Given the OK for selection, pass to the second
level where it is possible to set the value of the
parameter selected. The value is indicated by the
slow flashing of one of the LEDs between 1 and
8. The value is selected by rotating the heating
temperature selector switch (11).
Once the value of the parameter to be modified
has been selected, confirm the selection by
momentarily turning the main selector switch
onto Reset momentarily until the LED relative to
the parameter switches-off, then release.
Programming mode is exited if no operation is
carried out for 30 seconds or if the main selector
switch is positioned at OFF from the “parameter
setting” level.
For association of the LED to the relative value,
see the following tables:
Heating power.
The boiler is produced and
calibrated in the heating phase at nominal power.
It also has electronic modulation that adapts the
boiler potentiality to the effective heating demand
of the house. Then the boiler works normally in a
variable gas pressure field between the minimum
heating power and the maximum heating power
depending on the plants heating.
N.B:
the selection of the “Minimum heating power”
and “Maximum heating power” parameters, in the
presence of a heating demand , allows switch-on
of the boiler and power supply of the modulator
with current equal to the value of the respective
selected parameter.
Minimum heating power
(continuous variation)
Flashing
LED
(slow)
0% Imax. (Standard setting)
LED 1
7% Imax.
LED 2
14% Imax.
LED 3
21% Imax.
LED 4
28% Imax.
LED 5
35% Imax.
LED 6
42% Imax.
LED 7
63% Imax.
LED 8
Maximum heating power
(continuous variation)
Flashing
LED
(slow)
0% Imax.
LED 1
11% Imax.
LED 2
22% Imax.
LED 3
33% Imax.
LED 4
44% Imax.
LED 5
55% Imax.
LED 6
88% Imax.
LED 7
100% Imax. (Standard setting)
LED 8
Permanent reduction of the timer.
The boiler
has an electronic timing device that prevents the
burner from igniting too often in the heating
phase. The boiler has a standard supply of a timer
adjusted at 180 seconds.
Heating switch-on timer
(continuous variation)
Flashing
LED
(slow)
30 seconds
LED 1
55 seconds
LED 2
80 seconds
LED 3
105 seconds
LED 4
130 seconds
LED 5
155 seconds
LED 6
180 seconds (Standard setting)
LED 7
255 seconds
LED 8
Heating ramp timing.
The boiler distributes he
maximum power set in the previous parameter.
The boiler performs an ignition ramp of about
650 seconds to arrive from minimum power to
nominal heating power.
Heating ramp timer
(continuous variation)
Flashing
LED
(slow)
65 seconds
LED 1
130 seconds
LED 2
195 seconds
LED 3
390 seconds
LED 4
455 seconds
LED 5
520 seconds
LED 6
585 seconds
LED 7
650 seconds (Standard setting)
LED 8
Heating switch-on delay request from Room
thermostat and Remote Friend Control
V2
.
The
boiler is set to switch-on immediately after a
request. In the case of particular plants (e.g. area
plants with motorised thermostatic valves etc.) it
could be necessary to delay switch-on.
Heating switch-on delay re-
quest from Room thermostat
and Remote Friend Control
V2
(continuous variation)
Flashing
LED
(slow)
0 seconds (Standard setting)
LED 1
54 seconds
LED 2
131 seconds
LED 3
180 seconds
LED 4
206 seconds
LED 5
355 seconds
LED 6
400 seconds
LED 7
510 seconds
LED 8
Domestic water thermostat/Boiler hysteresis.
With the setting of hysteresis 1 the boiler switches
on with a boiling device temperature equal to a
set point at -3°C. With the setting of hysteresis
2 l the boiler switches on with a boiling device
temperature equal to a set point at -10°C.
Domestic water thermostat/
Boiler hysteresis
Flashing
LED
(slow)
Hysteresis 1 (Standard setting)
LED 1
Hysteresis 2
LED 8
Circulating pump function.
two circulating
pump operational modes can be selected in
heating phase.
In “intermittent” mode it is activated from the
environmental thermostat or from the remote
control, in “continual” mode the circulation pump
functions constantly when the main selector switch
(12) is on heating mode.
Circulating pump function
Flashing
LED
(slow)
Intermittent (Standard setting)
LED 1
Continuous
LED 8
Town Gas G110 – Industrial gas.
The setting of
this function is used to ad just the boiler in order
to function with gases from the first family.
Town Gas G110 - Industrial
gas (first family gas)
Flashing
LED
(slow)
Off (Standard setting)
LED 1
On
LED 8
Boiler mode.
Establishes if the boiler functions
in instantaneous mode or with boiler (standard
supply).
Boiler mode
Flashing
LED
(slow)
Instantaneous (Cannot be
used)
LED 1
With boiler (Standard setting)
LED 8
3.8 AUTOMATIC SLOW IGNITION
FUNCTION WITH TIMED RAMP
DELIVERY.
In the switch-on phase the electronic card carries
out an increasing gas delivery ramp (with pressure
values that depend on the type of gas selected) of
preset duration. This avoids every boiler lighting
phase calibration or preparation operation in any
conditions of use.
3.9 CHIMNEY SWEEP “FUNCTION”.
When activated, this function forces the boiler at
max. output for 15 minutes.
In this mode all the adjustments are cut out and
only the temperature safety thermostat and the
limit thermostat remain active. To activate the
“Chimney-Sweep” function, press the Reset key
for 8 to 15 seconds in absence of domestic water
and heating requests. Its activation is indicated
by the simultaneous flashing of LEDS (2) and
(3). This function allows the technician to check
the combustion parameters. After the checks
deactivate the function, switching the boiler off
and then on again.