ABH2015IQE01_ - Installation and Operation Manual
11. Connecting the PV array
These units can be connected to a PV array.
This chapter explains the requirements and process for connecting the PV array wiring to the unit. Read carefully
before starting the connection process.
CAUTION
The PV array cannot be grounded, so its terminals must be isolated from ground.
INFO
The inverter will only start if the ground impedance of the PV array is higher than 18.3 kOhms.
11.1. Safety instructions for connecting the PV array
CAUTION
Before you start to make the connections, make sure there is no voltage in the inverter. Verify that the AC
protection of the auxiliary genset and the DC protection of the storage system are open, as well as the PV array
and the consumption grid.
Do not switch on the power
to the unit until you have successfully made the rest of the connections and the unit
is closed.
When carrying out the connections, respect the polarities marked on the unit.
Ingeteam accepts no liability for any damages caused by an incorrect connection.
11.2. Wiring requirements for connecting the PV array
The wiring gauge for connecting the PV array is specified in the following table:
INGECON SUN STORAGE 1Play
Wiring gauge
4 ~ 6 mm
2
Connector type
MC4
11.3. PV array connection process
To carry out the connection of the PV array, follow the steps below:
1. Ensure that the DC switch for the PV array, which is located in the lower part of the unit, is OFF.
DC switch for the PV array
34
Connecting the PV array
Ingeteam
Содержание INGECON SUN STORAGE 1Play
Страница 1: ...INGECON SUN STORAGE 1Play Installation and Operation Manual ...
Страница 70: ...Notes ...
Страница 72: ...ABH2015IQE01_ 12 2021 Ingeteam Power Technology S A www ingeteam com ...