Instructions and 

recommendations

Installer

User

Maintenance technician

IE

SOLAR SYSTEM WITH  

NATURAL CIRCULATION  

NATURAL SOL 150 - 200 V2

*1.042024ENG*

STD.005441/000

Содержание NATURAL SOL 150 V2

Страница 1: ...Instructions and recommendations Installer User Maintenance technician IE SOLAR SYSTEM WITH NATURAL CIRCULATION NATURAL SOL 150 200 V2 1 042024ENG STD 005441 000...

Страница 2: ...STD 005441 000...

Страница 3: ...in force and the principles of good practice In compliance with the legislation in force the systems must be designed by qualified professionals within the dimensional limits established by the Law I...

Страница 4: ...r collectors 9 1 6 Kit composition 9 1 7 Installation on sloping roof 11 1 8 Free installation 21 1 9 System connection 31 1 10 By pass kit optional 31 1 11 Electrical resistance 32 1 12 Solar system...

Страница 5: ...5 1 1 INSTALLER USER MAINTENANCE TECHNICIAN 1 INSTALLATION 1 1 PACKAGING It must be stored in a dry place protected from humidity in its original closed packaging STD 005441 000...

Страница 6: ...2 2705 580 A 580 15 30 1 3 0 6 4 8 2000 2088 37 2002 1192 150 L mm 200 L mm A 1058 1290 INSTALLER USER MAINTENANCE TECHNICIAN 1 2 OVERALL DIMENSIONS FREE INSTALLATION INSTALLATION ON SLOPING ROOF STD...

Страница 7: ...7 1 3 250 870 134 620 250 1970 100 100 134 1870 INSTALLER USER MAINTENANCE TECHNICIAN 1 3 CLEARANCES WITH BRACKETS FOR SLATES TILES OPTIONAL STD 005441 000...

Страница 8: ...297 360 1 4 TECHNICAL DATA Forecastofannualperformanceaccordingtothe EN12976 2StandardforEuropeaninstallations 150 L Storage tank performance Performance indicators just for solar and solar pre heati...

Страница 9: ...ndards before starting the system the solar collector must be covered to protect the absorber from overheating and the operator from any burns The system must only be filled after all the hydraulic co...

Страница 10: ...s t u v w x y z aa ab ad ae ac af 1 5 INSTALLER USER MAINTENANCE TECHNICIAN Installation drawings key a Unmistakeable component identification 1 Sequential identification of the operation to perform...

Страница 11: ...USER MAINTENANCE TECHNICIAN 1 7 INSTALLATION ON SLOPING ROOF N B during installation of the components represented below pay full attention to the holes used and their correct recipro cal positioning...

Страница 12: ...4 c d c d ac z aa aa z ac aa z aa z 3 6 5 6 5 ab s ac s i aa z h s ac s i z aa ab h aa z z aa z aa z aa INSTALLER USER MAINTENANCE TECHNICIAN Assembletheupperframefollowingoperations 3 to 10 STD 0054...

Страница 13: ...13 1 8 e 9 10 7 8 10 9 e z ab aa z aa ab aa z ab aa z ab INSTALLER USER MAINTENANCE TECHNICIAN N B assemble the e bars without fully tight ening the nuts aa STD 005441 000...

Страница 14: ...ab z aa f INSTALLER USER MAINTENANCE TECHNICIAN Install the 4 frame fixing laminate f using the holes present on the bars b selecting from those suitable in a way to centre the laminates with the pit...

Страница 15: ...12 13 f ad ae ad ae 1 10 INSTALLER USER MAINTENANCE TECHNICIAN N B fix the laminates f to the roof using the mostsuitabledeviceforthetypeofroofon which the installation is to be carried out STD 005441...

Страница 16: ...N B if the installer does not deem it appropri ate to apply the complete weight of the structure on the tiles it is possible to fix the same using the brackets for slates tiles g supplied as an optio...

Страница 17: ...11 15 11 15 11 15 11 15 11 15 ab z aa aa z ab ab z aa ab z aa 1 13 INSTALLER USER MAINTENANCE TECHNICIAN Join the lower frame fixed to the roof to the upper frame as represented below sequences 14 an...

Страница 18: ...HNICIAN After positioning the manifold j as shown in the figure slide the upper mount bar e down until it touches the manifold itself At the end tighten the nuts used to assemble both bars e N B do no...

Страница 19: ...ENANCE TECHNICIAN Position the storage tank Cylinder on the two calenderedbrackets i selectingthemostsuitable hole on the basis of the inclination of the slope At the end of installation the upper fit...

Страница 20: ...11 22 t 11 23 11 24 11 24 11 25 11 26 v u u p w 1 17 1 18 INSTALLER USER MAINTENANCE TECHNICIAN N B the safety valves v and w must be mounted in a way that any emission of steam caused by overheating...

Страница 21: ...z z aa z aa z aa INSTALLER USER MAINTENANCE TECHNICIAN 1 8 FREE INSTALLATION N B during installation of the components represented below pay maximum at tention to the holes used and the correct recipr...

Страница 22: ...22 1 20 e 5 6 4 4 6 5 e z ab aa z aa ab aa z ab aa z ab INSTALLER USER MAINTENANCE TECHNICIAN N B assemble the e bars without fully tight ening the nuts aa STD 005441 000...

Страница 23: ...23 1 21 z 7 7 7 7 8 8 8 8 8 8 8 8 8 aa ab c ab z aa ab z aa ab o o ab c z aa z aa INSTALLER USER MAINTENANCE TECHNICIAN Assemble the rear vertical mount sequences 7 and 8 STD 005441 000...

Страница 24: ...24 1 22 9 a 10 10 10 9 10 a a ab z aa aa z a ab INSTALLER USER MAINTENANCE TECHNICIAN Fix the frame to the two frame structure bars a STD 005441 000...

Страница 25: ...11 12 12 12 12 12 12 12 12 z aa ab aa z ab ab aa z c aa z c 1 23 INSTALLER USER MAINTENANCE TECHNICIAN Assemble the rear mount to the frame and to the two horizontal cross members Sequences 11 and 12...

Страница 26: ...26 13 ab 13 14 14 14 14 14 14 14 14 z aa z aa ab z aa ab ab aa z n n 1 24 INSTALLER USER MAINTENANCE TECHNICIAN Fix the two frame reinforcement bars n se quence from 13 to 14 STD 005441 000...

Страница 27: ...le device for the type of surface on which installation must be carried out After positioning the manifold j as shown in the figure slide the upper mount bar e down until it touches the manifold itsel...

Страница 28: ...ENANCE TECHNICIAN Position the storage tank k on the two calen dered plates i selecting the most suitable hole on the basis of the inclination of the slope At the end of installation the upper fitting...

Страница 29: ...v p p r w INSTALLER USER MAINTENANCE TECHNICIAN N B the safety valves v and w must be mounted in a way that any emission of steam caused by overheating of the system does not cause damage to objects o...

Страница 30: ...30 1 30 25 y 27 25 27 29 28 26 28 29 m y q u q y l y u 26 29 x 29 x INSTALLER USER MAINTENANCE TECHNICIAN STD 005441 000...

Страница 31: ...TIONAL This kit allows you to install a bypass on the DHW circuit of a storage tank unit with natural circulation to keep it from freezing during the winter season see the relative instruction sheet G...

Страница 32: ...idues of braze welding Successively perform the sealing test When installation has been completed fill the cir cuit using the hole on the top of the tank remove the 3 4 cap located near the flange To...

Страница 33: ...yearly cleaning and maintenance contract with an authorised local company The frequency and methods of maintenance on the Immergas Solar Systems leave any control and maintenance obligations prescribe...

Страница 34: ...ircuit and DHW circuit Checksealingoftheassemblyelements screws bolts plugs structure elements etc Check that the system is in good condition Vent Any air present in the system must be bled upon start...

Страница 35: ...35 STD 005441 000...

Страница 36: ...S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 042024ENG rev ST 003657 000 07 18 Inglese per IRLA...