SunLight Series UPS User Manual 

 

 
 
 
 

 
 
 
4.4.4   FAULT  Codes 

 
FAULT 1

  

“BYPASS FAILURE”

 An AC voltage exists at the output of the UPS, although the 

inverter  is not  in operation . In such  a case , disconnect all the critical  equipment from  
the UPS and turn it off and on again. If it doesn't  start operating , 

please call for 

service

 

FAULT 2

 

“INVERTER FAILURE”

 Inverter can  not  generate  AC  output. Turn-off the UPS  and  

then  turn  it  on  again .  If  it  doesn't  start , 

please call for service

 

FAULT 3

 

The  temperature  on  the  heatsink  inside  the  UPS cabinet  has  exceeded  90 °C   
three  times in the last  30 minutes. In such  a case , the UPS should  be turned-off and 
on again to resume  normal operation. 

 

FAULT 4 

"Output Failure" alarm has occurred 4 times in the last 10minutes. 

Please call for service

.

 

 

FAULT 5 

Inverter is not generating AC output  since the battery voltage is below  the  lower limit . 
Turn-off  the  UPS  and  on again. 

 

FAULT 6 

"Possible Battery Failure"   

Please call service

 for checking the batteries. 

 

FAULT 7

 

Rectifier fault.  

Please call service

 for checking the UPS. 

 

FAULT 8

   

Line voltage out of tolerance.  

 
 
 
 
 
 

4.5

  

Automatic  battery  test system (optional) :    

 

There are some conditions to make this test ( e. g availability of by-pass supply, line synchronization,  . a 
min. time requirement since the last line failure etc.). The first test is performed automatically, 8 hours 
later following the first turning on of the UPS. There is a  65 hours interval between two successive tests 
an each test lasts about 36 seconds. 
 
During  the  battery  test  operation,  the  inverter  power   will be supplied  from batteries .  At   the  end of  
this  test ,if the battery voltage is below a predetermined value, " BATTERY FAILURE / BATTERY LOW

  

 

Fault messages  appear on the LCD panel and the UPS  starts  operating in By-Pass mode. 
 
In this case you have to call your service. 
 
If the batteries are in normal conditions the system will start operating in normal mode after 36 sec. 
 
This test protects your operation against unexpected battery failures, and indicates you if there are any 
damaged batteries. It also discharges the batteries periodically, which is a good thing for extending 
battery life. 
  
 
 
 
 
 

Содержание SunLight -210

Страница 1: ...USER MANUAL UNINTERRUPTIBLE POWER SUPPLIES 3 Phase Input 1 Phase Output info rise TECHNOLOGIES SunLight 206 6 kVA SunLight 207 7 5 kVA SunLight 210 10 kVA SunLight 215 15 kVA SunLight 220 20 kVA SunL...

Страница 2: ...edure 11 4 2 2 Turn Off Procedure 11 4 3 When Utility Power Is Interrupted 11 4 4 Operator Control Panel 12 4 4 1 Push Buttons 12 4 4 2 First Message Line Of The LCD 12 4 4 3 Second M L ALARMS Of The...

Страница 3: ...ified service personnel The output may be energized when the unit is not connected to a mains supply Risk of electric shock hazardous live parts inside this unit are energized from the battery supply...

Страница 4: ...and maintenance by pass LCD Liquid Crystal Display display Alarm history Memory for max 64 alarms Automatic battery testing optional High quality maintenance free lead acid type batteries High nonline...

Страница 5: ...ransfer Switch static by pass Static transfer switch is an electronically controlled switching circuit checked by main controller board In case of inverter overload or any other faults STS transfers t...

Страница 6: ...Frequency 50 Hz Line Synchronized 1 Output Frequency Tolerance Free Running 0 2 Efficiency 100 Load 85 87 Crest Factor 3 1 Overload capacity 100 125 Load 2 5 min 125 150 Load 10 sec 150 instant by pa...

Страница 7: ...ections Battery Fuse AC Output 220V AC 50Hz 10A max DB9 Port PK1 On Off Switch Main Switch Figure 2 2 1 6 7 5 10 kVA Rear view Figure 2 2 2 Front views Main Switch PK1 On Off Switch UPS Electrical Con...

Страница 8: ...ocation Selection The UPS is designed to be installed in a protected environment The following conditions should be prohibited 1 Blocking the airflow intake and outlet It is recommended to retain 10 c...

Страница 9: ...ioned and secured connect the power cables as described in the following section It is recommended that the UPS should be connected to the line voltage protected by a circuit breaker 1 Before connecti...

Страница 10: ...give the inverter power to the output 3 Disconnect the input power The LINE FAILURE indicator will be on and audible alarm will sound intermittently Now the output receptacles are supplied from the ba...

Страница 11: ...ion as well 4 Position 3 When PK1 is turned to this position the Load is supplied again by line voltage at during start up and after a short delay inverter starts running this can be seen by observing...

Страница 12: ...wer cords into outlets 4 2 15 20 30 kVA 4 2 1 Turn On Procedure 1 Turn On Main Switch PK1 on the front panel from position 0 to 3 step by step as in the instructions given in chapter 3 4 2 2 Turn on t...

Страница 13: ...onal sections LED indications and control and display As can be seen the upper section consists of leds which indicate the operation mode This panel shows the systems operation such as input and outpu...

Страница 14: ...LINE MODE UPS operating mode LINE FAILURE You have no AC input at the UPS input BATTERY TEST Performing battery test BAT AUTONOMY END Battery autonomy has finished BATTERY LOW UPS battery voltage is b...

Страница 15: ...g the batteries FAULT 7 Rectifier fault Please call service for checking the UPS FAULT 8 Line voltage out of tolerance 4 5 Automatic battery test system optional There are some conditions to make this...

Страница 16: ...oftware the UPS and the computer system communicate so that the computer system is warned of impending UPS shutdown Software RUPS RUPSII UPSILON SNMP devices is available for most operating systems an...

Страница 17: ...d to your network through SNMPVIEW Software supplied with the module or it is possible to monitor the UPS through an Internet Browser It is possible to shutdown the servers or users with Client mate S...

Страница 18: ...PS system from several different locations at the same time 5 5 UPS Port Sharer Multiple server shut down unit Using one of this units you can automatic shut down of 4 8 servers or PC where without LA...

Страница 19: ...18 SunLight Series UPS User Manual...

Страница 20: ...19 SunLight Series UPS User Manual Connection Diagram Of The RMP COM1...

Страница 21: ...persistent failure or problem properly turn off the unit first Then review the following check list Be prepared to answer the questions before calling the service 1 Did you follow the operation proced...

Страница 22: ...not apply if the product has been subjected to physical abuse improper installation unauthorized service or modification 2 The sole responsibility of corporation under this warranty shall be limited...

Отзывы: