110
RT-SVD03L-EN
Figure 68.
Setpoint input / voltmeter display
Heating Setpoint
Mode Input
Cooling Setpoint
Common
Zone Temperature
RTRM J6
DC
Volts
5.00
Table 81.
Setpoint input
Setpoint Inputs
Read voltage at either location
Cooling setpoint
RTRM J6-3
ZSM terminal 3
Heating setpoint
RTRM J6-5
ZSM terminal 5
Common
RTRM J6-2
ZSM terminal 2
Problems to Look for:
•
Mis-wire/short/open
•
Excessive resistance in circuit (corroded or loose
connection)
•
Setpoint lever inaccurate (should be +-2F of chart)
•
Induced voltage (high voltage wires in same
conduit)
Table 82.
Setpoint inputs
Temp °F
Resistance (K
ohms)
DC Volts
open
5.00 (open
circuit)
40
1.0841
2.601
41
1.0656
2.579
42
1.0472
2.557
43
1.0287
2.535
44
1.0102
2.513
45
0.9918
2.49
46
0.9733
2.466
47
0.9548
2.442
48
0.9363
2.418
49
0.9179
2.393
50
0.8994
2.368
51
0.8787
2.338
52
0.858
2.309
53
0.8373
2.278
54
0.8166
2.247
55
0.7958
2.216
56
0.7751
2.183
57
0.7544
2.15
58
0.7337
2.116
59
0.7142
2.083
60
0.6948
2.05
61
0.6753
2.015
62
0.6558
1.98
63
0.6363
1.944
64
0.6169
1.908
65
0.5974
1.87
66
0.5779
1.831
Table 82.
Setpoint inputs (continued)
Temp °F
Resistance (K
ohms)
DC Volts
67
0.5584
1.792
68
0.539
1.751
69
0.5195
1.709
70
0.5
1.667
71
0.4805
1.623
72
0.461
1.578
73
0.4416
1.532
74
0.4221
1.484
75
0.4026
1.435
76
0.3832
1.385
77
0.3637
1.333
78
0.3442
1.28
79
0.3247
1.226
80
0.3053
1.169
81
0.2858
1.111
82
0.2663
1.051
83
0.2468
0.99
84
0.2273
0.926
85
0.2079
0.86
86
0.1884
0.793
87
0.1689
0.723
88
0.1495
0.65
89
0.1301
0.575
90
0.1106
0.498
(shorted/no power)
0
Mode Input
Terminals to Read Voltage: RTRM J6-4, J6-2
Read DC voltage with Zone Sensor Module (ZSM)
attached. If voltage read does not appear to be correct,
read the resistance of the circuit, then the ZSM itself, to
see if a problem exists in the ZSM or the wiring. With
the ZSM not attached there should be 5.00 VDC at the
terminals listed above. To check for induced voltage,
read AC voltage to ground from each sensor wire.
Should be less than 2VAC.
Figure 69.
Mode input / Voltage reading
RTRM J6
HEATING SETPOINT
MODE INPUT
COOLING SETPOINT
COMMON
ZONE TEMPERATURE
Mode Input:
Mode Input
RTRM J6-4
ZSM terminal 4
Common
RTRM J6-2
ZSM terminal 2
Содержание ReliaTel
Страница 174: ...174 RT SVD03L EN N No ot te es s...
Страница 175: ...RT SVD03L EN 175 N No ot te es s...