Given the OK for selection, pass to the second 

level where it is possible to set the value of the 

parameter selected. The value is indicated by the 

slow flashing of one of the LEDs between 1 and 

8. The value is selected by rotating the heating 

temperature selector switch (11).

Once the value of the parameter to be modified 

has been selected, confirm the selection by 

momentarily turning the main selector switch 

onto Reset momentarily until the LED relative to 

the parameter switches-off, then release.

Programming mode is exited if no operation is 

carried out for 30 seconds or if the main selector 

switch is positioned at OFF from the “parameter 

setting” level.

For association of the LED to the relative value, 

see the following tables:

Heating power.

 The boiler is produced and 

calibrated in the heating phase at nominal power. 

It also has electronic modulation that adapts the 

boiler potentiality to the effective heating demand 

of the house. Then the boiler works normally in a 

variable gas pressure field between the minimum 

heating power and the maximum heating power 

depending on the plants heating.

N.B:

 the selection of the “Minimum heating power” 

and “Maximum heating power” parameters, in the 

presence of a heating demand , allows switch-on 

of the boiler and power supply of the modulator 

with current equal to the value of the respective 

selected parameter.

Minimum heating power 

(continuous variation)

Flashing 

LED 

(slow)

0% Imax. (Standard setting)

LED 1

7% Imax.

LED 2

14% Imax.

LED 3

21% Imax.

LED 4

28% Imax.

LED 5

35% Imax.

LED 6

42% Imax.

LED 7

63% Imax.

LED 8

Maximum heating power 

(continuous variation)

Flashing 

LED 

(slow)

0% Imax.

LED 1

11% Imax.

LED 2

22% Imax.

LED 3

33% Imax.

LED 4

44% Imax.

LED 5

55% Imax.

LED 6

88% Imax.

LED 7

100% Imax. (Standard setting)

LED 8

Permanent reduction of the timer.

 The boiler 

has an electronic timing device that prevents the 

burner from igniting too often in the heating 

phase. The boiler has a standard supply of a timer 

adjusted at 180 seconds.

Heating switch-on timer

(continuous variation)

Flashing 

LED 

(slow)

30 seconds

LED 1

55 seconds

LED 2

80 seconds

LED 3

105 seconds

LED 4

130 seconds

LED 5

155 seconds

LED 6

180 seconds (Standard setting)

LED 7

255 seconds

LED 8

Heating ramp timing.

 The boiler distributes he 

maximum power set in the previous parameter. 

The boiler performs an ignition ramp of about 

650 seconds to arrive from minimum power to 

nominal heating power.

Heating ramp timer

(continuous variation)

Flashing 

LED 

(slow)

65 seconds

LED 1

130 seconds

LED 2

195 seconds

LED 3

390 seconds

LED 4

455 seconds

LED 5

520 seconds

LED 6

585 seconds

LED 7

650 seconds (Standard setting)

LED 8

Heating switch-on delay request from Room 

thermostat and Remote Friend Control

V2

.

 The 

boiler is set to switch-on immediately after a 

request. In the case of particular plants (e.g. area 

plants with motorised thermostatic valves etc.) it 

could be necessary to delay switch-on.

Heating switch-on delay re-

quest from Room thermostat 

and Remote Friend Control

V2

 

(continuous variation)

Flashing 

LED 

(slow)

0 seconds (Standard setting)

LED 1

54 seconds

LED 2

131 seconds

LED 3

180 seconds

LED 4

206 seconds

LED 5

355 seconds

LED 6

400 seconds

LED 7

510 seconds

LED 8

Domestic water thermostat/Boiler hysteresis.

 

With the setting of hysteresis 1 the boiler switches 

on with a boiling device temperature equal to a 

set point at -3°C. With the setting of hysteresis 

2 l the boiler switches on with a boiling device 

temperature equal to a set point at -10°C.

Domestic water thermostat/

Boiler hysteresis 

Flashing 

LED 

(slow)

Hysteresis 1 (Standard setting)

LED 1

Hysteresis 2

LED 8

Circulating pump function.

 two circulating 

pump operational modes can be selected in 

heating phase.

In “intermittent” mode it is activated from the 

environmental thermostat  or from the remote 

control, in “continual” mode the circulation pump 

functions constantly when the main selector switch 

(12) is on heating mode.

Circulating pump function

Flashing 

LED 

(slow)

Intermittent (Standard setting)

LED 1

Continuous

LED 8

Town Gas G110 – Industrial gas.

 The setting of 

this function is used to ad just the boiler in order 

to function with gases from the first family.

Town Gas G110 - Industrial 

gas (first family gas)

Flashing 

LED 

(slow)

Off (Standard setting)

LED 1

On

LED 8

Boiler mode.

 Establishes if the boiler functions 

in instantaneous mode or with boiler (standard 

supply).

Boiler mode

Flashing 

LED 

(slow)

Instantaneous (Cannot be 

used)

LED 1

With boiler (Standard setting)

LED 8

3.8  AUTOMATIC SLOW IGNITION 

FUNCTION WITH TIMED RAMP 

DELIVERY.

In the switch-on phase the electronic card carries 

out an increasing gas delivery ramp (with pressure 

values that depend on the type of gas selected) of 

preset duration. This avoids every boiler lighting 

phase calibration or preparation operation in any 

conditions of use.

3.9  CHIMNEY SWEEP “FUNCTION”.

When activated, this function forces the boiler at 

max. output for 15 minutes.

