SELECTION OF THE INSTALLATION PLACE 

 

 

When  choosing  the  installation  place  of  the  heat  pump,  keep  in  mind  that  the  heat  pump 

produces a certain level of noise (see table “Heat pump technical data”). 

 

The device must be mounted on a flat and stationary surface with a permissible load of at least 

500 kstr. Minor surface irregularities can be compensated by adjusting the feet of the device.  

 

The ambient temperature near the heat pump must be between 10°C and 35°C, and the relative 

humidity must not exceed 80%. 

 

There must be no aggressive chemicals in the environment. 

 

The  heat  pump  should  not  be  installed  close  to  walls;  the  front  of  the  unit  should  always  be 

accessible (see, Annex No 6). 

 

A drainage system must be provided in the room where the unit is installed. In this case, leaking 

water can be drained. 

 

Do not use extra platforms. 

 

PRELIMINARY PREPARATION OF THE PIPELINES 

 

The connecting pipes for the outdoor circuit, the heating circuit and, if provided, the hot water 

circuit must be laid up to the intended location of the heat pump. Install an expansion vessel, safety 
valves,  coarse  suction  filters  and  pressure  gauges  for  the  outdoor,  heating  circuit  and  boiler.  The 
circuits must have a provided filling point. 

 

OUTDOOR CIRCUIT 

Installation and filling

 

 

The  outdoor  circuit  can  be  vertical  (boreholes)  or  horizontal.  The  horizontal  circuit  must  be 

installed  below  the  freezing  zone,  depending  on  the  ground  of  the  installation  site.  Fill  the  outdoor 
circuit with glycol, which ensures that it does not freeze in temperatures up to -15

o

C. 

Do not use the 

salt-based solution.

 The following fluids are approved for the outdoor circuit: 

• monoethylene glycol; 
• propylene glycol. 
 

It is recommended to use a mixture of water and monoethylene glycol concentrate in a ratio of 
3:1.  

The applicable rules and regulations must be observed when  installing and filling the outdoor 

circuit. There must be no stones or sharp objects in the ground where the outdoor circuit is installed 
that could damage the pipes. Prior to filling the system, make sure that the system is tightly sealed. 

When installing the outdoor circuit, it is necessary to protect the pipes from penetration of dirt 

or gravel. If the system is dirty, the heat  pump may become clogged and individual components  of 
the device may be damaged or corrupted.  

 

Filling and circulating unit 

 

The outdoor system refiller must be installed next to the circuit inlet so that the system can be 

replenished  when  the system  pressure drops  and  the  external and  glycol  mixing  procedure  can be 
performed  when  filling  the  outdoor  circuit. 

The  filling  unit  is  not  included  in  the  heat  pump 

package. 

Содержание Aleut 11

Страница 1: ...INSTALLATION MANUAL IGLU Aleut Series...

Страница 2: ...lling 8 THERMAL INSULATION 9 ELECTRICAL CONNECTION WORKS 9 Temperature sensors 10 Characteristics of temperature sensors NTC 10K 10 Phase sequence relay 10 Control panel 11 START OF OPERATION 11 HEAT...

Страница 3: ...iler 28 Technical data of IGLU Aleut 11 WT fixed capacity heat pump with boiler 29 Technical data of IGLU Aleut 13 WT fixed capacity heat pump with boiler 30 Technical data of IGLU Aleut 18 WTI heat p...

Страница 4: ...tall the devices Treat all constituents responsibly The heat pump may only be used for its intended purpose which means heating domestic hot water preparation coolinstr The device can only be operated...

Страница 5: ...vice and its components may only be carried out by qualified specialists heating refrigeration coolant technicians and electricians WARNING Observe the safety signs on and inside the device WARNING Th...

Страница 6: ...OUTDOOR CIRCUIT Installation and filling The outdoor circuit can be vertical boreholes or horizontal The horizontal circuit must be installed below the freezing zone depending on the ground of the ins...

Страница 7: ...RCUIT To avoid gas formation it is recommended not to use galvanised pipe systems WARNING The area of the domestic hot water tank heat exchanger must correspond to the capacity of the heat pump The wa...

Страница 8: ...e system The presence of air in the system produces corrosive products such as magnetite or sediment Magnetite has an abrasive effect that is especially enhanced in pumps valves or eddy flow component...

Страница 9: ...ecial means of thermal insulation in accordance with current standards The main normative document which defines the requirements for thermal insulation is Order No 1 245 of the Minister of Energy of...

Страница 10: ...5 0 262 20 0 96360 60 0 2490 140 0 232 15 0 72502 65 0 2084 145 0 206 10 0 55047 70 0 1753 150 0 183 5 0 42158 75 0 1481 155 0 163 0 0 32555 80 0 1256 160 0 145 5 0 25339 85 0 1070 165 0 130 10 0 1987...

Страница 11: ...ce with the requirements of this operating manual the electrical installation works have been properly performed the heating circuit has been flushed and properly filled all valves and shut off device...

Страница 12: ...r to vandens vo tuvas V sinimo vo tuvas NO5 C4 C5 C3 NO3 Boilerio teno rel NO5 C5 NC5 COM DI1 A1 13 KU1 13 14 Operatoriaus panel CAN RJ COM P1 P2 X1 1 X1 2 X1 6 X1 5 X1 4 X1 3 M M2 M M3 KM1 A2 F1 14 X...

