background image

 

                              Instruction  Manual 

 

            IMO Jaguar VXR 

 

PG Interface Cards “VXR-EFC” & 

“VXR-EFC-5V”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thank you for purchasing our EFC interface card. 

• Read through this instruction manual and be familiar with the option card before 

proceeding with installation, connections (wiring), operation, or maintenance and 
inspection. 

•  Deliver this manual to the end user of this product. Keep this manual in a safe place until 

this product is discarded. 

• Specifications of this option card are subject to change without prior notice for 

improvement.

 

 
 

 

IMO Precision Controls Ltd. 

 

Содержание VXR-EFC

Страница 1: ...familiar with the option card before proceeding with installation connections wiring operation or maintenance and inspection Deliver this manual to the end user of this product Keep this manual in a...

Страница 2: ...produced or copied without prior written permission from IMO Precision Controls Ltd All products and company names mentioned in this manual are trademarks or registered trademarks of their respective...

Страница 3: ...ecautions Read this manual thoroughly before proceeding with installation connections wiring operation or maintenance and inspection Ensure you have sound knowledge of the device and familiarize yours...

Страница 4: ...nt appropriate measure to prevent the nearby sensors and devices from malfunctioning due to such noise Otherwise an accident could occur Operation Be sure to install the terminal cover before turning...

Страница 5: ...Icons The following icons are used throughout this manual This icon indicates information which if not heeded can result in the inverter not operating to full efficiency as well as information concer...

Страница 6: ...NPUT 5 1 5 1 Specifications 5 1 5 2 Terminal Functions 5 1 5 3 Function Code List 5 1 5 4 Function Code Details 5 2 5 5 Description of the Control 5 3 5 5 1 Input pulse command polarity 5 3 5 5 2 Bloc...

Страница 7: ...FC interface card is applicable Table 1 1 Applicable ROM Version Series Type of inverter Applicable motor rating ROM version Jaguar VXR VXR E1 All capacities 0700 or later Checking the ROM version Use...

Страница 8: ...r details on how to remove the terminal cover refer to the Jaguar VXR Instruction Manual Chapter 2 Section 2 3 Wiring 2 If the interface PCB is installed on the inverter push the hooks provided on bot...

Страница 9: ...ions of the EFC 1 3 2 Mounting the EFC to the motor The counterclockwise rotation when viewed from the motor output shaft is regarded as forward rotation see Figure 1 4 During rotation in the forward...

Страница 10: ...erring to the connection diagrams given in Figures 2 1 to 2 3 1 Turn the inverter s power OFF 2 Use a shielded wire for wiring between the EFC and the EFC interface card 3 To prevent malfunction due t...

Страница 11: ...EFC common Common terminal for power supply and EFC input XA A phase pulse input X Pulse input terminal for commands To supply speed commands from the pulse train generator or EFC connect an open coll...

Страница 12: ...M YA YB YZ PO PI CM Screw size M2 Tightening torque 0 22 to 0 25 N m Figure 1 8 Option Terminals Terminal PLC on the EFC interface card cannot supply power to external equipment Use the terminal only...

Страница 13: ...pulse rate input Figure 2 1 Connection Diagrams for Frequency Control with Pulse Rate Input Note 1 For details about applicable PG specifications refer to Table 1 2 in Chapter 1 Section 1 3 1 PG speci...

Страница 14: ...ols Figure 2 2 shows connection diagram examples for speed and positioning controls Figure 2 2 Connection Diagrams for Speed Control with PG and Positioning Control When using inverter internal power...

Страница 15: ...the Electromagnetic Compatibility EMC Directive connect the shielded cable to the ground of the inverter as shown below Figure 2 3 Connection Diagrams for Compliance with EMC Directive When using inve...

Страница 16: ...urthermore after powering the inverter ON but before starting inverter operation check the followings Check the wiring surely before running the inverter Incorrect wiring causes the inverter or other...

Страница 17: ...requency Control with Pulse Rate Input This control specifies a frequency command with pulse trains For details refer to Chapter 5 It can be used together with speed control with EFC at the same time...

Страница 18: ...inal Receives power for the EFC from an external source PO Power output terminal Outputs power to the EFC CM Common terminal Common terminal for the EFC power XA Command input terminal for A phase pul...

Страница 19: ...e constant can stabilize the speed command in low pulse rate o07 o08 Command Pulse train input Pulse count factor 1 Command Pulse train input Pulse count factor 2 For the pulse input command these fun...

Страница 20: ...ity of the B Phase Pulse Input B phase input A phase input Polarity Figure 5 3 Polarity of the Run Forward Reverse Pulse Input Table 5 5 Relationship between Polarity of the Pulse Input FWD REV Comman...

Страница 21: ...rom an external source PO Power output terminal Outputs power to the EFC CM Common terminal Common terminal for the EFC power YA Feedback input terminal for A phase pulse train Receives an A phase fee...

Страница 22: ...Input Encoder pulse resolution 20 to 3600 P R 1024 N o10 Filter time constant 0 000 to 5 000 s 0 005 Y o11 Pulse count factor 1 1 to 9999 1 N o12 Pulse count factor 2 1 to 9999 1 N o13 Speed Control O...

Страница 23: ...not exceed 35 00 in the ordinary system Modifying F03 A01 data requires readjustment of o02 and o03 data o04 Speed Control Filter time constant This function code specifies a time constant determinin...

Страница 24: ...Transmission ratio c d No of teeth b No of teeth a No of teeth a Radius c Radius Inverter FRN E1S PG U V W Figure 6 1 Speed Control Model Using a EFC Motor shaft speed Pulse count factor 2 o12 Encode...

Страница 25: ...FC from an external source PO Power output terminal Outputs power to the EFC CM Common terminal Common terminal for the EFC power XA Command input terminal for A phase pulse train Receives an A phase...

Страница 26: ...999 to 999 p 0 Y J77 Preset point lower digits P 0 to 9999 1 p 0 Y J78 Creep speed switch point upper digits 0 to 999 p 0 Y J79 Creep speed switch point lower digits 0 to 9999 p 0 Y J80 Creep speed 0...

Страница 27: ...ER J83 CP J85 Run command OFF Time ET J84 Timer output TO OFF Positioning completed PSET OFF Note The current position must be within E ER point after the time ET has elapsed Decl time F08 E11 Decl ti...

Страница 28: ...the waiting time from when a run command comes ON with the S R terminal command being ON until the inverter starts running the motor This covers the delay of brake OFF If the output frequency has not...

Страница 29: ...serial pulse input shares an input terminal with other functional pulse inputs when the positioning control is concurrently enabled with frequency control with pulse rate input and or speed control wi...

Страница 30: ...S R being ON or A Z point correction is performed 7 5 Function Code Details o01 Command Feedback Input Input mode This function code switches the feedback pulse input mode with the data in the tens p...

Страница 31: ...amming mode on the standard keypad Running status in Running mode on the multi function keypad Remarks Upper 4 digits Lower 4 digits 9 999 999 999 9999 Maximum display value 19 999 1 9999 The lower di...

Страница 32: ...trol completed PSET 8 Status where the positioning control is completed and the inverter is issuing PSET Stop position override alarm OT 9 Status where the inverter is issuing a stop position override...

Страница 33: ...trol Positioning control o01 Symbol X in the above table stands for EFC terminals XA XB and XZ Specify their input modes with the data in the ones place of function code o01 Symbol Y stands for EFC te...

Страница 34: ...t t t 100 ms min Pulse train input Pulse train input 100 ms min For the pulse train input control restart pulse train input within 100 ms 100 ms max Pulse train input holding period Holds the pulse co...

Страница 35: ...which may cause the motor to rotate Injury may occur 8 1 Overspeed Alarm os Table 8 2 Overspeed Alarm Specifications Alarm code Descriptions os The inverter issues this alarm when the detected speed e...

Страница 36: ...Alarm EFC ERR output 0 Continue to run Any status of to in Figure 8 1 is kept exceeding the timer setting specified by o18 None Active 1 Stop running Alarm mode 1 ere Inactive 2 Stop running Alarm mod...

Страница 37: ...utput frequency and feedback position pulse when the inverter output frequency has exceeded the hysteresis width specified by E30 Frequency Arrival for 2 5 Hz min during the period longer than the tim...

Страница 38: ...ption card is applicable with following inverter ROM version Product Version of VXR EFC Applicable inverter ROM Version 5_14 None 0700 or later A 0800 or later To check the product version of VXR EFC...

Страница 39: ...2 The external power supply should satisfy the voltage specifications of the PG 4 Terminal Specifications Table 3 1 Terminal Specifications Terminal symbol Name Functions PI External power supply inp...

Страница 40: ...o07 Pulse count factor 1 1 to 9999 1 N o12 o08 Pulse count factor 2 1 to 9999 1 N Chapter 7 POSITIONING CONTROL P 7 9 Table 4 3 lists input assignments for terminals XA XB and XZ when the positioning...

Страница 41: ...n in handling setting up and operating of the EFC interface card Please feel free to send your comments regarding any errors or omissions you may have found or any suggestions you may have for general...

Страница 42: ...IMO Precision Controls Ltd Unit 15 1000 North Circular Road Staples Corner London NW2 7JP England Phone 44 208 452 6444 Fax 44 208 450 2274 URL http www imopconline com 2006 05 19 S Mc...

Отзывы: