If a power cord is used, the cord should be plugged into a 30-ampere receptacle.
•
The power cord is
NOT
provided with U.S. electric model dryers.
IMPORTANT
: When permitted by local codes, the dryer electrical supply may be connected by
means of a new power supply cord kit, marked for use with clothes dryer, that is U.L. listed, rated at
120/240 volts minimum, 30 amperes with three No. 10 copper wire conductors terminated with closed
loop terminals, open-end spade lugs with turned up ends or with tinned leads.
1. size of the conductors and the type of cord.
2. 3/4 in. (1.9 cm) UL-listed strain relief
•
Do not reuse a power supply cord from an old dryer. The power cord electric supply wiring must be
retained at the dryer cabinet with a suitable UL listed strain relief.
•
Where grounding through the neutral conductor is prohibited. Grounding through the neutral
conductor is prohibited for (1) new branch-circuit installations, (2) mobile homes, and (3)
recreational vehicles, and (4) areas where local codes prohibit grounding through the neutral
conductor.
(Use 4-prong plug for 4 wire receptacle, NEMA type 14-30R)
ELECTRIC MODELS - Canada Only
•
A 120/240 volt, 60 Hz AC approved electrical service fused through a 30 ampere fuse or circuit
breaker on both sides of the line is required.
•
All Canadian models are shipped with the power cord attached. The power cord should be plugged
into a 30 ampere receptacle.
NOTE:
It is not permissible to convert a dryer in Canada to 208 volts.
REPLACEMENT PARTS AND ACCESSORIES
If your dryer requires replacement parts or accessories, contact the dealer from whom you
purchased your dryer or Inglis Customer Service,Customer Interaction Center Whirlpool Canada LP
1901 Minnesota Court Mississauga, ON L5N 3A7 ,phone 1-800-807-6777 for Canada, for information
on the nearest authorized Inglis Parts Distributor.
8
ELECTRICAL CONNECTIONS
BEFORE OPERATING OR TESTING,
follow all grounding instructions in Grounding Section.
An individual branch (or separate) circuit serving only this appliance is recommended.
DO NOT USE AN
EXTENSION CORD.
GAS MODELS – U.S. and Canada
A 120 volt, 60 Hz AC, approved electrical service, with a 15 ampere fuse or circuit breaker is required.
ELECTRIC MODELS – U.S. Only
Most U.S. dryers, as manufactured, require a 120/240 volt, 60 Hz AC approved electrical service. Some
require 120/208 volt, 60 Hz approved electrical service. The electric service requirements can be found on
the data label located on the front behind the door. A 30 ampere fuse or circuit breaker on both sides of the
line is required.