Страница 13: ...omatinio jungiklio Kambario temp daviklio gnybt rinkl s Boilerio temp daviklio gnybt rinkl s Kabelinis latakas Element tvirtinimo plok t Heat pump inlet from a separate circuit breaker Neutral termina...

Страница 14: ...mperature medium The manufacturer recommends the use of underfloor heating for this connection method Each heat pump has the ability to connect to the Internet so you can see the heat pump settings an...

Страница 15: ...l flowing from the outdoor circuit during the warm season The outdoor circuit cannot be used for cooling and heating at the same time Each heat pump has the ability to connect to the Internet so you c...

Страница 16: ...nk up to 30 of the heating circuit can be closed at the same time Variable capacity heat pumps do not require buffer capacity Each heat pump has the ability to connect to the Internet so you can see t...

Страница 17: ...Variable capacity heat pumps do not require buffer capacity For fan radiators additional pipes must be laid from the outdoor circuit to which they will be connected via a three way valve The outdoor c...

Страница 18: ...essure bar 45 Heating system Rated flow DT 7K m3 h 1 00 1 50 2 00 2 00 2 20 Min flow temperature C 15 Max flow temperature C 60 Max permissible operating pressure bar 4 0 Connection Cu mm 28 Power net...

Страница 19: ...Rated flow DT 7K m3 h 1 00 1 50 2 00 2 00 2 20 Min flow temperature C 15 Max flow temperature C 60 Max permissible operating pressure bar 4 0 Hot water tank volume l 200 Capacity material Stainless s...

Страница 20: ...85 1 32 4 43 Compressor power 60 rps kW 13 00 2 84 4 58 Compressor power 85 rps kW 18 60 4 32 4 31 Compressor Type Scroll Mass of refrigerant R410A kg 2 20 Maximum pressure bar 45 Heating system Hot...

Страница 21: ...5 64 Tj 7 C Pdh 5 72 kW Tj 7 C COPd or PERd 5 71 Tj 12 C Pdh 5 81 kW Tj 12 C COPd or PERd 5 85 Tj Tiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd or PERd Tj operating limi...

Страница 22: ...2 C Pdh 7 92 kW Tj 12 C COPd arba PERd 5 84 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit temperatu...

Страница 23: ...2 C Pdh 9 82 kW Tj 12 C COPd arba PERd 5 85 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit temperatu...

Страница 24: ...j 12 C Pdh 11 87 kW Tj 12 C COPd arba PERd 6 08 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit tempe...

Страница 25: ...j 12 C Pdh 14 05 kW Tj 12 C COPd arba PERd 6 24 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit tempe...

Страница 26: ...71 Tj 12 C Pdh 5 81 kW Tj 12 C COPd arba PERd 5 85 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit te...

Страница 27: ...74 Tj 12 C Pdh 7 92 kW Tj 12 C COPd arba PERd 5 84 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit te...

Страница 28: ...79 Tj 12 C Pdh 9 82 kW Tj 12 C COPd arba PERd 5 85 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit te...

Страница 29: ...5 89 Tj 12 C Pdh 11 87 kW Tj 12 C COPd arba PERd 6 08 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit...

Страница 30: ...5 98 Tj 12 C Pdh 14 05 kW Tj 12 C COPd arba PERd 6 24 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd arba PERd Tj operating limit temperature Pdh kW Tj operating limit...

Страница 31: ...Tj 12 C Pdh 12 80 kW Tj 12 C COPd or PERd 5 71 Tj Tbiv bivalent temperature mode Pdh kW Tj Tbiv bivalent temperature mode COPd or PERd Tj operating limit temperature Pdh kW Tj operating limit tempera...

Страница 32: ...PM3 K FLEX AS 25 75 180 UPM3 K FLEX AS 25 75 180 IGLU Aleut 9 WT 9 KW UPM3 K FLEX AS 25 75 180 UPM3 K FLEX AS 25 75 180 IGLU Aleut 11 WT 11 KW UPM3 K FLEX AS 25 75 180 UPMXL 25 125 180 PWM IGLU Aleut...

Страница 33: ...33 Annex No 3 UPM3 K FLEX AS 25 75 180 characteristic UPM3 K FLEX AS 25 75 180 electrical parameters 1 x 230 V 50 60 Hz Speed P1 W I1 A Min 2 0 04 Max 60 0 58 Dimensions of the UPM3 circulation pump...

Страница 34: ...o 4 UPMXL GEO 25 125 180 PWM 1 x 230 V 50 60 Hz characteristics UPMXL GEO 25 125 180 PWM electrical parameters 1 x 230 V 50 60 Hz Speed P1 W I1 A Min 3 0 06 Max 180 1 4 Dimensions of the UPMXL circula...

Страница 35: ...inan io glikolio pajungimo atvamzdis E i einan io glikolio pajungimo atvamzdis F G angos elektrini pajungim kabeliams Where A supply heating water connection nozzle B nozzle of heating water supplied...

Страница 36: ...Annex No 6 Design dimensions of the heat pump from the front Design dimensions of the heat pump from the top 120cm 180cm 62cm 62cm 5cm 5cm 62cm 62cm 80cm 80cm 62cm 80cm 80cm 5cm 62cm 62cm 120cm 180cm...

Страница 37: ...__________________________________________ _____________________________________________________________ _____________________________________________________________ _________________________________...

Отзывы: