Immergas 3.029368 Скачать руководство пользователя страница 35

35

3-13

INS

TALLER

US

ER

MAINTEN

AN

CE TECHNI

CI

AN

3.15 "CHIMNEY SWEEP" FUNCTION.

This function allows the technician to check 

the combustion parameters. Boiler operation in 

chimney sweep function can be adjusted to an 

output between 0% and 100%.

To enable the function press and hold down “A”

If there is a common flow probe, it is possible 

to activate the chimney sweep function by 

pressing buttons “A” and “B” simultaneously. In 

this case, the plant pump is activated as well as 

the boiler (in the “simple cascade” both boilers 

are activated) 

The output is adjusted from the + and - DHW 

adjustment buttons at a range between 0 and 

100%, while using the + and - buttons for CH 

adjustment, the percentage changes by 1% each 

time they are pressed.

In this state all adjustments are excluded and 

only the temperature safety thermostat and the 

limit thermostat remain active. When the checks 

are finished, disable the function by pressing 

and holding down button “A” (Or A + b in the 

other case).
If you enable the function when there is no active 

request, you will need to wait approximately 30’’ 

to reach the set output. If you enable the function 

when there is an active request, you will need 

to wait approximately 3 minutes to reach the 

set output.

If you enable the function, you will need to wait 

approximately 30’’ to reach the set output (3’ on 

the Slave boiler)

3.16 3-WAY PUMP ANTI-BLOCK 

FUNCTION (OPTIONAL).

The boiler has a function that starts the pump 

and 3-way valve at least once every 24 hours for 

the duration of 20 seconds in order to reduce 

the risk of the pump becoming blocked due to 

prolonged inactivity.

3-8

3.17 RADIATORS ANTI-FREEZE 

FUNCTION.

The boiler has a function that makes the pump 

start when the system flow water reaches 8 °C. If 

the system flow water is at a temperature below 

5 °C, the boiler starts to operate until it reaches 

approximately 16 °C.

3.18 ANTI-HUMIDITY ELECTRODE 

FUNCTION.

With cascade installations combined with their 

relative flue manifold kits with flue adjusting 

devices, humidity may develop on the electrodes, 

causing them to fail. Avoid the formation of 

humidity by enabling this function (by setting 

a value other than 0), which turns the fan on 

at the speed set in parameter “P11” (5 minutes 

on and 5 minutes off). The function is active 

when the burner is off and the flow NTC probe 

temperature reading is greater than 35°C. The 

function is disabled when the temperature drops 

below 30 °C.

3.19 INLET 0 ÷ 10 V.

The microprocessor has an analogue 0 ÷ 10 V 

inlet (“Y” and “Z” terminals Fig. 1-4) that enables 

the boiler to be controlled from the outside.

By setting the “P37” parameter, it is possible 

to set-up the inlet by choosing the functioning 

mode between temperature set and power set.

The inlet activates a 2 V (minimum) request and 

increases it proportionally up to 9.5 V (max-

imum). The request is deactivated below 1 V.

Notes:

- If “P37” is set at “0”, it is not active when the 

boiler is in “stand-by” or “summer” mode.

The calculated set is limited by the “P02” ÷ 20 °C 

range. The maximum and minimum temperature 

within the set is limited by “P01” and “P32”.

- If “P37” is set on “1” it is always active.

It is not limited by the “P08” and “P09” param-

eters and does not have priority over the DHW 

request.

- Input voltage = -2.5 ÷ 12.5 V

- Input = 200 μA

- Impedance = > 50 KΩ

3.20 FUNCTIONING WITH COMMON 

FLOW PROBE.

With a hydraulic circuit breaker, there must be 

a common flow probe (with boiler flow probe 

functions) and a pump to be connected down-

stream of the plant.

The probe must be connected to terminals “S1” 

and “S2” and parameter “P38” must be set up, 

whereas the pump must be connected to termi-

nals “C” and “D”.

If there is a DHW circuit, it can be connected 

via an external 3-way to be connected to “IT”, 

“IS” and IK terminal, or use a suitable pump to 

be connected to “IT” and “IK” terminals. The 

DHW circuit has priority over the heating circuit.

Please refer to chart Fig. 3-13 for the correct 

configuration

3.21 AUTODETECTION.

This function enables the association of the 

display board to the boiler’s P.C.B. In addition, 

in case of “simple cascade” installation, it enables 

the detection and combination of cascade boilers.

Turn the boiler on, programme it according to 

your needs, press and hold the “-” (Fig. 2-1 ref. 

2) button down until “AUTO” appears, then press 

“RESET” until “bu 1” appears. 

3.22 SIMPLE CASCADE (MAX. 2 

BOILERS)

It is possible to create a “simple cascade” by 

directly connecting two boilers.

The two boilers turn on alternatively based on 

the plant’s requirements.

Carry out the connection as indicated in the 

diagram (Fig. 3-6). With this configuration, 

there must be a common flow probe on the 

thermal plant, see the chart (Fig. 3-13) for the 

possible options.

In order for the system to recognise the two 

boilers, you must activate the Autodetection and 

make sure both boilers are on.

They are associated when “bu 2” appears on 

the Master boiler and “SLA 2” appears on the 

Slave boiler.

From this moment on, all programming is car-

ried out on the Master boiler, while the “SLA 2” 

caption always appears on the Slave boiler, except 

in case of anomaly.

The customised parameters of the Master boiler 

are automatically replicated on the Slave boiler.

Warning: it is not possible to combine the cascade 

and zone regulator to the plant in this case. It is 

possible to connect an On/Off room thermostat 

or use the 0 ÷ 10 V inlet (which must only be 

connected to the Master) to control the plant.

N° 

boilers   

Parameter “P38”

Parameter “P17”

Common flow 

probe

Boiler flow probe

Common flow probe 

present = 1     

Common flow probe 

absent = 0   

DHW pump (down-

stream the distribu-

tion manifold) = 1   

3-way valve = 0

1

X

X

No

Central heating

Domestic hot water

1

X

X

Central heating

Domestic hot water

1

X

X

Central heating

Domestic hot water

Just as 

limit thermostat

2

X

Not admitted

Central heating

Just as 

limit thermostat

2

X

X

Central heating

Domestic hot water

Just as 

limit thermostat

Содержание 3.029368

Страница 1: ...VICTRIX PRO 68 2 ErP IE Instruction and warning book 1 042849ENG 1 042849ENG...

Страница 2: ......

Страница 3: ...stablished by the Law Installation and maintenance must be performed in compliance with the regulations in force according to the manufacturer s instructions and by professionally qualified staff inte...

Страница 4: ...9 Restoring central heating system pressure 26 2 10 System drainage 26 2 11Anti freeze protection 26 2 12Case cleaning 26 2 13Decommissioning 26 3 Boiler commissioning initial check 27 3 1 Hydraulic...

Страница 5: ...dequate support if inserted correctly according to technical standards in walls made of solid or semi hollow brick or block In the case of walls made from hollow brick or block partitions with limited...

Страница 6: ...is of their electrical protection rating 1 5 ANTI FREEZE PROTECTION Minimum temperature 5 C The boiler comes standard with an anti freeze function that activates the pump and burner when the system wa...

Страница 7: ...e to restore the purity of the fuel Storage tanks in case of supply from LPG depot New LPG storage tanks may contain residual inert gases nitrogen that degrade the mixture delivered to the appliance c...

Страница 8: ...pecified by current safety standards Attention the manufacturer declines any re sponsibility for damage or physical injury caused by failure to connect the boiler to an efficient earthing system or fa...

Страница 9: ...adjuster via 2 wires Thermoregulation electrical connection Fig 1 4 Thermoregulation electrical connections must be carried out on the boiler terminal board eliminating jumper X40 Thermostat or On Off...

Страница 10: ...aled chamber and fan assisted The boiler leaves the factory with B23 configuration to change the configuration of the boiler to type C sealed chamber and fan assisted disassemble the 80 adapter the br...

Страница 11: ...1 3 m Terminal complete with vertical ex haust 80 Exhaust m 3 DUCT TYPE Equivalent length in m of concentric pipe 80 125 Concentric pipe 80 125 m 1 1 0 m Concentric bend 90 80 125 1 9 m Concentric ben...

Страница 12: ...a concentric bend coupling in order to ensure sufficient space to carry out the tests required by law upon commissioning External grid The intake exhaust terminal if properly installed is pleasant to...

Страница 13: ...to the relevant groove Fix it to the lid using the previously disassembled sheet steel plate 3 Installation of the fake aluminium tile replace the tiles with the aluminium sheet 5 shaping it to ensure...

Страница 14: ...mum length MAX L Fig 1 15 The kit with this configuration can be extended up to a max measurement of 28 0 m with Victrix Pro 68 2ErP including the terminal Using the 80 vertical terminal for direct di...

Страница 15: ...al 3 and external 4 wall sealing plate has been fitted This will ensure sealing and joining of the elements making up the kit Horizontal kit 80 with exhaust in flue Kit assembly Fig 1 21 install the 8...

Страница 16: ...the end of work and on commissioning of the ducted system The instructions in the project or technical report must likewise be followed in cases provided for by the standard and current technical reg...

Страница 17: ...n domestic hot water mode the circulator pump always runs at maximum speed Pump release If after a prolonged period of inactivity the circulation pump is blocked unscrew the front cap and turn the mot...

Страница 18: ...e 10 Flue probe 11 Condensation module 12 Air pressure switch 13 Fumes hood 14 Air intake pipe 15 Igniter 16 Heat exchanger safety thermostat manual reset 17 Heat exchanger safety thermal fuse 18 Igni...

Страница 19: ...d block circuit breaker switches andofthethermometer notsuppliedasstandard with the boiler must be set up as described in the installation instructions in compliance with theprovisionsofthe R collecti...

Страница 20: ...tral heating circuit pump CMI 1 13 Zone 2 central heating circuit pump CMI 2 14 Zone 3 direct circuit pump CD 15 Storage tank unit feeding pump 16 Zone 1 safety thermostat CMI 1 17 Zone 2 safety therm...

Страница 21: ...eze is not used b shut off all electrical water and gas supplies N B in the case of maintenance interventions on the boiler that lead to the closure of one or both system cut off cocks the boiler must...

Страница 22: ...indicates a base value at which the system has been designed and calculated and however not less than 0 5 bar Open the gas cock upstream from the boiler Turn the main switch and the boiler runs a self...

Страница 23: ...If a certain amount of time lapses without saving the value the boiler will exit setting mode and maintain the previous setting Stand by mode by pressing buttons A and C at the same time it is possib...

Страница 24: ...error may be caused by a failure in one of the two probes Press the Reset button 1 0A18 Flow and return NTC probe temperature detection incorrect If the board detects a sudden drop in temperature on o...

Страница 25: ...ct on the flue NTC probe 2 1 0E81 Flow and return NTC probe temperature detection incorrect in stand by With the boiler in stand by the board detects an anomalous difference between the NTC probe flow...

Страница 26: ...drained completely or antifreeze substances must be added to the heating system water In systems that are drained frequently filling must be carried out with suitably treated water to eliminate hardn...

Страница 27: ...ction ing of fans check that the intake and or exhaust terminals are not blocked ensure activation of all adjustment devices seal the gas flow rate regulation devices if settings are modified check se...

Страница 28: ...h X90 Boiler configuration jumper Y1 Gas valve Z1 Anti jamming filter 1 External reset optional Configure the corresponding parameters when connecting in simple cascade or when con necting in system s...

Страница 29: ...DIAGRAM Key A2 Electronic board A4 Display board B1 Flow probe B1 2 System side flow probe optional B2 Domestic hot water probe optional B4 External temperature probe optional B5 Return probe B10 Flue...

Страница 30: ...2 Domestic hot water probe NTC optional B4 External probe optional M2 Plant CH pump optional M30 3 way valve optional Note probe B1 2 B2 B4 Connection cable diameter 3 7 mm Cable section 0 5 1 5 mm2 1...

Страница 31: ...tage of CO2 in flue gases The over temperature safety thermostat the flow probe or the return probe are triggered frequently It can depend on the lack of water in the boiler little water circulation i...

Страница 32: ...urve optional 0 disabled probe 0 10 0 P15 External probe offset This defines the CH offset in relation to the selected external probe curve 20 70 C 30 C P16 DHW set This defines the DHW temperature 35...

Страница 33: ...er takes priority in relation to the value set from the pushbutton panel P33 Antifreeze function activated by the common flow probe It activates the antifreeze function launched by the common flow pro...

Страница 34: ...gas circuit N B all boiler adjustment operations must be carried out by a qualified technician e g Immergas After Sales Assistance 3 12 ADJUSTMENT OF THE AIR GAS RATIO Calibration of minimum CO2 Turn...

Страница 35: ...e request is deactivated below 1 V Notes If P37 is set at 0 it is not active when the boiler is in stand by or summer mode The calculated set is limited by the P02 20 C range Themaximumandminimumtempe...

Страница 36: ...replaced at least every two years regardless of their state of wear Check that the burner is intact that it has no deformations or cuts and that it is properly fixed to the combustion chamber lid oth...

Страница 37: ...to de tach it from the central hooks and then slide it downwards take the two clamping screws out 4 from the control panel with their rings 5 press the two side hooks 7 and tilt the control panel 6 re...

Страница 38: ...38 3 15 1 6 8 9 9 12 12 10 11 13 13 13 13 A A Rif A 7 7 INSTALLER USER MAINTENANCE TECHNICIAN Ref A...

Страница 39: ...41 5370 4 71 5320 57 0 49020 6 19 5260 4 54 5210 55 0 47300 5 97 5140 4 38 5100 53 0 45580 5 75 5030 4 22 4980 51 0 43860 5 54 4910 4 06 4860 49 0 42140 5 32 4780 3 91 4740 47 0 40420 5 10 4660 3 75 4...

Страница 40: ...ue flow rate at min heat output kg h 13 13 CO2 at Q Nom Min 9 85 8 95 10 60 9 75 CO with 0 O2 at Nom Min Q Nom Min ppm 240 1 180 2 NOX at 0 of O2 at Q Nom Min mg kWh 81 5 58 4 Flue temperature at nomi...

Страница 41: ...0 Nom Min 107 3 107 2 Heat loss at casing with burner On Off 80 60 C 0 39 0 80 Heat loss at flue with burner On Off 80 60 C 0 01 1 9 Central heating circuit max operating pressure bar 6 0 Central heat...

Страница 42: ...Md Model code Sr N Serial Number CHK Check Cod PIN PIN code Type appliance configuration ref CEN TR 1749 Qnw min Minimum DHW heat input Qn min CH minimum heat input Qnw max DHW maximum heat input Qn...

Страница 43: ...eat output in high tempera ture mode 4 87 4 At 30 of nominal heat output in a low temperature mode P1 20 9 kW At 30 of nominal heat output in a low temperature mode 1 95 9 Auxiliary electricity consum...

Страница 44: ...n for the domestic hot water function AEC Yearly fuel consumption for the domestic hot water function AFC Seasonal room heating yield s 91 Domestic hot water production yield wh For proper installatio...

Страница 45: ...Supplementary heat pump From fiche of heat pump Solar contribution and Supplementary heat pump Select smaller value Boiler and supplementary heat pump installed with low temperature heat emitters at...

Страница 46: ...The energy efficiency of the package of products provided far in this fiche may not correspond to its actual energy efficiency once installed in a building as the efficiency is influenced by fur ther...

Страница 47: ...contribution From fiche of solar device 1 I 2 1 1 x I 10 x II III I Auxiliary electricity 3 G F E D C B A A A A 27 27 27 28 27 27 27 28 30 30 30 32 33 34 35 36 36 37 38 40 39 50 55 60 65 75 80 85 100...

Страница 48: ...ncy under colder and warmer climate conditions Colder 0 2 x Warmer 0 4 x Declared load profile Solar contribution From fiche of solar device 1 ___ 2 1 1 x ___ 10 x ___ ____ ____ Auxiliary electricity...

Страница 49: ...49...

Страница 50: ...50...

Страница 51: ...51...

Страница 52: ...mmergas S p A 42041 Brescello RE Italy Tel 0522 689011 Fax 0522 680617 Certified company ISO 9001 This instruction booklet is made of ecological paper Cod 1 042849ENG rev ST 003901 000 01 19 Inglese p...

Отзывы: