DRYER OPTION
33
SSR UP6 15, UP6 20, UP6 25, UP6 30
CALIBRATION
CCN
SETTING
COMPONENT
89320709
89327902
29.0 psig
(2 bar)
(+0.1, –0)
Automatic expansion valve
89327928
START:
113
_
F (45
_
C)
STOP:
104
_
F (40
_
C)
Fan condensing temperature
switch (TV)
The dryer is supplied factory set and therefore requires no further
calibration.
ENGINEERING DATA
Compressor
UP6 20/25/30 or HA dryer
Maximum operating
pressure psig (bar)
125
(8.62)
150
(10.34)
200
(13.79)
Factory set reload
pressure psig (bar)
110
(7.58)
135
(9.31)
185
(12.76)
Model
UP6 20 /
UP6 15 HA
UP6 25 /
UP6 20 HA
UP6 30 /
UP6 25 HA
Pressure Dew Point (
_
F)
(see note 3. below)
38
Base–Mounted Dryer
Package Weight (lb)
1411
1451
1537
120 Gallon Tank Dryer
Package Weight (lb)
1735
1775
1861
240 Gallon Tank Dryer
Package Weight (lb)
2004
2044
2130
Electrical Supply
(+/– 10%) (AC)
(see note 2. below)
115V / 1ph / 60Hz
L.R.A. Current (Amps)
45.0
48.8
48.8
F.L.A. Current (Amps)
9.6
12.3
12.3
Total Installed Power (kW)
0.96
1.19
1.19
Electrical Protection Class
(Std.)
NEMA 1 (IP20)
Refrigerant Type
134a
Notes:
1. Electrical data refers to dryer only.
2. The dryer requires a separate power supply from the compressor
drive.
3.
Rated at:
Working Pressure (psig)
100
Inlet Air Temperature (
_
F)
100
Ambient Temperature (
_
F)
100
Relative Humidity (%)
100
Notes on the use of the Schrader non–return valve.
ATTENTION
1. This unit is equipped with refrigerant as for quantity and kind clearly
shown in operating manual and with identification label.
2. Any ordinary test and / or refrigerant recharge by means of
connections can take place only after refrigerant evacuation. The
evacuation must be proportional to dimensions and length of the
connections used. The use of the valve can be justified only when the
dryer is not in working order.
3. During the unit guarantee period, the Schrader valve can be used by
authorized staff only, otherwise any damage caused by a wrong
refrigerant recharge will invalidate warranty.
Содержание SSR UP6 15
Страница 2: ......
Страница 43: ...DRYER OPTION 41 SSR UP6 15 UP6 20 UP6 25 UP6 30 Fig 1 Fig 2a Fig 2b Fig 2c...
Страница 48: ...PORO OPTION ELECTRO PNEUMATIC 46 SSR UP6 15 UP6 20 UP6 25 UP6 30...