19
Ingeteam Energy, S.A.
AAV2000IKI01
Installation manual
•
All units must have enough space for four 90-degree fasteners, one for each corner, and two additional
180-degree fasteners for each location with two different cubicles. For each unit, reserve minimum area on the con-
crete slab as follows:
Equipment
Space
IS 250 TL, 315HE TL, 365HE TL, 400HE TL, 420HE TL
Rectangle 2680 x 1040 mm
IS 375 TL NAC, 500HE TL NAC, 550HE TL, 600HE TL,
630HE TL
Rectangle 2740 x 1040 mm
IS 375 TL, 500HE TL, 550HE TL, 600HE TL, 630HE TL
Rectangle 3280 x 1040 mm
IS 500 TL NAC, 625HE TL NAC, 730HE TL NAC,
800HE TL NAC, 840HE TL NAC
Rectangle 3360 x 1040 mm
IS 500 TL, 625HE TL, 730HE TL, 800HE TL, 840HE TL
Rectangle 3900 x 1040 mm
2.2. Environmental characteristics
The environmental conditions for operation are:
Ambient conditions
Minimum temperature
-20 °C
Minimum surrounding air temperature
-20 °C
Minimum surrounding air temperature
65 °C
Maximum relative humidity without
condensation
95%
For further information see “3. Operating, conservation and transport conditions”
2.3. Characteristics of the electrical installation
Ingecon
®
Sun Power Max units are designed for connection to a dedicated network with an IT-type neutral connection
scheme.
An IT scheme has no directly grounded feed point.
In this system, the resulting intensity of a first phase against mass or phase against ground fault is sufficiently low as
to not cause the appearance of dangerous contact voltages.
2.4. EMC requirements
The Ingecon® Sun Power Max units are equipped with the necessary filtering elements to comply with EMC require-
ments for industrial applications in order to prevent disturbances in other equipment outside the installation.
All Ingecon
®
Sun Power Max units are connected to the grid through a low to medium voltage transformer with a star-
delta configuration. This transformer gives the unit galvanic isolation that affects its good performance in terms of
noise emission. This is why:
CAUTION
Any auxiliary element must be connected to the low voltage network powering Ingecon
®
Sun Power
Max units via a galvanic isolation transformer.