AAS2000IKI01
43
Installation manual
Ingeteam Power Technology, S.A.
5.6.3. Remote triggering kit
In some countries, current regulations require remote protection to be implemented in inverters to open the connec-
tions. To achieve this a kit may be used which opens the thermomagnetic circuit breaker on the grid connection.
To activate the coils that make the thermomagnetic circuit breakers open, just close a volt-free contact in the remote
activation terminals. The contact must be able to work with 230 Vac 50/60 Hz and 40 VA power.
This kit does not provide remote resetting. The unit must be reconnected manually.
5.6.4. Heating resistor kit
In installations in which the minimum ambient temperature may be less than -20 °C, it is recommended that a heat-
ing resistor kit be installed.
The heating resistor is supplied by 230 Vac 50/60 Hz, connected to terminals X220. It is protected by a thermo-
magnetic circuit breaker. The current when the circuit is closed is approximately 8,5 A. The temperature regulator
is set for 0 °C.
The heating resistor power is 550 W.
The connection terminals allow 2,5 mm
2
cables.
A
A