Type 0/1
24-230V AC
L
N
CIB+
CIB -
thermosensor
1.
2.
3.
4073-02-001 Rev
.0
H
eating
1. Set contents
- PS-30/24
power supply
- BPS2-01M
bus/supply voltage separator
- CU2-01M
central unit
- SA2-02B
switching actuator
- Alpha AA 230V NO
thermo valve
- IART2-01
analog thermo-controller
2. First start of the set in box
Set is already „preprogrammed“ by the manufacturer and ready for using.
1. Check whether all conductors are connected to terminals (no one is loose or fell out).
2. Connect the mains plug into the
AC 230 V
socket.
3. The
CU2-01M
starts the starting sequence. After the sequence is completed, the
CU2-01M
switches to the
RUN
operation mode whereas this mode is
signaled on the segmented display as
G
.
4. Set started this way is ready for use according to functions already pre-programmed in
CU2-01M
.
IART2-01
analog thermo controller is programmed as follows:
Thermo sensor TC / TZ
Thermo-valve
1. Rotary element is designated for correcting requested temperature -3°C/+3°C
2. Button 0/1 is designated for switching the heating circuit off - green LED signalizes that the heating circuit is switched on;
when orange, the heating circuit is active (heats up).
3. Button hand/clock is designed for switching the heating modes - first press switches to presentation (signalized by green LED),
the second press switches to the forced comfort (signalized by red LED), and the third press switches back into controlled time
schedule program.
A well-trained technician should always install the set. This simplified use instructions describe the set basic mounting; mounting details for single sections of the set are given in related manuals.
The complete instructions on system parametrization are available on the CD enclosed.
USE INSTRUCTIONS
4. Set installation in designated location
1. Install the set in designated place.
2. Connect
AC 230V
mains supply voltage cable to
PS-30-24
power supply terminals
N
and
L
.
3. Then continue in terms of point 2 - First start of the set in box.
3. Prior installation in designated location
1. Make sure all installation bus conductors are correctly connected into the
CIB+
and
CIB-
terminals.
2. Make sure that BPS2-01M bus/supply voltage separator is correctly connected into
the
PS-30-24
power supply.
5. Inels designer & manager (IDM) programming environment installation
IDM is used for activation and parametrization of the system, eventually for creating the basic visualization of
INELS® intelligent electro-installation application.
1. Start
IDM.exe file
, which is located on attached CD.
2. After starting, window
Installation guide language selection
appears.
3. Select language and confirm your selection with
OK
button; then appears window IDM installation guide
4. Follow the instructions of
IDM product guide
.
5. After the IDM installation is done,
history.txt
file opens, that contains new IDM features description,
or description of corrected errors; at the same time introductory login window appears.