reach the pre defined flow rate Fan speed management 5 5...

Страница 20: ...while making sure that they are fully closed to prevent air from escaping if the filters are in the right condition they can be cleaned using a vacuum cleaner or low pressure compressor View for remo...

Страница 21: ...pen the unit s cover by releasing the fixing hooks present on it check and if necessary clean the fans condensate discharge outlet and walls put the cover back on and lock it in place with the fixing...

Страница 22: ...uses Solutions The devoice does not switch on There is no power supply Check for the presence of mains voltage Check that the exclusive magnetothermic switch protecting the device has not intervened i...

Страница 23: ...ing from the unit Check for any cracks and or air leakages from the unit s panels Check the siphon s connection Verify whether the motors turn correctly bearings Noise coming from the ducts Check for...

Страница 24: ...egularly E3 OT outdoor air temperature probe faulty The cooling dehumidification and heating functions can be activated regularly E4 External OPT battery probe faulty The cooling dehumidification and...

Страница 25: ...Innova S r l Page 25 HRA I PLUS Manual 8 NOTES AND INFORMATION MAINTENANCE NOTES Technical Assistance Centre The manufacturer can modify the data contained in this manual without prior notice...