46
Ingeteam Energy, S.A.
AAV2000IKI01
Installation manual
Terminal strip for communications accessories
CAUTION:
As long as the panels are exposed to the light, the DC cables will carry potentially dangerous voltage
levels.
Never handle the connections before disconnecting the inverter from the grid and the PV array.
5.4.3. Order of connecting the unit
The basic connections to be made with the Ingecon
®
Sun Power Max units are as follows, in this order:
1.
Connecting the insulation failure detection switch (optional).
2.
Communication line (optional).
3.
Connecting the various grounding connections.
4.
Connecting the auxiliary supply.
5.
Connecting the 3-phase inverter system to the power grid.
6.
Connecting the DC cables from the PV array.
The following sections describe how to make these connections.
5.4.4. System wiring diagram
The electrical system of Ingecon
®
Sun Power Max units matches the following diagram (for example, a 500TL model):