ABH2015IQE01_ - Installation and Operation Manual
Hardware type A
Digital Input 1
J54 DIGITAL INPUT 1
Digital Input 2
J54 DIGITAL INPUT 2
These digital inputs can be configured for different purposes (see
“18.13. Configuring the digital inputs”
) and
used with a potential-free contact or with a power supply, both outside the unit.
1+
R
R
1-
1+
+
-
1-
V
External potential-free contact
External power supply
The truth table for these inputs is as follows.
Connector
CPU
Potential-free contact
Voltage level
Open
5 V ~ 24 V
“0”
Closed (R < 100 Ohm)
0 V
“1”
Closed (R > 100 Ohm)
1 V ~ 5 V
X
Hardware type B
Hardware type B
Digital Input 2
J54 DIGITAL INPUT 2
Input 2 can be configured for different purposes (see
“18.13. Configuring the digital inputs”
potential-free contact or with a power supply, both outside the unit.
43
Connecting the digital inputs
Ingeteam