9.3. Inverter alarms due to protections
Code
Description
0100H
This alarm goes off when a AC protection element is triggered.
The items monitored are:
Q
1
, Q
3
, Q
4
, Q
5
, F
ac
, RV
ac
, K
1
Which are the protections for the filters and AC intakes and DC intakes and contactor.
In normal operation, all contacts should be closed, except for the contactor circuit. Check the signalling
circuit to see where it is broken. The causes may be broken cables in the circuit, a triggered protection,
fused arresters or a connector out of its base.
Units with transformer:
X7.5
14
13 14
13 14
13 14
13
Q
3
Q
4
X1.5
Q
5
Q
1
X8.4
53
54
K
1
X1.3
TL units:
X7.2
14
13 14
13 14
13 14
13
Q
2
Q
4
X1.5
Q
5
Q
AC
X8.6
53
54
K
1
X1.3
0200H
This alarm goes off when a DC protection element is triggered.
The items monitored are:
RV
DC
Units with transformer:
X7.5
RV
DC
X1.1
TL units:
X7.2
RV
DC
X1.1
If a grounding kit is used, different protections will have been triggered.
The items monitored are:
RV
DC
,
Q
10
Units with transformer:
X7.5
RV
DC
Q
10
X1.1
TL units:
X7.2
RV
DC
Q
10
X1.1
In normal operation all contacts must be closed. Check the signalling circuit to see where it is broken.
The causes may be broken cables in the circuit, a triggered protection, fused arresters or a connector
out of its base.