
8.0 GENERAL INFORMATION
IRN37–160K–CC & IRN50–200H–CC & IRN75–160K–2S & IRN100–200H–2S
32
N90K
N110K
N125H
N150H
Water Cooling System
Cooling (clean) water flow m
3
/min (US
gallon/min) @ 10
_
C (50
_
F) / 32
_
C (90
_
F)
2.38 / 5.55
(9 / 21)
3.17 / 7.13
(12 / 27)
2.38 / 5.55
(9 / 21)
3.17 / 7.13
(12 / 27)
Maximum
∆
P in air ducts Pa (inch WG)
62 (0.25)
62 (0.25)
62 (0.25)
62 (0.25)
Compressed air outlet
∆
T
_
C (
_
F)
14 (25)
14 (25)
14 (25)
14 (25)
Main Power Circuit
***
Mean package full load current at 220V (A)**
184
222
–
–
Mean package full load current at 460V(A)**
–
–
167
197
Mean package full load current at 575V(A)**
–
–
134
158
Max fuse size @ 380V – 415V (A)
250
350
–
–
Max fuse size @ 440V – 480V (A)
–
–
200
250
Max fuse size @ 550V – 575V (A)
–
–
200
200
Fuse type
Fast acting class J, T or semiconductor type, current limiting
interrupt rating 200, 000 Amps
RMS SYM.
Heater Circuit
110V Single Phase Rating (A)
4
4
4
4
230V Single Phase Rating (A)
4
4
4
4
Fuse type
General purpose
* In accordance with PNEUROP PN8NTC2.3
** Tolerances in accordance with ISO 1217
*** Always apply local electrical codes for sizing cables and fusing. In the abscence of local codes the minimum
cable size should be calculated on basis of mean package full load current X1.25 (i.e. 25% margin)