24
Technical data of IGLU Aleut 11 fixed capacity heat pump
Model
IGLU Aleut 11
Air-to-water heat pump
No
Water-to-water heat pump
No
Ground-to-water heat pump
Yes
Low temperature heat pump
No
Equipped with supplementary heater
No
Supplementary heater is used
No
Parameters applied using average temperature are declared. Parameters are declared under average climatic
conditions.
Parameter
Conventional
representation
Value
Measurement
unit
Parameter
Conventional
representation
Value
Measurement
unit
Rated thermal power
P
rated
10.95 kW
Seasonal energy
efficiency for space
heating
η
s
150
%
Declared part load heating capacity at
20 °C indoor
temperature and outdoor temperature T
j
Declared efficiency coefficient or ratio of primary energy
to radiant heat output at room temperature 20 °C and
outdoor temperature T
j
T
j
=
– 7 °C
P
dh
11.56 kW
T
j
=
– 7 °C
COP
d
arba
PER
d
5.69
–
T
j
= + 2
°C
P
dh
11.60 kW
T
j
= + 2
°C
COP
d
arba
PER
d
5.75
–
T
j
= + 7
°C
P
dh
11.65 kW
T
j
= + 7
°C
COP
d
arba
PER
d
5.89
–
T
j
= + 12
°C
P
dh
11.87 kW
T
j
= + 12
°C
COP
d
arba
PER
d
6.08
–
T
j
= (T
biv
)
- bivalent
temperature mode
P
dh
-
kW
T
j
= (T
biv
)
- bivalent
temperature mode
COP
d
arba
PER
d
–
–
T
j
= operating limit
temperature
P
dh
-
kW
T
j
= operating limit
temperature
COP
d
arba
PER
d
–
°C
Air-to-water heat pump:
T
j
= -
15°C
(where TOL <-
20°C)
P
dh
-
kW
Air-to-water heat pump:
T
j
= -
15°C
(where TOL <-
20°C)
COP
d
arba
PER
d
-
Bivalent temperature
T
biv
-
°C
Air-to-water heat pump:
operating limit
temperature
TOL
-
°C
Power in cyclic heating
mode
P
cych
-
kW
Cyclical efficiency
COP
cyc
or
PER
cyc
-
– or %
Decreased efficiency in
cyclic mode
C
dh
0.99
—
Heating water limit
operating temperature
WTOL
60
°C
Power consumption in modes other than active mode
Supplementary heater
Off mode
P
OFF
0.009 kW
Rated thermal power
P
sup
-
kW
Thermostat-off mode
P
TO
0.009 kW
Type of energy input
Electricity
Standby mode
P
SB
0.064 kW
Crankcase heater mode
P
CK
-
kW
Other parameters
Capacity control
fixed
Air-to-water heat pump:
rated air flow rate,
outdoor
—
m
3
/h
Sound power level,
indoors/outdoors
L
WA
42
dB
Ground-to-water heat
pump: water flow,
outdoor heat exchanger
3.0
m
3
/h
Emissions of nitrogen
oxides
NO
x
-
mg/kWh
Contact details
IGLU TECH UAB Ozo str. 12A-1, Vilnius, Lithuania