In this mode all the adjustments are cut out and 

only the temperature safety thermostat and the 

limit thermostat remain active. To activate the 

“Chimney-Sweep” function, press the Reset key 

for 8 to 15 seconds in absence of domestic water 

and heating requests. Its activation is indicated 

by the simultaneous flashing of LEDS (2) and 

(3).  This function allows the technician to check 

the combustion parameters. After the checks 

deactivate the function, switching the boiler off 

and then on again.

Содержание ZEUS 24 Superior

Страница 1: ...ZEUS 24 28 kW IE Instruction booklet and warning 1 038761ENG...

Страница 2: ...ct correctly Maintenance must be carried out by skilled technical staff The Immergas Authorised After sales Service represents a guarantee of qualifications and professionalism The appliance must only...

Страница 3: ...sure sufficient space for normal servicing therefore it is advisable to leave a clearance of at least 3 cm between the boiler casing and the vertical sides of the cabinet Leave adequate space above th...

Страница 4: ...ranty before making the boiler connections carefully clean the heating system pipes radiators etc with special pickling or de scaling products to remove any deposits that could compromise correct boil...

Страница 5: ...t function disabled i e it must be set to On Off mode The CRD cannot be used for plants divided into zones Electrical connection of the Remote Friend ControlV2 or chronothermostat On Off Optional The...

Страница 6: ...s Cut the seal in the relative groove at the desired diameter 80 run it along the bend and fix it using the sheet steel plate Insert the exhaust pipe with the male end smooth into the female side of t...

Страница 7: ...the boiler the fumes separator positioned on the air fumes extraction well must be adjusted Fig 1 12 Adjustment is carried out by loosening the front retainer screw and moving the indicator to the cor...

Страница 8: ...Exhaust m 2 0 Terminal complete with concentric hori zontal intake exhaust 80 125 Intake and Exhaust 33 m 2 0 m 5 5 Intake m 14 3 Exhaust m 11 0 Terminal complete with concentric horizontal intake exh...

Страница 9: ...t kits 80 125 Kit assembly Fig 1 18 install the bend with flange 2 on the central hole of theboiler inserting the seal 1 and tighten using the screws in the kit Fit the male end smooth of the adapter...

Страница 10: ...flues and air intake pipes according to the diagram shown in the figure Fig 1 22 Fumes are expelled from duct S Air is taken in through duct A for combustion Intake duct A can be installed either on...

Страница 11: ...red use 80 pipes with insulation see insulated separator kit 80 80 chapter Insulated separator kit 80 80 Kit assembly Fig 1 26 install flange 4 on the central hole of the boiler fitting seal 1 and tig...

Страница 12: ...kit optional air intake takes place directly from the environment in which the boiler is installed and the fumes are expelled in an individual flue or directly to the outside The boiler in this config...

Страница 13: ...tail to ensure maximum reliability Thelowerinspectionflangeensurespracticalcontrol oftheboilerandthecoiledheatexchangerandeasy internal cleaning The domestic water attachments are found on the flange...

Страница 14: ...irculation pump 9 Gas valve 10 3 way valve motorised 11 System filler tap 12 System expansion tank 13 Domestic hot water probe 1 17 ZEUS 24 28 KW BOILER COMPONENTS 14 Stainless Steel Boiler 15 3 bar s...

Страница 15: ...devices for flue extraction and relative accessories switch off the appliance and on completion of operations ensure that a qualified technician checks efficiency of the ducting or other devices Neve...

Страница 16: ...it and that the system is free of air deaerated circulating pump blocked free the circulating pump If this phenomenon occurs frequently contact a qualified technician for assistance e g Immergas Techn...

Страница 17: ...elow 4 C and stops once it exceeds 42 C The antifreeze function is guaranteed if the boiler is fully operative and not in block status and is electrically powered To avoid keeping the system switched...

Страница 18: ...nd or exhaust terminals are not blocked check activation of the no air safety pressure switch ensure activation of all adjustment devices seal the gas flow rate regulation devices if settings are modi...

Страница 19: ...ESHOOTING N B Maintenance must be carried out by a qualified technician e g Immergas Technical Assistance Service Smell of gas Caused by leakage from gas circuit pipelines Check sealing efficiency of...

Страница 20: ...f gas by turning in a clockwise direction the heating potential increases and in an anti clockwise direction it decreases Adjust the boiler minimum thermal input Fig 3 3 N B only proceed after having...

Страница 21: ...seconds LED 7 650 seconds Standard setting LED 8 Heating switch on delay request from Room thermostat and Remote Friend ControlV2 The boiler is set to switch on immediately after a request In the cas...

Страница 22: ...n the casing Unhook the lower part of the casing as described in the figure Pull the casing 4 forwards and up at the same time see figure to detachit from the upper hooks 3 15 YEARLY APPLIANCE CHECK A...

Страница 23: ...erted in the test pressure outlet of the modulating adjustable gas valve and on the sealed chamber positive pressure test outlet The power data given in the table is obtained with intake exhaust pipe...

Страница 24: ...ppm 123 71 161 84 165 80 Flue temperature at nominal heat output C 108 109 107 Flue temperature at minimum heat output C 87 91 91 Zeus 28 kW Gas nozzle diameter mm 1 35 0 79 0 79 Supply pressure mbar...

Страница 25: ...loss at case with burner On Off 0 40 0 89 0 60 0 62 Heat loss at flue with burner On Off 5 50 0 03 5 50 0 01 Heating circuit max working pressure bar 3 3 Heating circuit max working temperature C 90...

Страница 26: ......

Страница 27: ......

Страница 28: ...mmergas com Immergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 038761ENG rev ST 002107 000 10...

Отзывы: