A-7
Appendices
Sinking Output
Application Example
Active LOW Output will be opem a relay, useful for Fault.
‘[VARIABLES]
S1=19,0,0 ‘Configure IO 1 as a Fault output.
Internal
pull-up
voltage
24.9k ohms
Sinking Output Equivalent Circuit
always
off
switched
IOx
GND
MForce Plus
Sinking Output
*External Resistor may be needed to
limit output sink current to 600mA
up to
24 V
+
Figure B.3: Sinking Output to Relay
NOTE: On the
Standard MForce
Plus, when configured
as outputs, the I/O
set is sinking ONLY! The Plus2
Models add the functionality of
I/O Power, which enables the
user to use all the outputs, both
Standard and Enhanced, as
Sinking or Sourcing.
IO1
IO2
IO3
IO4
GND
S1 = 16,0
S2 = 4,1,1
S3 = 2,0,0
S4 = 3,0,0
GO
+ LIMIT
- LIMIT
LOAD
PNP
up to
+24 V
+
S Parameter Settings
Mixed Input/Output Example
Figure B.4: Mixed Output Example- Standard I/O Set