background image

© MASS ELECTRONICS Pty Ltd  2006

Models:

GENII CSFCAH REM: 

Control Station with 3 Speed Fan

DS 15.10

 

August 2013

  

GENII CSFCAH REM

Control Station with 3 Speed Fan

Applications

Expands GENESIS Controller capabilities by providing a numeric output 

display, numerical value input, a single toggle digital input switch and 

three speed fan LED display output for distributed control via RS485.

Application Notes

A GENESIS Controller must have version 4 firmware installed to 

support REM Modules. Version 5.0 or higher Config Software must be 

used to configure a GENESIS Controller that has CSFCAH REM Modules 

connected to it.

One GENESIS Controller can have up to 15 GENII CSFCAH REM Modules* 

connected to it via the REM comms bus.

For detailed connection information to the pre-version 5 GENESIS 

Digital Controller Family, please refer to DS 99.03

Overview

The Innotech GENII CSFCAH REM Control Station Module with 

3 Speed Fan is an expansion device for the GENESIS range of 

Digital Controllers.

The module is powered by 24VAC and provides a limited User 

Interface to the GENESIS Controller. There are no physical 

connections between field equipment and the GENII CSFCAH 

REM, all input/output values are edited and viewed on the wall 

unit.

The GENII CSFCAH REM may be located remotely from the 

GENESIS Controller providing a distributed User Interface for the 

system.

The GENII CSFCAH REM is configured via the wallplate and 

programmed via the GEN2Config Software. The GENII CSFCAH 

REM communicates with the Genesis Controller via the REM 

Comms port. The remote link uses RS485 at a baud rate of 

38400. For pre-version 5 controllers, a Gen II RMI Remote Module 

Interface is required. 

Please refer to DS 15.01 for further information.

Features

•  One three decimal place numerical value input

•  One three decimal place numerical output

•  Two momentary digital inputs

•  One LED digital display output

•  Three ‘Fan Speed’ LED outputs

•  Housed in a switchplate that mounts in standard electrical 

wall plates

•  RS485 interconnection between REM Modules

•  24VAC operation

•  Wiring Diagrams for modules generated by GEN2Config 

Software

•  Adjustable user input range

•  Configurable power on settings

•  LED indication of network traffic on rear to ease debugging & 

setup

Approvals

The GENII CSFCAH REM conforms to:

•  EN 55011 Class B Group 1 & AS/NZS 2064:1997 for RCM 

Labelling

•  FCC Title 47 CFR, Part 15 Class A for FCC Marking

•  UL listed to UL916, File Number E242628

Отзывы: