I l l u s i o n - A u s t r a l i a n M a d e G a s L o g F i r e s
INSTALLATION OPTION 1
INTO FABRICATED ENCLOSURE VERTICALLY ONLY
IMPORTANT:
THE FITTING OF ANY
ENCLOSURE PANEL
OVER THE HEATER,
AND OR BETWEEN
THE HEATER AND THE
CEILING PANEL
IS NOT PERMITTED.
ANY HORIZONTAL OR
VERTICAL SUPPORT
TIMBERS MUST NOT
EXCEED 100mm IN
WIDTH AND MUST NOT
BE CLOSER THAN 70mm
TO THE TOP OF THE
HEATER CASE.
PLEASE NOTE:
ALL ILLusion GAS
LOG FIRES MUST BE
INSTALLED BY AN
AUTHORISED PERSON
IN ACCORDANCE WITH
AS/NZS 5601
CURRENT EDITION
FIRST LENGTH OF
ACTIVE FLUE PIPE
IS STAINLESS STEEL.
ALL OTHERS ARE GALVANISED
The maximum recommended
fl ue length is 3.6m
The recommended minimum distance
from the top of the heater to the
underside of ay timber framing is
70mm provided that the gap between
any active fl ue pipe and any timber
or combustible material is a minimum
of 25mm, or the gap between any
fl ue outer case and any timber or
combustible material is a minimum of
10mm. Standoffs are provided on the
top of the appliance body to ensure no
framing timbers can come in contact
with the appliance body.
NOTE: All fl ue pipes
including active inner
and any outer cases
mustbe installed with
the crimped end of the
pipe facing up.
Plaster or similar
faced wall with
timber framing